- Communication
- Modbus TCP master/slave || Modbus (UDP), CODESYS V3 Library || Modbus (RTU), CODESYS V3 Library || ETHERNET || EtherNet/IPTM Adapter (slave) || EtherNet/IPTM Scanner || EtherCAT® Master || OPC UA Server/Client || OPC UA Pub/Sub (can be installed later) || MQTT || BACnet/IP, requires an additional license || Telecontrol protocols, requires an additional license
- ETHERNET protocols
- DHCP || DNS || NTP || FTP || FTPS || SNMP || HTTP || HTTPS || SSH
- Telecontrol protocols
- IEC 60870-5-101/-103/-104 (additional license as slave or master) || IEC-61850 (additional license as Client 300) || DNP3 (additional license as Slave or Master 300)
- Visualization
- Web-Visu
- Operating system
- Real-time Linux (with RT-Preempt patch)
- CPU
- Cortex A8; 1 GHz
- Programming languages per IEC 61131-3
- Instruction List (IL) || Ladder Diagram (LD) || Function Block Diagram (FBD) || Continuous Function Chart (CFC) || Structured Text (ST) || Sequential Function Chart (SFC)
- Programming environment
- CODESYS V3.5, from firmware release 23 || e!COCKPIT (based on CODESYS V3), up to firmware release 22 || WAGO-I/O-PRO V2.3 (based on CODESYS V2.3), up to firmware release 22
- Configuration options
- CODESYS V3 || e!COCKPIT || WAGO-I/O-CHECK || Web-Based Management || e!RUNTIME library || CODESYS Library
- Baud rate (communication/fieldbus 1)
- 10/100 Mbit/s
- Baud rate
- ETHERNET: 10/100 Mbit/s
- Transmission medium (communication/fieldbus)
- ETHERNET: Twisted pair S-UTP; 100 Ω; Cat. 5; 100 m maximum cable length;
- Main memory (RAM)
- 512 MB
- Internal memory (flash)
- 4096 MB
- Non-volatile hardware memory
- 128 KB
- Program memory
- CODESYS V2: 16 MB; CODESYS V3: 32 MB
- Data memory
- CODESYS V2: 64 MB; CODESYS V3: 128 MB
- Non-volatile software memory
- 128 KB || 128 KB
- Type of memory card
- SD and SDHC up to 32 GB (all guaranteed properties only valid with WAGO Memory Card)
- Memory card slot
- Push-push mechanism; cover lid (sealable)
- Number of modules per node (max.)
- 250
- Number of modules without a bus extension (max.)
- 64
- Input and output process image (internal) max.
- 1000 words/1000 words
- Input and output process image (Modbus®) max.
- CODESYS V2: 1000 words/1000 words; CODESYS V3: 32000 words/32000 words
- Indicators
- LED (SYS, RUN, I/O, U1 … U7) red/green/orange: Status of system, program, local data bus, status programmable by user (can be used via CODESYS library); LED (A, C) green: Status of system power supply, field supply
- Supply voltage (system)
- 24 VDC (-25 … +30 %); via pluggable connector (CAGE CLAMP® connection)
- Input current (typ.) at nominal load (24 V)
- 550 mA
- Total current (system supply)
- 1700 mA
- Supply voltage (field)
- 24 VDC (-25 … +30 %); via power jumper contacts
- Current carrying capacity (power jumper contacts)
- 10 A
- Number of outgoing power jumper contacts
- 3
- Isolation
- 500 V system/field