Wago

883-3504

1 / 2
thumbnail
thumbnail
Part Number
883-3504
Tariff Code
85369010000
UPC
4055143940658
ETIM
Group Code : EG000012
Group Description : Terminal blocks
Class Description : Feed-through terminal block
Class Code : EC000897
Version : 7
  • Erhalten Sie bis zu 90 Tage Zahlungsziele von 500+ Lieferanten
  • Wiederverkaufsrabatte bis zu 40%!
Sign-Up
Preisanfrage senden
1
Zahlungsmöglichkeiten:
Fordern Sie ein Angebot an und wir senden Ihnen Informationen zu Verfügbarkeit und Preis.

Ratings Per Iec/En

Ratings per
IEC/EN 60947-7-1
Nominal voltage (III/3)
1000 V
Rated impulse voltage (III/3)
8 kV
Rated current
125 A
Current at conductor cross-section (max.) mm²
150 A
Legend (ratings)
(III / 3) ≙ Overvoltage category III / Pollution degree 3

Environmental Requirements

Continuous operating temperature
-35 … +105 °C

Physical Data

Width
16.1 mm / 0.634 inches
Height
59 mm / 2.323 inches
Depth from upper-edge of DIN-rail
65.5 mm / 2.579 inches

Material Data

Note (material data)
Information on material specifications can be found here
Color
Blue
Insulation material
Polyamide (PA66)
Flammability class per UL94
V0
Fire load
0.000 MJ
Weight
58.000 g

Mechanical Data

Tightening torque
3.2 … 3.7 Nm
Mounting type
DIN-rail 35 x 7.5
Marking level
Side marking

Specifications

Product Group Code
0001

Commercial Data

Packaging type
Box
Country of origin
DE
GTIN
4055143940658
Customs tariff number
85369010000

Ratings Per Csa

Approvals per
CSA 22.2 No 158
Rated voltage CSA (Use Group C)
600 V
Rated current CSA (Use Group C)
150 A

Power Loss

Power loss, per pole (potential)
4.0625 W
Rated current IN for specified power loss
125 A
Resistance value for specified, current-dependent power loss
0.00026 Ω

Connection 1

Connection technology
Screw connection
Actuation type
Slot screwdriver; (6.5 x 1.2) mm blade
Connectable conductor materials
Copper || Aluminum
Connectable conductor materials (note)
Terminating Aluminum Conductors Both restrictions and application notes must be observed when terminating aluminum conductors. These instructions can be found in the WAGO Webshop under “Downloads – Documentation – Additional Information: Terminating Aluminum Conductors.”
Nominal cross-section
35 mm²
Solid conductor
1.5 … 50 mm² / 16 … 1/0 AWG
Stranded conductor
1.5 … 50 mm² / 16 … 1/0 AWG
Fine-stranded conductor
1.5 … 50 mm² / 16 … 1/0 AWG
Fine-stranded conductor; with insulated ferrule
1.5 … 35 mm² / 16 … 2 AWG
Note (conductor cross-section)
Connecting 50 mm² is only possible on a copper DIN 35 x 15 rail (2.3 mm thick).
Strip length
18 mm / 0.71 inches
Wiring direction
Side-entry wiring
Screw thread
M6

Ratings Per Ul 1059

Approvals per
UL 1059
Rated voltage UL (Use Group B)
600 V
Rated current UL (Use Group B)
150 A
Rated voltage UL (Use Group C)
600 V
Rated current UL (Use Group C)
150 A

Ähnliche Produkte