Schneider Electric
XY2CEDA190H7
1 / 1
Beschreibung
Aktiv Reif
- Country of Origin
- MA
- Part Number
- XY2CEDA190H7
- Tariff Code
- 85365080
- EAN
- 3606480880100
- UNSPSC
- 39122213
Zahlungsmethoden:
- Bestes Angebot von:
- Vertrauenswürdiger Automa.Net Lieferant
- Verfügbarkeit:
- 10 Stk.Auf LagerAktualisiert am: 08-11-2024
- Garantie:
- 12 Monate
- Geschätzte Lieferung:
- Auf Anfrage
- Zustand:
- Neu versiegelt ab Werk
Neu versiegelt ab Werk - Ein brandneuer, unbenutzter, ungeöffneter, unbeschädigter Artikel in seiner original vom Hersteller versiegelten Verpackung.
Sicherer Zahlungsprozess
Rückgabe- und Erstattungsrichtlinien
Versandrichtlinien
Garantiebedingungen
Specifications
- Housing Colour
- red RAL 3000
- Range Of Product
- Telemecanique Emergency stop rope pull switches XY2C
- Overvoltage Category
- class I EN/IEC 61140
- Product Or Component Type
- dual emergency stop rope pull switch
- Device Short Name
- XY2CED
Complementary
- Trigger Cable Maximum Length
- 2 x 100 m
- Connections - Terminals
- screw clamp terminal, 1 x 0.5...2 x 1.5 mm²
- Reset
- by flush push-button
- Contacts Type And Composition
- 2 x (1 NC + 1 NO)
- Number Of Cables
- 2
- Terminals Description Iso N°1
- (21-22)NC || (13-14)NO
- [Ui] Rated Insulation Voltage
- 500 V 3)EN/IEC 60947-1 || 300 VUL 508 || 300 VCSA C22.2 No 14
- Short-Circuit Protection
- 10 A cartridge fuse gG EN/IEC 60269
- Bellow Material
- nitril
- [Ie] Rated Operational Current
- 3 A 240 V, AC-15, A300 EN/IEC 60947-5-1 appendix A || 0.27 A 250 V, DC-13, Q300 EN/IEC 60947-5-1 appendix A
- Contact Operation
- slow-break
- Distance Between Cable Supports
- 3-5 m
- Mechanical Durability
- 60000 cycles
- Positive Opening
- with EN/IEC 60947-5-1
- Cable Entry Number
- 3 tapped entry 1/2" NPT conduit entry
- Compatibility Code
- XY2CED
- Body Material
- zamak
- [Ithe] Conventional Enclosed Thermal Current
- 10 A
- Trigger Cable Anchor Point
- RH and LH sides
- Safety Reliability Data
- B10d = 300000 value given for a life time of 20 years limited by mechanical or contact wear IEC 60947-5-5
- Marking
- CE
- Cover Material
- stainless steel
- Local Signalling
- without pilot light
- Net Weight
- 1.9 kg
- Tightening Torque
- 0.8-1.2 N.m
- [Uimp] Rated Impulse Withstand Voltage
- 6 kV EN/IEC 60947-1
- Maximum Resistance Across Terminals
- 25 MOhm EN/IEC 60255-7 category 3
- Safety Level
- can reach PL = e with the appropriate monitoring system and correctly wired EN/ISO 13849-1 || can reach category 4 with the appropriate monitoring system and correctly wired EN/ISO 13849-1 || can reach SIL 3 with the appropriate monitoring system and correctly wired EN/IEC 61508
Offer Sustainability
- Rohs Exemption Information
- Yes
- Mercury Free
- Yes
- Environmental Disclosure
- ENVPEP111159EN
- Sustainable Offer Status
- Green Premium product
- Eu Rohs Directive
- Pro-active compliance (Product out of EU RoHS legal scope)
- Reach Regulation
- Reference contains Substances of Very High Concern above the threshold
- California Proposition 65
- WARNING: This product can expose you to chemicals including: Diisononyl phthalate (DINP), which is known to the State of California to cause cancer, and Di-isodecyl phthalate (DIDP), which is known to the State of California to cause birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
Environment
- Ambient Air Temperature For Operation
- -25-70 °C
- Ambient Air Temperature For Storage
- -40-70 °C
- Standards
- UL 508 || EN/IEC 60947-5-5 || EN/ISO 13850 || work equipment directive 2009/104/EC || EN/IEC 60204-1 || machinery directive 2006/42/EC || EN/IEC 60947-5-1 || CSA C22.2 No 14
- Product Certifications
- UL category NISD emergency stop devices || CSA || CCC || EAC
- Shock Resistance
- 50 gn 11 ms EN/IEC 60068-2-27
- Vibration Resistance
- 10 gn 10-300 Hz)EN/IEC 60068-2-6
- Protective Treatment
- TC
- Ip Degree Of Protection
- IP66 IEC 60529