Aktiv Reif
This modular timing relay belongs to the Schneider Electric Harmony Timer relays range. This is an off-delay timer with single function and is activated by the control input Y1 when connected to 0V. This is a 17.5mm slim relay with input of 24Vac to 240Vac and solid state output of 0.7A. It has one of slimmest form-factors, allowing for a flexible and easy installation on DIN rail using the same space as any modular 1-pole DIN device. This is a spring terminal type relay with a sealable cover and rotary trimmers for simple and precise settings. It has 7 selectable timing ranges of 1s, 10s, 1min, 10min, 1h, 10h, and 100h and 2 dials for adjusting. It weighs 0.050Kg. 0 0 The product conforms to IEC 61812-1 and EN 61812-1 standards, and UL, CSA, GL, RCM, EAC, CCC, and China ROHS certifications. 0 0 0 The spring terminals timing relays bring you easy, time-saving and secured wiring during installation and maintenance. 0 0 0 0 0
Country of Origin
ID
Part Number
RE17LCBMS
Tariff Code
85364900
EAN
3606489861537
UNSPSC
39122329
  • Erhalten Sie bis zu 90 Tage Zahlungsziele von 500+ Lieferanten
  • Wiederverkaufsrabatte bis zu 40%!
Sign-Up
Preisanfrage senden
1
Zahlungsmöglichkeiten:
Fordern Sie ein Angebot an und wir senden Ihnen Informationen zu Verfügbarkeit und Preis.

Specifications

Discrete Output Type
solid state
Range Of Product
Harmony Timer Relays
Product Or Component Type
single function relay
Component Name
RE17L
Time Delay Range
10...100 h || 6...60 s || 6...60 min || 1...10 h || 1...10 s || 1...10 min || 0.1...1 s
Nominal Output Current
0.7 A
Width
17.5 mm
Time Delay Type
off-delay

Complementary

Safety Reliability Data
MTTFd = 353.8 years || B10d = 320000
Setting Accuracy Of Time Delay
+/- 10 % of full scale 25 °C IEC 61812-1
Height
90 mm
Creepage Distance
4 kV/3 IEC 60664-1
Maximum Delay Response
100 ms
Control Type
selector switch front panel
Insulation Resistance
100 MOhm 500 V DC IEC 60664-1
Power Consumption In Va
0-3 VA 240 V AC
Dielectric Strength
2.5 kV 1 mA/1 minute 50 Hz IEC 61812-1
Marking
CE
Voltage Range
0.85...1.1 Us
Reset Time
350 ms on de-energisation typical
Operating Rate In Hz
10 Hz
Net Weight
0.05 kg
Maximum Voltage Drop
<4 V 3-wire || <8 V 2-wire
Mounting Position
any position in relation to normal vertical mounting plane
Voltage Drift
+/- 0.2 %/V
Maximum Switching Voltage
250 V AC
Connections - Terminals
spring terminals, 2 x 0.2...2 x 1.5 mm² AWG 24...AWG 16) solid without cable end || spring terminals, 2 x 0.2...2 x 1.5 mm² AWG 24...AWG 16) flexible without cable end
Functionality
off-delay timing
[Us] Rated Supply Voltage
24...240 V AC 50/60 Hz
Temperature Drift
+/- 0.05 %/°C
Input Voltage
7 V
Minimum Switching Current
10 mA
Mounting Support
35 mm DIN rail conforming to EN/IEC 60715
Maximum Output Current
20 A
Compatibility Code
RE17
On-Load Factor
100 %
Housing Material
self-extinguishing
Impulse Duration
0.05 s typical
Maximum Leakage Current
5 mA
Time Delay Type
C
[Uimp] Rated Impulse Withstand Voltage
5 kV 1.2/50 µs
Depth
72 mm
Electrical Durability
100000000 cycles
Breaking Capacity
0.5 A AC UL || 0.7 A AC 20 °C
Supply Frequency
50...60 Hz +/- 5 %
Repeat Accuracy
+/- 0.5 % IEC 61812-1

Offer Sustainability

Rohs Exemption Information
Yes
Mercury Free
Yes
Environmental Disclosure
ENVPEP121117EN
Sustainable Offer Status
Green Premium product
Reach Regulation
Reference contains Substances of Very High Concern above the threshold
California Proposition 65
WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
Weee
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
China Rohs Regulation
X
Circularity Profile
ENVEOLI121113EN
Eu Rohs Directive
Pro-active compliance (Product out of EU RoHS legal scope)

Environment

Product Certifications
CSA || cULus || DNV-GL || EAC
Ambient Air Temperature For Operation
-20-60 °C
Standards
2004/108/EC || EN 61000-6-3 || 2006/95/EC || EN 61000-6-2 || IEC 61812-1 || EN 61000-6-4 || EN 61000-6-1
Immunity To Microbreaks
20 ms
Electromagnetic Compatibility
electrostatic discharge immunity test 6 kV in contact) level 3 IEC 61000-4-2 || electrostatic discharge immunity test 8 kV in air) level 3 IEC 61000-4-2 || susceptibility to electromagnetic fields 10 V/m 80 MHz to 1 GHz) level 3 IEC 61000-4-3 || electrical fast transient/burst immunity test 1 kV capacitive connecting clip) level 3 IEC 61000-4-4 || electrical fast transient/burst immunity test 2 kV direct) level 3 IEC 61000-4-4 || 1.2/50 µs shock waves immunity test 1 kV differential mode) level 3 IEC 61000-4-5 || 1.2/50 µs shock waves immunity test 2 kV common mode) level 3 IEC 61000-4-5 || conducted RF disturbances 10 V 0.15...80 MHz) level 3 IEC 61000-4-6 || voltage dips and interruptions immunity test 0 % 1 cycle) IEC 61000-4-11 || voltage dips and interruptions immunity test 70 % 25/30 cycles) IEC 61000-4-11 || conducted and radiated emissionsclass B EN 55022
Shock Resistance
15 gn 11 ms IEC 60068-2-27
Vibration Resistance
20 m/s² 10-150 Hz)IEC 60068-2-6
Ip Degree Of Protection
IP20 IEC 60529 terminal block) || IP40 IEC 60529 housing) || IP50 IEC 60529 front panel)
Ambient Air Temperature For Storage
-30-60 °C
Relative Humidity
93-93 % without condensation IEC 60068-2-30
Derating Factor
5 mA/°C

CAD Models

traceparts
traceparts
Herunterladen