- Interlocking Type
- mechanical
- [Uc] Control Circuit Voltage
- 24 V DC
- [Ue] Rated Operational Voltage
- power circuit 690 V AC 25...400 Hz
- Power Dissipation Per Pole
- 9.6 W AC-1 || 6.3 W AC-3
- Average Impedance
- 1.5 mOhm - Ith 80 A 50 Hz for power circuit
- Auxiliary Contact Composition
- 1 NO + 1 NC
- [Ith] Conventional Free Air Thermal Current
- 10 A (at 60 °C) for signalling circuit || 80 A (at 60 °C) for power circuit
- Mounting Support
- rail || plate
- Control Circuit Type
- DC DC low consumption
- Standards
- EN/IEC 60947-4-1 || EN/IEC 60947-5-1 || UL 60947-4-1 || CSA C22.2 No 60947-4-1 || IEC 60335-1
- Safety Reliability Level
- B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
- Contactor Application
- motor control || resistive load
- Rated Breaking Capacity
- 1000 A at 440 V for power circuit conforming to IEC 60947
- Product Or Component Type
- reversing contactor
- Product Certifications
- CCC || CSA || EAC || UL || KC || DNV-GL || LROS (Lloyds register of shipping) || UKCA
- Irms Rated Making Capacity
- 140 A AC for signalling circuit conforming to IEC 60947-5-1 || 250 A DC for signalling circuit conforming to IEC 60947-5-1 || 1000 A at 440 V for power circuit conforming to IEC 60947
- Product Name
- Tesys Deca green || TeSys Deca
- Associated Fuse Rating
- 10 A gG for signalling circuit conforming to IEC 60947-5-1 || 125 A gG at <= 690 V coordination type 1 for power circuit || 125 A gG at <= 690 V coordination type 2 for power circuit
- [Uimp] Rated Impulse Withstand Voltage
- 6 kV IEC 60947
- Connections - Terminals
- control circuit screw clamp terminals 1 1-4 mm²flexible without cable end || control circuit screw clamp terminals 2 1-4 mm²flexible without cable end || control circuit screw clamp terminals 1 1-4 mm²flexible with cable end || control circuit screw clamp terminals 2 1-2.5 mm²flexible with cable end || control circuit screw clamp terminals 1 1-4 mm²solid || control circuit screw clamp terminals 2 1-4 mm²solid || power circuit EverLink BTR screw connectors 1 1-35 mm²flexible without cable end || power circuit EverLink BTR screw connectors 2 1-25 mm²flexible without cable end || power circuit EverLink BTR screw connectors 1 1-35 mm²flexible with cable end || power circuit EverLink BTR screw connectors 2 1-25 mm²flexible with cable end || power circuit EverLink BTR screw connectors 1 1-35 mm²solid || power circuit EverLink BTR screw connectors 2 1-25 mm²solid
- Range
- TeSys || TeSys Deca
- Pole Contact Composition
- 3 NO
- Device Presentation
- preassembled with reversing power busbar
- Utilisation Category
- AC-3 || AC-1
- [Ie] Rated Operational Current
- 80 A (at <60 °C) at <= 440 V AC-1 for power circuit || 65 A (at <60 °C) at <= 440 V AC-3 for power circuit
- Operating Time
- 55...65 ms closing || 20...120 ms opening >= 17221) || 20...80 ms opening >= 18011)
- Maximum Operating Rate
- 3600 cyc/h 60 °C
- Electrical Durability
- 1.8 Mcycles 57 A AC-3 <= 440 V || 0.5 Mcycles 80 A AC-1 <= 440 V
- Tightening Torque
- control circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || control circuit 1.7 N.m screw clamp terminals Philips No 2 || power circuit 8 N.m EverLink BTR screw connectors 25-35 mm² hexagonal 4 mm || power circuit 5 N.m EverLink BTR screw connectors 1-25 mm² hexagonal 4 mm
- Poles Description
- 3P
- Overvoltage Category
- III
- Motor Power Kw
- 18.5 kW at 220...230 V AC 50 Hz || 30 kW at 380...400 V AC 50 Hz || 37 kW at 415 V AC 50 Hz || 37 kW at 440 V AC 50 Hz || 37 kW at 500 V AC 50 Hz || 37 kW at 660...690 V AC 50 Hz
- Maximum Horse Power Rating
- 5 hp at 115 V AC 60 Hz for 1 phase motors || 10 hp at 230/240 V AC 60 Hz for 1 phase motors || 20 hp at 200/208 V AC 60 Hz for 3 phase motors || 20 hp at 230/240 V AC 60 Hz for 3 phase motors || 40 hp at 460/480 V AC 60 Hz for 3 phase motors || 50 hp at 575/600 V AC 60 Hz for 3 phase motors
- [Ui] Rated Insulation Voltage
- power circuit 690 V IEC 60947-4-1 || signalling circuit 690 V IEC 60947-1
- Mechanical Durability
- 6 Mcycles
- Device Short Name
- LC2D
- [Icw] Rated Short-Time Withstand Current
- 100 A - 1 s for signalling circuit || 120 A - 500 ms for signalling circuit || 140 A - 100 ms for signalling circuit || 520 A 40 °C - 10 s for power circuit || 900 A 40 °C - 1 s for power circuit || 110 A 40 °C - 10 min for power circuit || 260 A 40 °C - 1 min for power circuit
- Protective Cover
- with