Additional Information

Part Number
2938730
UPC
4017918899554
Country of Origin
PL

Input data

Nominal input voltage range
100 V AC - 240 V AC
Input voltage range
85 V AC - 264 V AC
Input voltage range
90 V DC - 350 V DC
AC frequency range
45 Hz - 65 Hz
Current consumption
0.7 A (120 V AC)
Current consumption
0.4 A (230 V AC)
Current consumption
0.65 A (90 V DC)
Current consumption
0.2 A (350 V DC)
Nominal power consumption
84 VA
Inrush surge current
< 15 A (typical)
Mains buffering
> 35 ms (120 V AC)
Mains buffering
> 170 ms (230 V AC)
Input fuse
2.5 A (slow-blow, internal)
Choice of suitable circuit breakers
6 A - 16 A (Characteristics B, C, D, K)

Dimensions

Width
45 mm
Height
99 mm
Depth
107 mm

Output data

Nominal output voltage
24 V DC ±1 %
Setting range of the output voltage (U<sub>Set</sub>)
22.5 V DC - 28.5 V DC (> 24 V DC, constant capacity restricted)
Nominal output current (I<sub>N</sub>)
2 A (-25 °C - 60 °C)
POWER BOOST (I<sub>Boost</sub>)
2.9 A (-25°C - 40°C permanent )
Derating
60 °C - 70 °C (2.5%/K)
Connection in parallel
Yes, for redundancy and increased capacity
Connection in series
yes
Feedback resistance
35 V DC
Protection against surge voltage on the output
≤ 35 V DC
Starting delay with capacitive load
unrestricted
Max. capacitive load
unlimited
Control deviation
< 1 % (change in load, static 10 % - 90 %)
Control deviation
< 3 % (change in load, dynamic 10 % - 90 %)
Control deviation
< 0.1 % (change in input voltage ±10 %)
Residual ripple
< 20 mVPP (20 MHz)
Output power
48 W
Typical response time
< 1 s
Peak switching voltages nominal load
< 100 mVPP (20 MHz)
Maximum power dissipation in no-load condition
2 W
Power loss nominal load max.
7 W

Connection data, input

Connection method
Pluggable screw connection
Conductor cross section solid min.
0.2 mm²
Conductor cross section solid max.
2.5 mm²
Conductor cross section flexible min.
0.2 mm²
Conductor cross section flexible max.
2.5 mm²
Conductor cross section AWG min.
24
Conductor cross section AWG max.
12
Stripping length
7 mm
Screw thread
M3

Connection data, output

Connection method
Pluggable screw connection
Conductor cross section solid min.
0.2 mm²
Conductor cross section solid max.
2.5 mm²
Conductor cross section flexible min.
0.2 mm²
Conductor cross section flexible max.
2.5 mm²
Conductor cross section AWG min.
24
Conductor cross section AWG max.
12
Stripping length
7 mm
Screw thread
M3

Ambient conditions

Degree of protection
IP20
Ambient temperature (operation)
-25 °C - 70 °C (> 60 °C Derating: 2.5 %/K)
Ambient temperature (storage/transport)
-40 °C - 85 °C
Max. permissible relative humidity (operation)
≤ 95 % (at 25 °C, non-condensing)
Climatic class
3K3 (in acc. with EN 60721)
Degree of pollution
2

Connection data for signaling

Conductor cross section solid min.
0.2 mm²
Conductor cross section solid max.
2.5 mm²
Conductor cross section flexible min.
0.2 mm²
Conductor cross section flexible max.
2.5 mm²
Conductor cross section AWG min.
24
Conductor cross section AWG max.
12
Screw thread
M3

Environmental Product Compliance

REACh SVHC
Lead 7439-92-1
China RoHS
Environmentally Friendly Use Period = 25;
China RoHS
For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration”

Standards and Regulations

Electromagnetic compatibility
Conformance with EMC Directive 2014/30/EU
Noise emission
EN 55011 (EN 55022)
Noise immunity
EN 61000-6-2:2005
Connection in acc. with standard
CUL
Standards/regulations
EN 61000-4-2
Contact discharge
8 kV
Standards/regulations
EN 61000-4-3
Frequency range
80 MHz - 1 GHz
Test field strength
10 V/m
Frequency range
1 GHz - 2 GHz
Test field strength
3 V/m
Standards/regulations
EN 61000-4-4
Comments
Criterion B
Standards/regulations
EN 61000-6-3
Standards/regulations
EN 61000-4-6
Frequency range
0.15 MHz - 80 MHz
Voltage
10 V
Standards/regulations
EN 61000-4-11
Low Voltage Directive
Conformance with LV directive 2006/95/EC
Standard - Electrical safety
EN 60950-1/VDE 0805 (SELV)
Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations
EN 50178/VDE 0160 (PELV)
Standard – Safety extra-low voltage
EN 60950-1 (SELV)
Standard – Safety extra-low voltage
EN 60204 (PELV)
Standard - Safe isolation
DIN VDE 0100-410
Standard – Limitation of mains harmonic currents
EN 61000-3-2
UL approvals
UL/C-UL listed UL 508
UL approvals
UL/C-UL Recognized UL 60950-1
UL approvals
UL ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C, D (Hazardous Location)
UL approvals
NEC Class 2 as per UL 1310
Shock
18 ms, 30g, in each space direction (according to IEC 60068-2-27)
Vibration (operation)
< 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6)
Vibration (operation)
15 Hz - 150 Hz, 2.3g, 90 min.
Rail applications
EN 50121-4