Beschreibung

Mersen fuses for the protection of transformers and distribution lines deliver overload and short circuit protection. These current-limiting fuses will melt at current that can be as low as 1.7 times the fuse current ratings up to its maximum interrupting rating. These fuses are designed to withstand the transformer magnetizing inrush current. They have 2" (size C), 3" (size D) and 2x3" (size DD) inch diameter barrels with ferrules and are mounted in spring reinforced clips.
Country of Origin
MX
Part Number
9F62DDD080
UPC
782001395810
  • Erhalten Sie bis zu 90 Tage Zahlungsziele von 500+ Lieferanten
  • Wiederverkaufsrabatte bis zu 40%!
Sign-Up
Preisanfrage senden
1
Zahlungsmöglichkeiten:
Fordern Sie ein Angebot an und wir senden Ihnen Informationen zu Verfügbarkeit und Preis.

Specifications

Blown-fuse indicator to give positive identification of open fuse
Amp-Trap
Max Operating Temp
80 °C
Max Storage Temp
80 °C
Min Storage Temp
-25 °C
Ampere Rating
80 A
Rated Voltage Ac Ul
15500 V
Ac Max I R Breaking Capacity I1
50 kA
Product Diameter
3 in
Country Of Origin
MX
Product Line
15.5kV Ferrule Mount Transformer Fuses
Product Brand
Amp-Trap®
Body Insulating Material
Epoxy
Connection Terminal Material
Silver-Plated Copper
Connection Terminal Type
Ferrule
Speed Characteristic
E-Rated
Mounting
Clip