1 / 1
thumbnail
Country of Origin
FR
Part Number
LV848253
Tariff Code
85362090
EAN
3606480806957
UNSPSC
39121601
  • Erhalten Sie bis zu 90 Tage Zahlungsziele von 500+ Lieferanten
  • Wiederverkaufsrabatte bis zu 40%!
Sign-Up
Preisanfrage senden
1
Zahlungsmöglichkeiten:
Fordern Sie ein Angebot an und wir senden Ihnen Informationen zu Verfügbarkeit und Preis.

Specifications

Network Frequency
50/60 Hz
Network Type
AC
Breaking Capacity Code
H2
Product Or Component Type
circuit breaker
Product Name
MasterPact MTZ2
Range
Masterpact
Utilisation Category
category B
Suitability For Isolation
yes IEC 60947-2
Poles Description
4P
Neutral Position
left
Device Application
protection
Device Short Name
MTZ2 10 H2

Complementary

[Ics] Rated Service Breaking Capacity
100 kA 220/415 V AC 50/60 Hz IEC 60947-2 || 100 kA 440 V AC 50/60 Hz IEC 60947-2 || 85 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 85 kA 660/690 V AC 50/60 Hz IEC 60947-2
Line Rated Current
1000 A 40 °C
Connection Pitch
115 mm
[Ue] Rated Operational Voltage
690 V AC 50/60 Hz IEC 60947-2
Mounting Support
rails || base plate
Circuit Breaker Ct Rating
1000 A
Maximum Breaking Time
25-25 ms
Depth
drawout circuit breaker without chassis 300 mm || drawout circuit breaker with chassis 403 mm
Control Type
push-button
Maximum Closing Response Time
70 ms
Mounting Mode
drawout
Breaking Capacity
100 kA Icu 220/415 V AC 50/60 Hz IEC 60947-2 || 100 kA Icu 440 V AC 50/60 Hz IEC 60947-2 || 85 kA Icu 500/525 V AC 50/60 Hz IEC 60947-2 || 85 kA Icu 660/690 V AC 50/60 Hz IEC 60947-2
[Icm] Rated Short-Circuit Making Capacity
220 kA 220/415 V AC 50/60 Hz || 220 kA 440 V AC 50/60 Hz || 187 kA 500/525 V AC 50/60 Hz || 187 kA 660/690 V AC 50/60 Hz
Electrical Durability
10000 cycles 440 V AC 50/60 Hz IEC 60947-2 || 10000 cycles 690 V AC 50/60 Hz IEC 60947-2 || AC-23A 10000 cycles 440 V AC 50/60 Hz IEC 60947-3 || AC-23A 10000 cycles 690 V AC 50/60 Hz IEC 60947-3 || AC-3 6000 cycles 440/690 V AC 50/60 Hz IEC 60947-3
[Ui] Rated Insulation Voltage
1000 V AC 50/60 Hz IEC 60947-2
Mechanical Durability
25000 cycles with periodic preventive maintenance IEC 60947-2
Height
drawout circuit breaker without chassis 300 mm || drawout circuit breaker with chassis 439 mm
Width
drawout circuit breaker without chassis 493 mm || drawout circuit breaker with chassis 556 mm
Integral Instant Protection
171-209 kA
[Uimp] Rated Impulse Withstand Voltage
12 kVIEC 60947-2
[Icw] Rated Short-Time Withstand Current
85 kA 0.5 s IEC 60947-2 || 85 kA 1 s IEC 60947-2 || 50 kA 3 s IEC 60947-2

Offer Sustainability

Rohs Exemption Information
Yes
Mercury Free
Yes
Environmental Disclosure
ENVPEP1607009EN
Sustainable Offer Status
Green Premium product
Pvc Free
Yes
Reach Regulation
Reference contains Substances of Very High Concern above the threshold
California Proposition 65
WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
China Rohs Regulation
Product out of China RoHS scope. Substance declaration for your information.
Circularity Profile
ENVEOLI1607009EN
Eu Rohs Directive
Compliant

Environment

Product Certifications
ASEFA
Ambient Air Temperature For Operation
-25-70 °C
Standards
IEC 60364-8-1 || IEC 60947-2
Pollution Degree
3 IEC 60947-1
Ambient Air Temperature For Storage
-40-85 °C

CAD Models

traceparts
traceparts
Herunterladen