Weidmuller
1352270000
1 / 2
Beschreibung
Surge voltage arrester, Low voltage, with remote contact, Single-phase, IT with N, IT without N, TN- Part Number
- 1352270000
Zahlungsmethoden:
- Bestes Angebot von:
- Vertrauenswürdiger Automa.Net Lieferant
- Verfügbarkeit:
- 3 Stk.Auf LagerAktualisiert am: 30-04-2024
- Geschätzte Lieferung:
- Auf Anfrage
- Zustand:
- Neu versiegelt ab Werk
Neu versiegelt ab Werk - Ein brandneuer, unbenutzter, ungeöffneter, unbeschädigter Artikel in seiner original vom Hersteller versiegelten Verpackung.
Sicherer Zahlungsprozess
Rückgabe- und Erstattungsrichtlinien
Versandrichtlinien
Garantiebedingungen
General Data
- Colour
- black, orange, blue
- Design
- Installation housing; 2TE, Insta IP 20
- Optical function display
- green = OK; red = arrester is defective - replace
- Protection degree
- IP20
- Rail
- TS 35
- Segment
- Power distribution
- UL 94 flammability rating
- V-0
- Version
- with remote contact
Approvals
- Approvals
- CE, EAC, OEVE
- ROHS
- Conform
Insulation Coordination Acc. To En 50178
- Pollution severity
- 2
- Surge voltage category
- IV
Rated Data Iec / En
- Discharge current I
- 20 kA
- Energy coordination (≤10 m)
- Type I, Type II, Type III
- Follow-on current extinguishing capability I
- Not available due for technical reasons
- Frequency range, max.
- 60 Hz
- Frequency range, min.
- 50 Hz
- Fuse
- 250 A gL (if back up fuse > 250 A)
- Leakage current at U
- 100 µA
- Lightning test current I
- 12.5 kA
- Lightning test current, I
- 50 kA
- Low voltage network
- Single-phase, IT with N, IT without N, TN
- Max. continuous voltage, Uc (AC)
- 280 V
- Max. continuous voltage, Uc (N-PE)
- 260 V
- Number of poles
- 2
- Protection level U
- ≤ 1.5 kV
- Rated voltage (AC)
- 230 V
- Requirements category acc. to IEC 61643-11
- Type I, Type II
- Requirements class, acc. to EN 61643-11
- T1, T2
- Response time
- ≤ 25 ns, ≤ 100 ns
- Short-circuit current rating I
- 25 kA
- Signalling contact
- 250 V 1A 1CO
- Standards
- IEC61643-11, EN61643-11
- Temporary surge voltage (over-voltage) - TOV
- 438 V
- Voltage type
- AC
Dimensions And Weights
- Width
- 35.6 mm
- Width (inches)
- 1.402 inch
- Height
- 106 mm
- Height (inches)
- 4.173 inch
- Depth
- 69 mm
- Depth (inches)
- 2.717 inch
- Mounting dimension - height
- 75 mm
- Net weight
- 304 g
Connection Data
- Type of connection
- Screw connection
- Stripping length, rated connection
- 15 mm
- Tightening torque, min.
- 2 Nm
- Tightening torque, max.
- 3 Nm
- Clamping range, rated connection
- 16 mm²
- Clamping range, min.
- 4 mm²
- Clamping range, max.
- 35 mm²
- Wire cross-section, solid, min.
- 2.5 mm²
- Wire cross-section, solid, max.
- 16 mm²
- Wire connection cross-section, finely stranded, min.
- 2.5 mm²
- Wire connection cross section, finely stranded, max.
- 25 mm²
- Conductor cross-section, flexible, AEH (DIN 46228-1), min.
- 2.5 mm²
- Conductor cross-section, flexible, AEH (DIN 46228-1), max.
- 50 mm²
- Connection cross-section, stranded, min.
- 2.5 mm²
- Connection cross-section, stranded, max.
- 50 mm²
Tender Specification Sheets
- Long specification
- Multi-pin lightning arrestor according to the requirements of Class I in accordance with IEC 61643-11, EN61643-11:2013. On interface transition from 0 to 1 (in accordance with IEC 1312-1), the arrestor, made from V0 material, serves as lightning protection providing equipotential bonding and is used in applications in accordance with IEC 61643-12. The use of a high-performance varistor meets the inspection requirements for Class I surge protection systems according to the VDEW (Association of German Power Stations) directive. The arrestor is installed in the vicinity of the power supply for the equipment that needs protection, in a standard installation/electrical distribution enclosure. The VPU I 1+1 R 280 V/12.5 kA is used in the single-phase mains network. With thermal separation device on the varistor. If protection is no longer available, the colour in the display window changes from green to red. The functional state is also displayed by a voltage-free signalling contact (changeover). Rated voltage: 230 VAC lightning test current (10/350 µs): 12.5 kA protection level with lightning test current < 1.4 kV 25 kA short-circuit withstand rating with max. back-up fuse of 250 A gl telecommunication output: contact: 250 V/0.5 A 48 VDC/0.1 A, type: Weidmüller VPU I 1+1 R 280 V/12.5 kA, Order No. 1352270000 or equivalent
- Short specification
- Class I arrester for LPL III/IV with 12.5 kA suitable for 230/400 V single-phase mains systems. Protection level < 1.45 kV. With remote alert Type: Weidmüller VPU I 1+1 R 280 V/12.5 kA Order no. 1352270000 or equivalent
Classifications
- ETIM 6.0
- EC000941
- ETIM 7.0
- EC000941
- EClass 9.0
- 27-13-08-05
- EClass 9.1
- 27-13-08-05
- EClass 10.0
- 27-13-08-05
- UNSPSC
- 30-21-19-22
Connection Data, Remote Alert
- Connection type
- PUSH IN
- Stripping length
- 8 mm
- Cross-section for connected wire, solid core, min.
- 0.14 mm²
- Cross-section for connected wire, solid core, max.
- 1.5 mm²
Temperatures
- Humidity
- 5 - 95% rel. humidity
- Operating temperature, max.
- 70 °C
- Operating temperature, min.
- -40 °C
- Storage temperature, max.
- 80 °C
- Storage temperature, min.
- -40 °C
- Operating temperature
- -40 °C...70 °C
- Storage temperature
- -40 °C...80 °C
Andere Kategorien
AktuatorenBlöckeKabel, Rohre & SchläucheKompressorenKontrolleKupplungen & FittingsZylinder & KolbenElektronikFilterHVACIndustrie-PCs & HMIsBeleuchtungLineartechnikMotorenStromversorgungLeistungsübertragungPumpen & VentileErneuerbare energieRobotikDichtungen, Ringe & VerbinderSensoren und MessgeräteWerkzeuge und ZubehörCNCSonstiges