This XMLP electronic pressure sensor has a a pressure rating of 10 bar, a M12 connector electrical connection and a G 1/4 a DIN 3852-e male fluid connection. This pressure transmitter is designed for accurate pressure control of air, fresh water, between 0°C and +135°C, refrigeration fluids, hydraulic oils and any fluid compatible with AISI 304 stainless steel, between -30°C and +135°C. It is fixed directly on tubage. It provides high corrosion resistance AISI 316L stainless steel and fluorocarbon resin pressure chamber for maximum longevity. 10 million cycles mechanical durability for minimum required maintenance on your pressurized fluid circuits. It complies with EN/IEC 61326-2-3, RCM, cULus, EAC. Its very short body makes it ideal for fitting in tight tubage areas. This product replaces XMLP010BD71V.- Country of Origin
- CH
- Part Number
- XMLP010BD71F
- Tariff Code
- 90262020
- EAN
- 3389119638784
- UNSPSC
- 41111927
Zahlungsmethoden:
- Bestes Angebot von:
- Vertrauenswürdiger Automa.Net Lieferant
- Verfügbarkeit:
- 1 Stk.Auf LagerAktualisiert am: 21-10-2024
- Geschätzte Lieferung:
- Auf Anfrage
- Zustand:
- Neuer Überschuss
Neuer Überschuss - Ein neuer, unbenutzter, unbeschädigter Artikel ohne Herstellergarantie. Der Artikel kann ohne Originalverpackung oder in Ersatzverpackung geliefert werden. Wenn vorhanden, könnte die Verpackung geöffnet worden sein.
Sicherer Zahlungsprozess
Rückgabe- und Erstattungsrichtlinien
Versandrichtlinien
Garantiebedingungen
Specifications
- Pressure Sensor Type
- pressure transmitter
- Analogue Output Function
- 0...10 V, 3-wire
- Type Of Output Signal
- analogue
- Controlled Fluid
- air -30-135 °C) || fresh water 0-135 °C) || hydraulic oil -30-135 °C) || gas -30-135 °C) || refrigeration fluid -30-135 °C)
- Range Of Product
- Telemecanique Pressure sensors XM
- Electrical Connection
- 1 male connector M12 4 pins
- Pressure Sensor Size
- 10-10 bar
- Quantity Per Set
- set of 1
- Electrical Circuit Type
- control circuit
- Product Or Component Type
- electronic pressure sensors
- Type Of Packing
- individual
- [Us] Rated Supply Voltage
- 24 V DC SELV 12-33 V)
- Local Display
- without
- Pressure Sensor Name
- XMLP
- Current Consumption
- < 7 mA
- Fluid Connection Type
- G 1/4A (male) DIN 3852-E
Complementary
- Accuracy
- 0.1 % of the measuring range
- Diameter
- 26 mm
- [Uimp] Rated Impulse Withstand Voltage
- 0.5 kV
- Mechanical Durability
- 10000000 cycles
- Drift Of The Zero Point
- +/- 0.02 % of measuring range/°K
- Operating Position
- any position
- Electromagnetic Compatibility
- electrical fast transient/burst immunity test EN/IEC 61000-4-4 2 kV || electrostatic discharge immunity test EN/IEC 61000-4-2 8 kV air, 4 kV contact || 1.2/50 µs shock waves immunity test EN/IEC 61000-4-5 1 kV 42 Ohm || immunity to magnetic fields EN/IEC 61000-4-8 100 A/m 50 Hz || susceptibility to electromagnetic fields EN/IEC 61000-4-3 10 V/m 80...3000 MHz || radiated RF fields EN/IEC 61000-4-6 10 V 0.01...80 MHz
- Measurement Accuracy
- +/- 0.5 % of the measuring range
- Protection Type
- load short-circuit || reverse polarity
- Drift Of The Sensitivity
- +/- 0.02 % of measuring range/°K
- Maximum Permissible Accidental Pressure
- 30 bar
- Materials In Contact With Fluid
- fluorocarbon FPM || stainless steel AISI 316L
- Length
- 38.1 mm
- Destruction Pressure
- 60 bar
- Net Weight
- 0.09 kg
- Response Time On Output
- <= 2 ms 10...90 % of full scale
- Pressure Setting Range
- 0-10 bar
Offer Sustainability
- Rohs Exemption Information
- Yes
- Mercury Free
- Yes
- Environmental Disclosure
- ENVPEP1511013EN
- Sustainable Offer Status
- Green Premium product
- Eu Rohs Directive
- Pro-active compliance (Product out of EU RoHS legal scope)
- Reach Regulation
- Reference contains Substances of Very High Concern above the threshold
- California Proposition 65
- WARNING: This product can expose you to chemicals including: Diisononyl phthalate (DINP), which is known to the State of California to cause cancer, and Di-isodecyl phthalate (DIDP), which is known to the State of California to cause birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
Environment
- Product Certifications
- EAC || RCM || CE || cULus
- Ambient Air Temperature For Operation
- -30-85 °C
- Ambient Air Temperature For Storage
- -50-100 °C
- Standards
- EN/IEC 61326-2-3 || NSF ANSI 61
- Shock Resistance
- 100 gn 11 ms EN/IEC 60068-2-27
- Vibration Resistance
- 20 gn 15-2000 Hz) EN/IEC 60068-2-6
- Protective Treatment
- TC
- Ip Degree Of Protection
- IP65 conforming to EN/IEC 60529 || IP67 conforming to EN/IEC 60529 || IP69K conforming to EN/IEC 60529