Input data
- Sensor types (RTD) that can be used
- Sensors (2-, 3-, 4-wire)
- Temperature measuring range
- -200 °C - 850 °C (Range depending on the sensor type)
- Input signal range
- 0 Ω - 2000 Ω
- Max. permissible overall conductor resistance
- 50 Ω (Per cable)
- Sensor input current
- 200 µA - 1 mA
- Measuring range span
- min. 50 K
Note
- Utilization restriction
- EMC: class A product, see manufacturer's declaration in the download area
Dimensions
- Width
- 12.5 mm
- Height
- 116.9 mm
- Depth
- 113.7 mm
Connection data
- Connection method
- Push-in connection
- Stripping length
- 8 mm
- Conductor cross section solid
- 0.2 mm² - 1.5 mm²
- Conductor cross section flexible
- 0.2 mm² - 1.5 mm²
- Conductor cross section AWG
- 24 - 16
Output data
- Signal output
- Current output
- Configurable/programmable
- Yes
- Current output signal
- 0 mA - 20 mA
- Current output signal
- 4 mA - 20 mA
- Load/output load current output
- ≤ 500 Ω
- Output ripple (current)
- < 50 µAPP
- Behavior in the event of a sensor error
- As per NE 43 or can be freely defined
- Configurable/programmable
- no
Ambient conditions
- Ambient temperature (operation)
- -20 °C - 60 °C (Any mounting position)
- Ambient temperature (storage/transport)
- -40 °C - 80 °C
- Maximum altitude
- ≤ 2000 m
- Permissible humidity (operation)
- 5 % - 95 % (non-condensing)
- Degree of protection
- IP20 (not assessed by UL)
- Noise immunity
- EN 61000-6-2 When being exposed to interference, there may be minimal deviations.
Environmental Product Compliance
- REACh SVHC
- Lead 7439-92-1
- China RoHS
- Environmentally Friendly Use Period = 50 years
- China RoHS
- For details about hazardous substances go to tab 'Downloads', Category 'Manufacturer's declaration'
EMC data
- Designation
- Electromagnetic RF field
- Standards/regulations
- EN 61000-4-3
- Designation
- Fast transients (burst)
- Standards/regulations
- EN 61000-4-4
- Designation
- Conducted interferences
- Standards/regulations
- EN 61000-4-6
Safety data
- Max. output voltage Uo
- 6 V
- Max. output current Io
- 6.3 mA
- Max. output power Po
- 9.4 mW
- Group
- IIC
- Max. external inductivity Lo
- 100 mH
- Max. external capacitance Co
- 1.4 µF
- Additional text
- mixed circuit
- Max. external inductivity Lo
- 10 mH
- Max. external capacitance Co
- 1.9 µF
- Max. external inductivity Lo
- 1 mH
- Max. external capacitance Co
- 2.7 µF
- Group
- IIB
- Max. external capacitance Co
- 6.9 µF
- Max. external capacitance Co
- 9.4 µF
- Max. external capacitance Co
- 15 µF
- Group
- IIA
- Max. external capacitance Co
- 10 µF
- Max. external capacitance Co
- 13 µF
- Max. external capacitance Co
- 21 µF
- Safety-related maximum voltage Um
- 253 V AC (125 V DC)
Safety characteristic data
- Integrity requirement
- IEC 61508 - Low demand
- Architecture
- Single-channel, 1oo1
- Equipment type
- Type B
- Safe Failure Fraction (SFF)
- 91.3 %
- MTBF
- 119 Years
- ΛSD
- 4.61 x 10-⁷ (461 FIT)
- ΛDU
- 3.23 x 10-⁷ (323 FIT)
- ΛDD
- 3.18 x 10-⁸ (31.8 FIT)
- Probability of a hazardous failure on demand (PFDAVG)
- 1.3 x 10-⁴ (1 year)
- Probability of a hazardous failure on demand (PFDAVG)
- 2.6 x 10-⁴ (2 years)
- Probability of a hazardous failure on demand (PFDAVG)
- 3.91 x 10-⁴ (3 years)
- Probability of a hazardous failure on demand (PFDAVG)
- 6.51 x 10-⁴ (5 years)
- Probability of a hazardous failure on demand (PFDAVG)
- 9.11 x 10-⁴ (7 years)
- Probability of a hazardous failure on demand (PFDAVG)
- 1.04 x 10-³ (8 years)
- Diagnostic coverage (DC)
- 90.2 %
- Integrity requirement
- IEC 61508 - High demand
- ΛSU
- 1.5 x 10-⁷ (150 FIT)
- Probability of a hazardous failure per hour (PFHD)
- 3,23 x 10-⁸
Standards and Regulations
- Noise emission
- EN 61000-6-4
- Designation
- Electromagnetic RF field
- Standards/regulations
- EN 61000-4-3
- Standards/regulations
- EN 61000-4-4
- Designation
- Conducted interferences
- Standards/regulations
- EN 61000-4-6
- Conformance
- CE-compliant, additionally EN 61326
- ATEX
- II (1) G [Ex ia Ga] IIC/IIB
- ATEX
- II (1) D [Ex ia Da] IIIC
- ATEX
- II 3(1) G Ex nA ic [ia Ga] IIC T4 Gc X
- IECEx
- [Ex ia Ga] IIC
- IECEx
- [Ex ia Da] IIIC
- IECEx
- Ex nA ic [ia Ga] IIC T4 Gc
- UL, USA/Canada
- Class I Div 2; IS for Class I, II, III Div 1
- Group
- IIC
- Group
- IIB
Power supply
- Nominal supply voltage
- 24 V DC
- Supply voltage range
- 19.2 V DC - 30 V DC (24 V DC -20%...+25%)
- Power dissipation
- < 1 W
Andere Kategorien
NanometerManometerDurchflussmesserSensorenBeschleunigungssensorenLichtwellenleiter-SensorenDetektorenUltraschallsensorenTemperatur- und FeuchtigkeitssensorenSchwingungssensorenFüllstandssensorenDrucksensorenNäherungssensorenInduktive SensorenBewegungssensorenMagnetische Sensoren GruppeOptische SensorenKapazitive SensorenFotoelektrische SensorenPositionsgeberEncoderAndere Sensoren und Zubehör