- Short-Circuit Protection
- 16 A cartridge fuse gG
- Number Of Steps
- 3
- [Ithe] Conventional Enclosed Thermal Current
- 10 A
- Net Weight
- 0.235 kg
- [Uimp] Rated Impulse Withstand Voltage
- 4 kV in isolating function || 6 kV IEC 947-1
- Cad Overall Height
- 50 mm
- Switching Angle
- 45 °
- Electrical Connection
- captive screw clamp terminals flexible 2 x 1.5 mm² || captive screw clamp terminals solid 1 x 2.5 mm²
- Electrical Durability
- 1000000 cycles AC-15 || 1000000 cycles AC-21 || 500000 cycles AC-23 || 500000 cycles AC-3
- Maximum Operating Rate
- 2.5 cyc/mn AC-21 || 2.5 cyc/mn AC-23 || 2.5 cyc/mn AC-3 || 8.333 cyc/mn AC-15
- Short-Circuit Current
- 10000 A
- [Ui] Rated Insulation Voltage
- 690 V 3)IEC 60947-1
- Positive Opening
- with
- Contact Operation
- slow-break
- Mechanical Durability
- 1000000 cycles
- Cad Overall Width
- 45 mm
- Cad Overall Depth
- 89 mm
- Rated Operational Power In W
- 10500 W AC-21, 500...660 V 3 phase IEC 947-3 || 1100 W AC-3, 230 V 3 phase IEC 947-3 || 1500 W AC-23A, 230 V 3 phase IEC 947-3 || 1500 W AC-3, 400 V 1 phase IEC 947-3 || 1500 W AC-3, 400 V 3 phase IEC 947-3 || 1500 W AC-3, 500 V 3 phase IEC 947-3 || 1500 W AC-3, 690 V 3 phase IEC 947-3 || 2200 W AC-23A, 400 V 3 phase IEC 947-3 || 2200 W AC-23A, 500 V 3 phase IEC 947-3 || 2200 W AC-23A, 690 V 3 phase IEC 947-3 || 4800 W AC-21, 230 V 3 phase IEC 947-3 || 600 W AC-3, 230 V 1 phase IEC 947-3 || 8300 W AC-21, 400 V 3 phase IEC 947-3
- [Ie] Rated Operational Current Ac
- 1.8 A 690 V AC-3 3 phase IEC 947-3 || 2.8 A 500 V AC-3 3 phase IEC 947-3 || 2.8 A 690 V AC-23A 3 phase IEC 947-3 || 3.3 A 400 V AC-3 3 phase IEC 947-3 || 3.8 A 500 V AC-23A 3 phase IEC 947-3 || 4.6 A 230 V AC-3 3 phase IEC 947-3 || 4.8 A 400 V AC-23A 3 phase IEC 947-3 || 5.6 A 230 V AC-23A 3 phase IEC 947-3 || 1 A 500 V AC-15 IEC 947-5-1 || 2 A 400 V AC-15 IEC 947-5-1 || 3 A 230 V AC-15 IEC 947-5-1