Schneider Electric

ATS48C25YS316

1 / 1
thumbnail
Country of Origin
ID
Part Number
ATS48C25YS316
Tariff Code
85371098
EAN
3606480621468
Zahlungsmethoden:
Bestes Angebot von:
SKVertrauenswürdiger Automa.Net Lieferant
Verfügbarkeit:
10 Stk.
Auf Lager
Aktualisiert am: 08-11-2024
Garantie:
12 Monate
Geschätzte Lieferung:
Auf Anfrage
Zustand:
Neu versiegelt ab Werk
Neu versiegelt ab Werk - Ein brandneuer, unbenutzter, ungeöffneter, unbeschädigter Artikel in seiner original vom Hersteller versiegelten Verpackung.
Sicherer Zahlungsprozess
Rückgabe- und Erstattungsrichtlinien
Versandrichtlinien
Garantiebedingungen

Specifications

Product Destination
asynchronous motors
Range Of Product
Altistart 48
Product Or Component Type
soft starter
Motor Power Kw
110 kW 400 V for severe applications || 110 kW 440 V for severe applications || 132 kW 400 V for standard applications || 132 kW 440 V for standard applications || 132 kW 500 V for severe applications || 132 kW 525 V for severe applications || 160 kW 500 V for standard applications || 160 kW 525 V for standard applications || 160 kW 660 V for severe applications || 200 kW 690 V for severe applications || 220 kW 660 V for standard applications || 250 kW 690 V for standard applications || 55 kW 230 V for severe applications || 75 kW 230 V for standard applications
Utilisation Category
AC-53A
[Us] Rated Supply Voltage
208...690 V - 15...10 %
Product Specific Application
heavy duty industry and pumps
Maximum Horse Power Rating
100 hp 230 V for standard applications || 150 hp 460 V for severe applications || 200 hp 460 V for standard applications || 200 hp 575 V for severe applications || 250 hp 575 V for standard applications || 60 hp 208 V for severe applications || 75 hp 208 V for standard applications || 75 hp 230 V for severe applications
Device Short Name
ATS48
Supply Frequency
50...60 Hz - 5...5 %

Complementary

Product Certifications
CCC || C-tick || CSA || UL || GOST || SEPRO || DNV || TCF || NOM 117
Device Connection
in the motor supply line || to the motor delta terminals
Height
380 mm
Standards
EN/IEC 60947-4-2
Analogue Output Type
current output AO 0-20 mA or 4-20 mA 500 Ohm
Marking
CE
Net Weight
18.2 kg
Connector Type
1 RJ45
Communication Data Link
serial
Function Available
external bypass (optional)
Discrete Output Number
2
Communication Port Protocol
Modbus
Discrete Input Type
PTC, 750 Ohm 25 °C || Stop, Run, LI3, LI4) logic, <= 8 mA 4300 Ohm
Minimum Switching Current
10 mA 6 V DC relay outputs
Physical Interface
RS485 multidrop
Discrete Input Number
5
Operating Position
vertical +/- 10 degree
Width
320 mm
Transmission Rate
4800, 9600 or 19200 bps
Depth
265 mm
Discrete Input Logic
positive logic Stop, Run, LI3, LI4 < 5 V <= 2 mA > 11 V, >= 5 mA
Protection Type
phase failure line || thermal protection motor || thermal protection starter
Discrete Output Type
LO1) logic output 0 V common configurable || LO2) logic output 0 V common configurable || R1) relay outputs fault relay NO || R2) relay outputs end of starting relay NO || R3) relay outputs motor powered NO

Offer Sustainability

Rohs Exemption Information
Yes
Mercury Free
Yes
Environmental Disclosure
ENVPEP111032EN
Sustainable Offer Status
Green Premium product
Reach Regulation
Reference contains Substances of Very High Concern above the threshold
California Proposition 65
WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
Weee
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
China Rohs Regulation
X
Circularity Profile
ENVEOLI111008EN
Eu Rohs Directive
Pro-active compliance (Product out of EU RoHS legal scope)

Environment

Electromagnetic Compatibility
conducted and radiated emissions level A IEC 60947-4-2 || damped oscillating waves level 3 IEC 61000-4-12 || electrostatic discharge level 3 IEC 61000-4-2 || immunity to electrical transients level 4 IEC 61000-4-4 || immunity to radiated radio-electrical interference level 3 IEC 61000-4-3 || voltage/current impulse level 3 IEC 61000-4-5
Ambient Air Temperature For Operation
40-60 °C with current derating of 2 % per °C) || -10-40 °C without derating)
Ambient Air Temperature For Storage
-25-70 °C
Relative Humidity
0-95 % without condensation or dripping water EN/IEC 60068-2-3
Operating Altitude
<= 3280.84 ft (1000 m) without derating || > 3280.84...6561.68 ft (> 1000...2000 m) with current derating of 2.2 % per additional 100 m