- Rated Operational Voltage
- 208 ... 600 V AC
- Rated Control Supply Voltage (Us)
- 100 ... 250 V AC
- Rated Control Circuit Voltage (Uc)
- 24 V DC
- Rated Frequency (f)
- 50/60 HzMain Circuit 50 / 60 Hz
- Rated Operational Power - In-Line Connection (Pe)
- (230 V) 30 kW(400 V) 55 kW(500 V) 75 kW
- Rated Operational Current - In-Line Connection (Ie)
- 106 A
- Service Factor Percentage
- 100 %
- Overload Protection
- Build-in electronic overload protection
- Integrated Electronic Overload
- Yes
- Adjustable Rated Motor Current Ie
- 30 ... 100 %
- Starting Capacity at Maximum Rated Current Ie
- 4xIe for 10s
- Ramp Time
- 0 ... 30 second [unit of time]1 ... 30 second [unit of time]
- Initial Voltage During Start
- 30 ... 70 %
- Step Down Voltage Special Ramp
- No %
- Current Limit Function
- 1.5 ... 7xIe
- Switch for Inside Delta Connection
- No
- Run Signal Relay
- Yes
- By-pass Signal Relay
- Yes
- Fault Signal Relay
- Yes
- Overload Signal Relay
- Yes
- Analog Outputs
- 4…20 mA
- Signal Indication Completed Start Ramp (LED)
- Green
- Signal Indication Ready to Start/Standby ON (LED)
- Green
- Signal Indication Running R (LED)
- Green
- Signal Indication Ramping Up/Down (LED)
- Green
- Signal Indication Protection (LED)
- Yellow
- Signal Indication Fault (LED)
- Red
- Number of Starts Per Hour at 3.5*Ie for 7 sec. 50% ON Time 50% OFF Time
- 10
- Communication
- Modbus-RTU
- Degree of Protection
- IP00
- Terminal Type
- Screw Terminals
- Connecting Capacity Main Circuit
- Hole Diameter 8.5 mmRigid 1/2 x 2.5 ... 70 mm²Width and Thickness 17.5x5 mm
- Connecting Capacity Control Circuit
- Rigid 1 x 2.5 mm²Rigid 2 x 1.5 mm²
- Connecting Capacity Supply Circuit
- Rigid 1 x 2.5 mm²
- Tightening Torque
- Control Circuit 0.5 N·mMain Circuit 9 N·mSupply Circuit 0.5 N·m
- Product Main Type
- PSE105
- Function
- Soft start with torque controlSoft start with voltage rampSoft stop with torque controlSoft stop with voltage rampKick startSequence startCurrent limitStart reverse (external contactors)Automatic restartEvent log
- Protection Function
- Electronic overload protection, EOL; Locked rotor protection; Current underload protection