Schneider Electric
REL52122
1 / 1
Beschreibung
Aktiv Reif
- Part Number
- REL52122
- Tariff Code
- 8536490055
- UNSPSC
- 39121106
- Erhalten Sie bis zu 90 Tage Zahlungsziele von 500+ Lieferanten
- Wiederverkaufsrabatte bis zu 40%!
Preisanfrage senden
1
Zahlungsmöglichkeiten:
Complementary
- Number Of Key
- 2 customizable
- Local Signalling
- 2 LEDs || 16 LEDs programmable
- Depth
- 230 mm
- Operating Threshold
- 110 V AC/DC
- Time Synchronisation Protocol
- SNTP
- Width
- 270 mm
- Height
- 176 mm
- Display Type
- LCD 128 x 128 pixels with single line diagram || LCD 128 x 128 pixels with ANSI symbols
- Net Weight
- 4.2 kg maximum
- Web Server
- embedded HTTP server
Specifications
- Analogue Output Number
- 0
- Input Type
- 6 1/5 A CT phase current || 2 5/1 A CT residual current || 1 1/0.2 A CT residual current || 4 100 V/110 V VT voltage
- Range Of Product
- PowerLogic P3
- Connections - Terminals
- screw removable (digital input/output) || ring lugs fixed (current transformer) || pin removable (voltage transformer)
- Network And Machine Diagnosis Type
- event recording || disturbance recording || tripping context
- Device Mounting
- flush
- Number Of Outputs
- 14 DO || 1 watchdog
- Protection Type
- overfluxing (V/Hz) 24 || synchro-check 25 || undervoltage 27 || directional active underpower 37P || negative sequence overcurrent 46 || thermal overload protection 49 || earth fault overcurrent 50N/51N || phase overcurrent 50/51 || breaker failure 50BF || switch ON to fault (SOTF) || capacitor bank unbalance 51C || capacitor overvoltage 59C || overvoltage 59 || earth fault overvoltage 59N || restricted earth fault 64REF || directional phase overcurrent 67 || directional earth fault 67N || H2 detection 68H2 || H5 detection 68H5 || underfrequency 81/81N || rate of change of frequency 81R || lockout relay 86 || two-winding transformer differential 87T || programmable stages 99 || programmable curve || cold load pick-up
- Relay Application
- transformer
- Communication Port Protocol
- IEC 61850 ed. 1 || IEC 61850 ed. 2 || IEC 60870-5-101 || DNP3 TCP || Modbus TCP || EtherNet/IP || IEC 60870-5-103 || DNP3 || Modbus RTU || DeviceNet || SPAbus
- Product Or Component Type
- protection relay
- Single Line Diagram
- 6 controlled + 8 displayed
- Monitoring Function
- trip circuit supervision 74 || circuit breaker monitoring || relay self-monitoring
- Analogue Input Number
- 0
- Relay Type
- differential current relay
- Control Type
- switchgear control and monitoring || programmable switchgear interlocking || local control on single-line diagram || local control with I/O keys || local/remote control || 2 function keys || mobile application with Easergy SmartApp || web-server
- Digital Input Number
- 12
- Setting
- 4
- Integrated Connection Type
- front USB port 1 || rear RJ45 1 || rear RS485 1
- Cybersecurity
- password protection || port hardening
- Number Of Sensors
- 0 temperature sensor(s) || 0 arc sensor(s)
- Switchgear Diagnosis Type
- CT/VT supervision || trip circuit supervision TCS
- Arc Flash Protection
- no
- Type Of Measurement
- current 3-phase || current zero sequence || current positive sequence || current negative sequence || current ratio of negative and positive || voltage phase to earth || voltage phase to phase || voltage zero sequence || voltage positive sequence || voltage negative sequence || voltage ratio of negative and positive || short circuit fault reactance || fault location current || earth fault reactance || frequency || active power || RMS active power || reactive power || RMS reactive power || apparent power || RMS apparent power || active energy || reactive energy || cos φ || tan φ || power angle || power factor || voltage phasor diagram view || current phasor diagram view || current 2nd, 15th harmonics with THD || voltage 2nd, 15th harmonics with THD || condition monitoring CB wear || voltage interruption
- Device Short Name
- P3T32-CGG1A-AA1FA-BBAAB
- [Us] Rated Supply Voltage
- 48...230 V AC/DC
Environment
- Mechanical Robustness
- vibrations class II) IEC 60255-21-1 || vibrationsFc IEC 60068-2-6 || shocks class II) IEC 60255-21-2 || shocksEa IEC 60068-2-27 || seismic tests method A class II) IEC 60255-21-3
- Ambient Air Temperature For Operation
- -40-65 °C
- Environmental Characteristic
- exposure to dry heat Bd EN/IEC 60068-2-2 || exposure to cold Ad EN/IEC 60068-2-1 || exposure to damp heat in service Db EN/IEC 60068-2-30 || exposure to damp heat in service Cab EN/IEC 60068-2-78
- Ip Degree Of Protection
- IP54 IEC 60529
- Electromagnetic Compatibility
- emission tests IEC/EN 60255-26 ed. 3 || emission tests class A CISPR 11 || emission tests class A CISPR 22 || EMC immunity IEC/EN 60255-26 ed. 3 || EMC immunity EN/IEC 61000-4-18 || EMC immunity IEC 60255-22-1 || EMC immunity level 4 EN/IEC 61000-4-2 || EMC immunity IEC 60255-22-2 || EMC immunity level 3 EN/IEC 61000-4-3 || EMC immunity IEC 60255-22-3 || EMC immunity level 4 EN/IEC 61000-4-4 || EMC immunity IEC 60255-22-4 || EMC immunity level 3 EN/IEC 61000-4-5 || EMC immunity IEC 60255-22-5 || EMC immunity level 3 EN/IEC 61000-4-6 || EMC immunity IEC 60255-22-6 || EMC immunity EN/IEC 61000-4-8 || EMC immunity level 5 EN/IEC 61000-4-9 || EMC immunity EN/IEC 61000-4-29 || EMC immunity EN/IEC 61000-4-11 || EMC immunity EN/IEC 61000-4-17 || EMC immunity IEC 60255-27 || EMC immunity class III IEC 60255-5 || EMC immunity EN/IEC 60255-1
- Ambient Air Temperature For Storage
- -40-70 °C
- Relative Humidity
- 0-95 %, without condensation
- Protective Treatment
- conformal coating
- Operating Altitude
- 6561.68 ft (2000 m)
Dokumente
Data Sheet
HerunterladenAndere Kategorien
AktuatorenBlöckeKabel, Rohre & SchläucheKompressorenKontrolleKupplungen & FittingsZylinder & KolbenElektronikFilterHVACIndustrie-PCs & HMIsBeleuchtungLineartechnikMotorenStromversorgungLeistungsübertragungPumpen & VentileErneuerbare energieRobotikDichtungen, Ringe & VerbinderSensoren und MessgeräteWerkzeuge und ZubehörCNCSonstiges