1 / 1
thumbnail

Beschreibung

Aktiv Reif
This Multi9 C60N is a low voltage miniature circuit breaker (MCB). It is a 4P circuit breaker with 4 protected poles, 3A rated current and D tripping curve. The rated short circuit breaking capacity goes up to 10kA at 415VAC conforming to EN/IEC 60947-2 standard. This product complies with both industrial standard EN/IEC 60898-1 and residential standard EN/IEC 60947-2. It has been designed to offer enhanced protection by preventing, protecting people and equipment from electrical threats. This product protects from short circuit, earth leakage and overload. Its fast closing mechanism, overvolatge resistance and high performance limitation improve its service life. This product is dedicated for original equipment manufacturers (OEM) and control panel builders. It has an electrical endurance going up to 10000 cycles and a mechanical endurance going up to 20000 cycles. The Ue operational voltage is 240VAC. The Ui rated insulation voltage is 500VAC. The Uimp rated impulse withstand voltage is 6kV. The operating frequency is 50Hz or 60Hz. The product can be clipped on a DIN rail. Pollution degree is 3. Overvoltage category is IV. The product colour is light grey (RAL7035). The dimensions are (W) 72mm x (H) 81mm x (D) 72mm. The weight is 0.48kg. It has an IP20 degree of protection (as per IEC/EN 60529) on its terminals. The operating temperature is -30°C to 70°C. The storage temperature is -40°C to 80°C.
Country of Origin
BG
Part Number
M9F12403
Tariff Code
85362010
EAN
3606480576935
UNSPSC
39121603
  • Erhalten Sie bis zu 90 Tage Zahlungsziele von 500+ Lieferanten
  • Wiederverkaufsrabatte bis zu 40%!
Sign-Up
Preisanfrage senden
1
Zahlungsmöglichkeiten:
Fordern Sie ein Angebot an und wir senden Ihnen Informationen zu Verfügbarkeit und Preis.

Specifications

Line Rated Current
3 A 50 °C EN/IEC 60947-2
Curve Code
D
Number Of Protected Poles
4
Network Type
DC || AC
Standards
EN/IEC 60947-2
Product Certifications
EAC || CCC
Product Or Component Type
miniature circuit-breaker
Product Name
Multi9 C60
Utilisation Category
category A EN/IEC 60947-2
Range
Multi9
Breaking Capacity
40 kA Icu <= 250 V DC EN/IEC 60947-2 || 10 kA Icu 415 V AC 50/60 Hz between phases EN/IEC 60947-2 || 20 kA Icu 240 V AC 50/60 Hz between phases EN/IEC 60947-2 || 6 kA Icu 440 V AC 50/60 Hz between phases EN/IEC 60947-2
Suitability For Isolation
yes EN/IEC 60947-2
Poles Description
4P
Device Application
distribution
Device Short Name
C60N
Trip Unit Technology
thermal-magnetic

Complementary

Network Frequency
50/60 Hz
[Ics] Rated Service Breaking Capacity
7.5 kA 75 % EN/IEC 60947-2 - 415 V AC 50/60 Hz || 16 kA 75 % EN/IEC 60947-2 - 240 V AC 50/60 Hz || 4.5 kA 75 % EN/IEC 60947-2 - 440 V AC 50/60 Hz || 40 kA 100 % EN/IEC 60947-2 - <= 250 V DC
Height
81 mm
Contact Position Indicator
yes
Earth-Leakage Protection
separate block
Mounting Support
DIN rail
9 Mm Pitches
8
Limitation Class
3
Net Weight
0.48 kg
Wire Stripping Length
14 mm top or bottom
Control Type
toggle
Connections - Terminals
tunnel type terminal top or bottom) 1-25 mm² - rigid || tunnel type terminal top or bottom) 1-25 mm² - flexible || tunnel type terminal top or bottom) 1-25 mm² - flexible with ferrule
[Ui] Rated Insulation Voltage
500 V AC 50/60 Hz EN/IEC 60947-2
Mounting Mode
clip-on
Electrical Durability
10000 cycles
Mechanical Durability
20000 cycles
Local Signalling
ON/OFF indication
[Uimp] Rated Impulse Withstand Voltage
6 kVEN/IEC 60947-2
Color
Gray
Width
72 mm
Provision For Padlocking
padlockable
Depth
72 mm
Tightening Torque
2-2 N.m top or bottom
Magnetic Tripping Limit
12 x In +/- 20 % AC || 17 x In +/- 20 % DC
[Ue] Rated Operational Voltage
240 V AC 50/60 Hz between phases || 415 V AC 50/60 Hz between phases || 440 V AC 50/60 Hz between phases || <= 250 V DC

Environment

Ambient Air Temperature For Operation
-30-70 °C
Tropicalisation
2 IEC 60068-1
Ip Degree Of Protection
IP20 conforming to IEC 60529 || IP40 (modular enclosure) conforming to IEC 60529
Pollution Degree
3 EN/IEC 60947-2
Ambient Air Temperature For Storage
-40-80 °C
Relative Humidity
95-95 % 55-55 °C
Overvoltage Category
IV
Heat Dissipation
8.8-8.8 W 415 V - 3 A