1 / 1
thumbnail

Beschreibung

PowerPacT P-Frame circuit breakers are designed to protect electrical systems from damage caused by overloads and short circuits. PowerPacT P-Frame circuit breakers have either a fixed long time electronic trip unit, ET 1.0I, or Micrologic trip units. Micrologic trip units can be interchanged in the field to allow for maximum flexibility; the basic electronic trip unit doesn't have that interchangeability. This circuit breaker has an electronic trip unit, ET 1.0I. All PowerPacT circuit breakers have an integral push-to-trip button in the cover to manually trip the circuit breaker. PowerPacT P circuit breakers are available in 2, 3, and 4-pole unit mount, I-Line, or drawout construction. This unit has lugs on both the line and load sides. This PowerPacT P, 600A, 3 pole, circuit breaker has an interrupting rating of 18kA at 600VAC. This circuit breaker has a continuous current rating of 80%. PowerPacT P circuit breakers comply to UL, CSA, NOM, and IEC standards and are CE marked.
Country of Origin
US
Part Number
PGL36060
EAN
39121601
UPC
785901564508
UNSPSC
39121601
  • Erhalten Sie bis zu 90 Tage Zahlungsziele von 500+ Lieferanten
  • Wiederverkaufsrabatte bis zu 40%!
Sign-Up
Preisanfrage senden
1
Zahlungsmöglichkeiten:
Fordern Sie ein Angebot an und wir senden Ihnen Informationen zu Verfügbarkeit und Preis.

Specifications

Product Or Component Type
circuit breaker
Product Name
PowerPact P
Range
PowerPact
Device Application
distribution

Contractual warranty

Warranty
18 months

Complementary

Network Frequency
50/60 Hz
Terminal Identifier
AL800M23K
[Ics] Rated Service Breaking Capacity
25 kA 240 V AC 50/60 Hz IEC 60947-2 || 20 kA 380/415 V AC 50/60 Hz IEC 60947-2
Trip Unit Technology
electronic, basic, ET 1.0I, I
Trip Unit Name
ET 1.0I
Height
12.86 in
[Ue] Rated Operational Voltage
600 V AC 50/60 Hz UL 489
Tightening Torque
50-50 N.m 95-240 mm² (3 x AWG 3/0...3 x 500 kcmil) || 1.0-1.3 N.m
Breaking Capacity Code
G
Local Signalling
1 trip indicator green)
Number Of Slots
2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
Electrical Connection
lugs load || lugs line
Net Weight
32 lb(US)
[Uimp] Rated Impulse Withstand Voltage
8 kV IEC 60947-2
Control Type
toggle
Circuit Breaker Application
HACR rated
Wire Stripping Length
25 mm
Line Rated Current
600-600 A
Long Time Pick-Up Adjustment Range
1 In
Continuous Current Rating
80 %
Breaking Capacity
AIR 65 kA 240 V AC 50/60 Hz UL 489 || AIR 35 kA 480 V AC 50/60 Hz UL 489 || AIR 18 kA 600 V AC 50/60 Hz UL 489 || Icu 50 kA 240 V AC 50/60 Hz IEC 60947-2 || Icu 35 kA 380/415 V AC 50/60 Hz IEC 60947-2
[Ui] Rated Insulation Voltage
750 V IEC 60947-2
Poles Description
3P
Quantity Per Set
1
Awg Gauge
3 x AWG 3/0...3 x 500 kcmil aluminium/copper
Width
8.27 in
Depth
8.05 in

Offer Sustainability

Rohs Exemption Information
Yes
Mercury Free
Yes
Environmental Disclosure
ENVPEP2206033EN
Sustainable Offer Status
Green Premium product
Pvc Free
Yes
Reach Regulation
Reference contains Substances of Very High Concern above the threshold
California Proposition 65
WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
China Rohs Regulation
Product out of China RoHS scope. Substance declaration for your information.
Circularity Profile
ENVEOLI2206033EN
Eu Rohs Directive
Compliant

Environment

Ambient Air Temperature For Operation
-2-70 °C
Standards
UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
Product Certifications
UL || CSA || NOM
Ip Degree Of Protection
front cover IP40
Pollution Degree
3 IEC 60947-1
Ambient Air Temperature For Storage
-50-85 °C
Quality Labels
CE
Operating Altitude
< 6561.68 ft (2000 m) without derating || 13123.36 ft (4000 m) with derating

Dokumente

Data Sheet

Herunterladen