- Electrical Durability
- 7000 cycle60 cycles per hour
- Mechanical Durability
- 20000 cycle120 cycles per hour
- Number of Poles
- 3
- Power Loss
- at Rated Operating Conditions per Pole 10.6 W
- Product Main Type
- SACE Tmax T
- Product Name
- Moulded Case Circuit Breaker
- Product Type
- Automatic Circuit Breaker
- Rated Current (In)
- 320 A
- Rated Impulse Withstand Voltage (Uimp)
- 8 kV
- Rated Insulation Voltage (Ui)
- 1000 V
- Rated Operational Voltage
- 690 V AC
- Rated Service Short-Circuit Breaking Capacity (Ics)
- (220 V AC) 100 kA(230 V AC) 100 kA(380 V AC) 70 kA(400 V AC) 70 kA(415 V AC) 70 kA(440 V AC) 65 kA(500 V AC) 50 kA(690 V AC) 40 kA
- Rated Short-time Withstand Current Low Voltage (Icw)
- for 1 s 5 kA
- Rated Ultimate Short-Circuit Breaking Capacity (Icu)
- (220 V AC) 100 kA(230 V AC) 100 kA(380 V AC) 70 kA(400 V AC) 70 kA(415 V AC) 70 kA(440 V AC) 65 kA(500 V AC) 50 kA(690 V AC) 40 kA
- Rated Uninterrupted Current (Iu)
- 400 A
- Release
- PR222DS/P-LSI
- Release Type
- EL
- Short-Circuit Performance Level
- H
- Standards
- IEC
- Sub-type
- T5
- Suitable For
- T5
- Suitable for Product Class
- Moulded Case Circuit Breakers
- Terminal Connection Type
- Fixed Circuit-BreakersFront
- Test Voltage Max (Utest)
- 3500 V
- Version
- F