Schneider Electric
LV429492
Earth-leakage add-on protection module VigiPacT, ComPacT NSX 250, 200VAC to 440VAC, 30mA to 30A, 3 poles
- Erhalten Sie bis zu 90 Tage Zahlungsziele von 500+ Lieferanten
- Wiederverkaufsrabatte bis zu 40%!
Preisanfrage senden
1
Zahlungsmöglichkeiten:
Insgesamt 59 Parts In-Stock von 18 Distributors
Produktbedingungen:
Angebot mit Herstellervorlaufzeit
Lieferung:1 - 2 Viele Arbeitstage
Bester Preis:
€315.90
Additional Information
- Part Number
- LV429492
- UNSPSC
- 41113645
- Tariff Code
- 8536308000
- Country of Origin
- IT
Offer Sustainability
- Rohs Exemption Information
- Yes
- Mercury Free
- Yes
- Environmental Disclosure
- ENVPEP2309055EN
- Sustainable Offer Status
- Green Premium product
- Pvc Free
- Yes
- Reach Regulation
- Reference contains Substances of Very High Concern above the threshold
- Weee
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- China Rohs Regulation
- Product out of China RoHS scope. Substance declaration for your information.
- Circularity Profile
- ENVEOLI2309055EN
- Eu Rohs Directive
- Compliant with Exemptions
Specifications
- Line Rated Current
- 250 A
- Range Of Product
- ComPacT NSX100...250 new generation || ComPact NSX100...250
- Range Compatibility
- ComPacT new generation ComPacT NSX250 new generation circuit breaker || ComPact ComPact NSX250 circuit breaker
- Earth-Leakage Protection Class
- class A || class AC
- Earth-Leakage Sensitivity
- 0.03 A class A || 0.1 A class A || 0.3 A class A || 0.5 A class A || 1 A class A || 3 A class A || 10 A class AC || 30 A class AC
- Product Or Component Type
- Vigi add-on
- [Δt] Residual Earth-Leakage Time Delay Adjustment
- 0-0 ms || 60-60 ms || 150-150 ms || 300-300 ms || 500-500 ms || 800-800 ms || 1.2-1.2 s || 4-4 s
- Residual Earth-Leakage Sensitity Adjustment Type
- adjustable
- Poles Description
- 3P
- Device Application
- wiring
- Residual Earth-Leakage Time Delay Adjustment Type
- adjustable
- Device Short Name
- VigiPacT
Complementary
- Network Frequency
- 50/60 Hz
- [Ue] Rated Operational Voltage
- 200...440 V AC 50/60 Hz IEC 60947-2
- Earth-Leakage Protection
- with
- Network Type
- AC
- Maximum Breaking Time
- 800 ms
- Overvoltage Category
- IV
Environment
- Standards
- IEC 60947-2
- Electrical Shock Protection Class
- class II
Dokumente
Data Sheet
HerunterladenCAD Models
Andere Kategorien
AktuatorenBlöckeKabel, Rohre & SchläucheKompressorenKontrolleKupplungen & FittingsZylinder & KolbenElektronikFilterHVACIndustrie-PCs & HMIsBeleuchtungLineartechnikMotorenStromversorgungLeistungsübertragungPumpen & VentileErneuerbare energieRobotikDichtungen, Ringe & VerbinderSensoren und MessgeräteWerkzeuge und ZubehörCNCSonstiges