Mersen

NH3GG50V300-1

1 / 1
thumbnail

Beschreibung

The NH system is classified among plug-in fuse systems and is composed of: fuse-base (possibly including terminal covers and phase barriers) fuse-link with blade contact fuse-link replacement device (LV HRC fuse puller) Since the design of this system cannot guarantee non-interchangeability of rated current it must be handled by a qualified professional. Type gG NH fuse-links are full range breaking capacity fuse-links and are used to protect cables and equipment. They can interrupt any current surge, from the lowest fusing current up to their breaking capacity, and so can be used alone as protection. They also protect electrical devices and industrial set-ups from the electrodynamic effects of very high short-circuit currents.
Part Number
NH3GG50V300-1
  • Erhalten Sie bis zu 90 Tage Zahlungsziele von 500+ Lieferanten
  • Wiederverkaufsrabatte bis zu 40%!
Sign-Up
Preisanfrage senden
1
Zahlungsmöglichkeiten:
Fordern Sie ein Angebot an und wir senden Ihnen Informationen zu Verfügbarkeit und Preis.

Product Details

Ampere Range
2 - 630 A
Lead Free
Consult Technical Services
Size per Standard
000 00 0 1 2 3
Standards
VDE 0636 Part 201 IEC 60269-1 and -2
Speed / Characteristic
gG
ROHS Compliant
Consult Technical Services
CE conformity
Yes
Body Material
Ceramic
Body Style
Square
Materials Contact
Copper, Silver-plated
Applications
gG: general purpose cable and line protection