- Product Certifications
- UL || CSA || RINA || GOST || CCC || DNV || LROS (Lloyds register of shipping) || GL || BV || UKCA
- Interlocking Type
- mechanical
- [Uc] Control Circuit Voltage
- 240 V AC 50/60 Hz
- [Ue] Rated Operational Voltage
- power circuit <= 690 V AC 25...400 Hz || power circuit <= 300 V DC
- Power Dissipation Per Pole
- 12.5 W AC-1 || 5.1 W AC-3 || 5.1 W AC-3e
- Average Impedance
- 0.8 mOhm - Ith 125 A 50 Hz power circuit
- Auxiliary Contact Composition
- 1 NO + 1 NC
- [Ith] Conventional Free Air Thermal Current
- 10 A 60 °C signalling circuit || 125 A 60 °C power circuit
- Mounting Support
- rail || plate
- Control Circuit Type
- AC 50/60 Hz
- Standards
- CSA C22.2 No 14 || EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 508
- Safety Reliability Level
- B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
- Contactor Application
- resistive load || motor control
- Rated Breaking Capacity
- 1100 A 440 V power circuit IEC 60947
- Product Or Component Type
- reversing contactor
- Irms Rated Making Capacity
- 140 A AC signalling circuit IEC 60947-5-1 || 250 A DC signalling circuit IEC 60947-5-1 || 1100 A 440 V power circuit IEC 60947
- Product Name
- TeSys Deca
- Associated Fuse Rating
- 10 A gG signalling circuit IEC 60947-5-1 || 200 A gG <= 690 V type 1 power circuit || 160 A gG <= 690 V type 2 power circuit
- [Uimp] Rated Impulse Withstand Voltage
- 8 kV IEC 60947
- Connections - Terminals
- control circuit screw clamp terminals 1 1-4 mm²flexible without cable end || control circuit screw clamp terminals 2 1-4 mm²flexible without cable end || control circuit screw clamp terminals 2 1-2.5 mm²flexible with cable end || control circuit screw clamp terminals 1 1-4 mm²solid || control circuit screw clamp terminals 2 1-4 mm²solid || control circuit screw clamp terminals 1 1-2.5 mm²flexible with cable end || power circuit connector 1 4-50 mm²flexible without cable end || power circuit connector 2 4-25 mm²flexible without cable end || power circuit connector 1 4-50 mm²flexible with cable end || power circuit connector 2 4-16 mm²flexible with cable end || power circuit connector 1 4-50 mm²solid || power circuit connector 2 4-25 mm²solid
- Range
- TeSys
- Pole Contact Composition
- 3 NO
- Device Presentation
- preassembled with reversing power busbar
- Utilisation Category
- AC-1 || AC-3 || AC-3e || AC-4
- [Ie] Rated Operational Current
- 125 A 60 °C) <= 440 V AC AC-1 power circuit || 80 A 60 °C) <= 440 V AC AC-3 power circuit || 80 A 60 °C) <= 440 V AC AC-3e power circuit || 55 A 60 °C) <= 400 V AC AC-4 power circuit
- Maximum Operating Rate
- 3600 cyc/h 60 °C
- Tightening Torque
- control circuit 1.2 N.m screw clamp terminals flat Ø 6 mm || control circuit 1.2 N.m screw clamp terminals Philips No 2 || power circuit 12 N.m connector flat Ø 6 to Ø 8 mm || power circuit 12 N.m connector hexagonal 4 mm
- Electrical Durability
- 0.8 Mcycles 125 A AC-1 <= 440 V || 1.5 Mcycles 80 A AC-3 <= 440 V || 1.5 Mcycles 80 A AC-3e
- Mechanical Durability
- 4 Mcycles
- Poles Description
- 3P
- Operating Time
- 20...35 ms closing || 6...20 ms opening
- Overvoltage Category
- III
- Motor Power Kw
- 22 kW 220...230 V AC 50 Hz || 37 kW 380...400 V AC 50 Hz || 45 kW 415...440 V AC 50 Hz || 55 kW 500 V AC 50 Hz || 45 kW 660...690 V AC 50 Hz
- Maximum Horse Power Rating
- 20 hp 200/208 V at AC 60 Hz for 3 phase || 7.5 hp 115 V at AC 60 Hz for 1 phase || 15 hp 230/240 V at AC 60 Hz for 1 phase || 25 hp 230/240 V at AC 60 Hz for 3 phase || 60 hp 460/480 V at AC 60 Hz for 3 phase || 60 hp 575/600 V at AC 60 Hz for 3 phase
- [Ui] Rated Insulation Voltage
- power circuit 600 V CSA || power circuit 600 V UL || signalling circuit 690 V IEC 60947-1 || signalling circuit 600 V CSA || signalling circuit 600 V UL || power circuit 1000 V IEC 60947-4-1
- Device Short Name
- LC2D
- [Icw] Rated Short-Time Withstand Current
- 135 A 40 °C - 10 min power circuit || 320 A 40 °C - 1 min power circuit || 640 A 40 °C - 10 s power circuit || 990 A 40 °C - 1 s power circuit || 100 A - 1 s signalling circuit || 120 A - 500 ms signalling circuit || 140 A - 100 ms signalling circuit
- Protective Cover
- with