Schneider Electric
PLL34120
Circuit breaker, PowerPacT P, 1200A, 3 pole, 480VAC, 100kA, lugs, ET1.0l, 80%
- Erhalten Sie bis zu 90 Tage Zahlungsziele von 500+ Lieferanten
- Wiederverkaufsrabatte bis zu 40%!
Preisanfrage senden
1
Zahlungsmöglichkeiten:
Additional Information
- Part Number
- PLL34120
- UPC
- 785901830672
- UNSPSC
- 39121601
- Tariff Code
- 8536200020
- Country of Origin
- US
Environment
- Ambient Air Temperature For Operation
- -2-70 °C
- Standards
- UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
- Product Certifications
- UL || CSA || NOM
- Ip Degree Of Protection
- front cover IP40
- Pollution Degree
- 3 IEC 60947-1
- Ambient Air Temperature For Storage
- -50-85 °C
- Quality Labels
- CE
- Operating Altitude
- < 6561.68 ft (2000 m) without derating || 13123.36 ft (4000 m) with derating
Contractual warranty
- Warranty
- 18 months
Offer Sustainability
- Rohs Exemption Information
- Yes
- Mercury Free
- Yes
- Environmental Disclosure
- ENVPEP2206033EN
- Sustainable Offer Status
- Green Premium product
- Pvc Free
- Yes
- Reach Regulation
- Reference contains Substances of Very High Concern above the threshold
- California Proposition 65
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
- China Rohs Regulation
- Product out of China RoHS scope. Substance declaration for your information.
- Circularity Profile
- ENVEOLI2206033EN
- Eu Rohs Directive
- Compliant with Exemptions
Complementary
- Mounting Mode
- unit mount lug)
- Network Frequency
- 50/60 Hz
- Terminal Identifier
- AL1200P25K
- [Ics] Rated Service Breaking Capacity
- 65 kA 240 V AC 50/60 Hz IEC 60947-2 || 45 kA 380/415 V AC 50/60 Hz IEC 60947-2
- Trip Unit Technology
- electronic, basic, ET 1.0I, I
- Trip Unit Name
- ET 1.0I
- Height
- 16.16 in
- [Ue] Rated Operational Voltage
- 480 V AC 50/60 Hz UL 489
- Tightening Torque
- 50-50 N.m 95-240 mm² (4 x AWG 3/0...500 kcmil) || 1.0-1.3 N.m
- Mounting Support
- lug
- Breaking Capacity Code
- L
- Local Signalling
- 1 trip indicator green)
- Number Of Slots
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
- Electrical Connection
- lugs, line || lugs, load
- Net Weight
- 32 lb(US)
- [Uimp] Rated Impulse Withstand Voltage
- 8 kV IEC 60947-2
- Control Type
- toggle
- Circuit Breaker Application
- HACR rated
- Wire Stripping Length
- 30 mm
- Line Rated Current
- 1200-1200 A
- Long Time Pick-Up Adjustment Range
- 1 In
- Continuous Current Rating
- 80 %
- Breaking Capacity
- AIR 125 kA 240 V AC 50/60 Hz UL 489 || AIR 100 kA 480 V AC 50/60 Hz UL 489 || AIR 25 kA 600 V AC 50/60 Hz UL 489 || Icu 125 kA 240 V AC 50/60 Hz IEC 60947-2 || Icu 85 kA 380/415 V AC 50/60 Hz IEC 60947-2
- [Ui] Rated Insulation Voltage
- 750 V IEC 60947-2
- Poles Description
- 3P
- Quantity Per Set
- 1
- Awg Gauge
- 4 x AWG 3/0...500 kcmil aluminium/copper
- Width
- 8.27 in
- Depth
- 8.05 in
Specifications
- Product Or Component Type
- circuit breaker
- Product Name
- PowerPact P
- Range
- PowerPact
- Device Application
- distribution
Dokumente
Data Sheet
HerunterladenAndere Kategorien
AktuatorenBlöckeKabel, Rohre & SchläucheKompressorenKontrolleKupplungen & FittingsZylinder & KolbenElektronikFilterHVACIndustrie-PCs & HMIsBeleuchtungLineartechnikMotorenStromversorgungLeistungsübertragungPumpen & VentileErneuerbare energieRobotikDichtungen, Ringe & VerbinderSensoren und MessgeräteWerkzeuge und ZubehörCNCSonstiges