Circuit breaker, ComPact NSX630R, 200kA/415VAC, MicroLogic 2.3 trip unit 630A, 4 poles 4d
LV433701
  • Erhalten Sie bis zu 90 Tage Zahlungsziele von 500+ Lieferanten
  • Wiederverkaufsrabatte bis zu 40%!
Sign-Up
Preisanfrage senden
1
Zahlungsmöglichkeiten:
Angebot mit Herstellervorlaufzeit
Lieferung:1 - 2 Viele Arbeitstage
Bester Preis:
€1,170.72

Additional Information

Part Number
LV433701
UNSPSC
39121601
Country of Origin
FR

Specifications

Network Frequency
50/60 Hz
Line Rated Current
630 A 40 °C
Trip Unit Name
Micrologic 2.3
Range Of Product
ComPact NSX400...630
[Ue] Rated Operational Voltage
690 V AC 50/60 Hz
Trip Unit Protection Functions
LSoI
Network Type
AC
Protected Poles Description
4t || 3t || 3t + N/2
Product Or Component Type
circuit breaker
Product Name
ComPact NSX
Range
ComPact
Control Type
toggle
Utilisation Category
category A
Mounting Mode
fixed
Breaking Capacity
200 kA Icu 220/240 V AC 50/60 Hz IEC 60947-2 || 200 kA Icu 380/415 V AC 50/60 Hz IEC 60947-2 || 200 kA Icu 440 V AC 50/60 Hz IEC 60947-2 || 80 kA Icu 500 V AC 50/60 Hz IEC 60947-2 || 65 kA Icu 525 V AC 50/60 Hz IEC 60947-2 || 45 kA Icu 660/690 V AC 50/60 Hz IEC 60947-2
Suitability For Isolation
yes EN/IEC 60947-2
Poles Description
4P
Breaking Capacity Code
R 200 kA 415 V AC
Neutral Position
left
Device Application
distribution
Device Short Name
NSX630R
Trip Unit Technology
electronic

Contractual warranty

Warranty
18 months

Complementary

[Ics] Rated Service Breaking Capacity
200 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 200 kA 380/415 V AC 50/60 Hz IEC 60947-2 || 200 kA 440 V AC 50/60 Hz IEC 60947-2 || 80 kA 500 V AC 50/60 Hz IEC 60947-2 || 16 kA 525 V AC 50/60 Hz IEC 60947-2 || 12 kA 660/690 V AC 50/60 Hz IEC 60947-2
Height
255 mm
Thermal Memory
20 minutes before and after tripping
Earth-Leakage Protection
without
Mounting Support
backplate
Instantaneous Pick-Up Adjustment Range
6900 A
Downside Connection
front
Number Of Slots
6
Protection Type
L : for overload protection (long time) || So : for short time short-circuit protection with fixed delay || I : for instantaneous short-circuit protection
Long Time Delay Adjustment Type
fixed
Instantaneous Pick-Up Adjustment Type Ii
fixed
Zone Selective Interlocking Zsi
without
Net Weight
8.13 kg
[Tr] Long-Time Delay Adjustment Range
11-11 s 7.2 x Ir || 16-16 s 6 x Ir || 400-400 s 1.5 x Ir
Electrical Durability
2000 cycles 690 V In || 6000 cycles 690 V In/2 || 4000 cycles 440 V In || 8000 cycles 440 V In/2
Short-Time Delay Adjustment Type
fixed
Neutral Protection Setting
0.5 x Ir 3t + N/2) || 1 x Ir 4t) || no protection 3t)
Long Time Pick-Up Adjustment Type Ir
adjustable 9 settings
Long Time Pick-Up Adjustment Range
250...630 A
Upside Connection
front
[Ui] Rated Insulation Voltage
800 V AC 50/60 Hz
Trip Unit Rating
630-630 A 40 °C
Local Signalling
for ready to operate flashing LED (green) || for overload LED 105 % Ir (red) || for overload LED 90 % Ir (orange)
Mechanical Durability
15000 cycles
[Isd] Short-Time Pick-Up Adjustment Range
1.5...10 x Ir
Connection Pitch
45 mm
[Uimp] Rated Impulse Withstand Voltage
8 kV
Width
185 mm
Depth
110 mm
Short-Time Pick-Up Adjustment Type Isd
adjustable 9 settings

Offer Sustainability

Rohs Exemption Information
Yes
Mercury Free
Yes
Environmental Disclosure
ENVPEP120606EN
Sustainable Offer Status
Green Premium product
Reach Regulation
Reference contains Substances of Very High Concern above the threshold
California Proposition 65
WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
China Rohs Regulation
Product out of China RoHS scope. Substance declaration for your information.
Circularity Profile
ENVEOLI120604EN
Eu Rohs Directive
Compliant

Environment

Product Certifications
Marine || EAC || CCC
Ik Degree Of Protection
IK07 IEC 62262
Ambient Air Temperature For Operation
-25-70 °C
Standards
EN/IEC 60947
Ip Degree Of Protection
IP40 conforming to IEC 60529
Electrical Shock Protection Class
class II
Pollution Degree
3 IEC 60664-1
Ambient Air Temperature For Storage
-50-85 °C
Relative Humidity
0-95 %
Operating Altitude
0...6561.68 ft (0...2000 m) without derating || 2000 m...5000 m with derating
Overvoltage Category
class II