- Product Certifications
- CB Scheme || CCC || cULus || EAC || CE || UKCA || EU-RO-MR by DNV-GL
- Height
- 255 mm
- Power Dissipation Per Pole
- 20 W AC-1 - Ith 330 A || 8 W AC-3 - Ith 225 A
- Average Impedance
- 0.00015 Ohm
- Auxiliary Contact Composition
- 1 NO + 1 NC
- Connection Pitch
- 35 mm
- [Ith] Conventional Free Air Thermal Current
- 330 A (at 40 °C)
- Standards
- EN/IEC 60947-4-1 || EN/IEC 60947-5-1 || UL 60947-4-1 || CSA C22.2 No 60947-4-1 || JIS C8201-4-1 || JIS C8201-5-1
- Mounting Support
- plate
- Hold-In Power Consumption In W
- 5.7-5.7 W
- Rated Breaking Capacity
- 2050 A at 440 V
- Irms Rated Making Capacity
- 2720 A at 440 V
- Associated Fuse Rating
- 250 A aM at <= 440 V for motor || 200 A aM at <= 690 V for motor || 400 A gG at <= 690 V
- Net Weight
- 4.1 kg
- [Uimp] Rated Impulse Withstand Voltage
- 8 kV
- Inrush Power In Va
- 290-290 VA
- Pole Contact Composition
- 3 NO
- Connections - Terminals
- power circuit: bar 2 - busbar cross section: 25 x 6 mm || power circuit: lugs-ring terminals 1 185-185 mm² || power circuit: bolted connection || control circuit: push-in 1 0.2-2.5 mm² - cable stiffness: solid stranded without cable end || control circuit: push-in 1 0.25-2.5 mm² - cable stiffness: flexible with cable end || control circuit: push-in 2 0.5-1.0 mm² with cable end || control circuit: push-in 0.75-2.5 mm² - cable stiffness: solid stranded without cable end || control circuit: push-in 0.75-2.5 mm² - cable stiffness: flexible with cable end
- Coil Technology
- built-in bidirectional peak limiting
- Operating Time
- 40...70 ms closing || 15...50 ms opening
- Maximum Operating Rate
- 600 cyc/h AC-3 || 600 cyc/h AC-3e || 300 cyc/h AC-1 || 150 cyc/h AC-4
- Mechanical Durability
- 8 Mcycles
- Tightening Torque
- 18 N.m
- Compatibility Code
- LC1G
- Hold-In Power Consumption In Va
- 10-10 VA
- Width
- 108 mm
- Overvoltage Category
- III
- Depth
- 193 mm
- Maximum Horse Power Rating
- 60 hp at 200/208 V 60 Hz || 75 hp at 230/240 V 60 Hz || 150 hp at 460/480 V 60 Hz || 150 hp at 575/600 V 60 Hz
- Motor Power Kw
- 55 kW at 230 V AC 50/60 Hz (AC-3e) || 110 kW at 400 V AC 50/60 Hz (AC-3e) || 110 kW at 415 V AC 50/60 Hz (AC-3e) || 132 kW at 440 V AC 50/60 Hz (AC-3e) || 132 kW at 500 V AC 50/60 Hz (AC-3e) || 160 kW at 690 V AC 50/60 Hz (AC-3e) || 132 kW at 1000 V AC 50/60 Hz (AC-3e) || 55 kW at 230 V AC 50/60 Hz (AC-3) || 110 kW at 400 V AC 50/60 Hz (AC-3) || 110 kW at 415 V AC 50/60 Hz (AC-3) || 132 kW at 440 V AC 50/60 Hz (AC-3) || 132 kW at 500 V AC 50/60 Hz (AC-3) || 160 kW at 690 V AC 50/60 Hz (AC-3) || 132 kW at 1000 V AC 50/60 Hz (AC-3) || 55 kW at 230 V AC 50/60 Hz (AC-4) || 110 kW at 400 V AC 50/60 Hz (AC-4) || 110 kW at 415 V AC 50/60 Hz (AC-4) || 129 kW at 440 V AC 50/60 Hz (AC-4) || 132 kW at 500 V AC 50/60 Hz (AC-4) || 132 kW at 690 V AC 50/60 Hz (AC-4) || 110 kW at 1000 V AC 50/60 Hz (AC-4)
- [Ui] Rated Insulation Voltage
- 1000 V
- Inrush Power In W
- 220 W
- [Icw] Rated Short-Time Withstand Current
- 1.8 kA - 10 s || 1.0 kA - 30 s || 0.85 kA - 1 min || 0.56 kA - 3 min || 0.44 kA - 10 min