- [Ics] Rated Service Breaking Capacity
- 100 kA UL 508 A
- Ambient Air Temperature For Operation
- -40-302 °F
- Height
- 4 in
- Mounting Support
- surface mount
- Electrical Connection
- tin plated copper lugs
- Connections - Terminals
- line lug 40 lbf.in AWG 8 copper || line lug 35 lbf.in AWG 14...AWG 10 copper || line lug 120 lbf.in AWG 6...AWG 2/0 copper || load lug 35 lbf.in AWG 14...AWG 4 copper
- Wire Stripping Length
- load: 0.38 in for top connection || load: 0.75 in for bottom connection || line: 0.75 in
- Number Of Cables
- line 2 , AWG 14...AWG 2/0, copper || load 6 , AWG 14...AWG 4, copper
- Material
- phenolic: block
- Width
- 3.47 in
- Depth
- 2.61 in
- Product Compatibility
- 9080LB32
- Number Of Poles
- 2
- [Ue] Rated Operational Voltage
- 600 V AC/DC
- Number Of Terminals
- 2 load || 6 line