Weidmuller

7760054306

ACT20P-VM-AO-S
7760054306
7760054306
7760054306
7760054306
  • Erhalten Sie bis zu 90 Tage Zahlungsziele von 500+ Lieferanten
  • Wiederverkaufsrabatte bis zu 40%!
Sign-Up
Preisanfrage senden
1
Zahlungsmöglichkeiten:
Fordern Sie ein Angebot an und wir senden Ihnen Informationen zu Verfügbarkeit und Preis.
Angebot mit Herstellervorlaufzeit
Lieferung:Auf Anfrage
Bester Preis:
€117.89

Additional Information

Part Number
7760054306

General Data

Accuracy
0.5 % FSR
Configuration
With FDT/DTM software
Galvanic isolation
3-way isolator, between input ⁄ output ⁄ supply
Power consumption
≤ 100 mA @ 24 VDC, ≤ 120mA @ 24V AC
Rail
TS 35
Step response time
< 300 ms
Temperature coefficient
≤ 200 ppm/K
Voltage supply
24…240 VUC (±10%)

Approvals

Approvals
CE, EAC
ROHS
Conform

Dimensions And Weights

Width
22.5 mm
Width (inches)
0.886 inch
Height
119.2 mm
Height (inches)
4.693 inch
Depth
114.3 mm
Depth (inches)
4.5 inch
Net weight
110 g

Connection Data

Type of connection
Screw connection
Tightening torque, min.
0.4 Nm
Tightening torque, max.
0.6 Nm
Clamping range, rated connection
1.5 mm²
Clamping range, min.
0.5 mm²
Clamping range, max.
2.5 mm²
Wire connection cross section AWG, min.
AWG 26
Wire connection cross section AWG, max.
AWG 12

Input

Number of inputs
1
Input signal
UDC, UACEffective value (sinusoidal only) 40-60 Hz
Input voltage
0…30 V DC, 0…60 V DC, 0…150 V DC, 0…300 V DC, 0…440 V DC, 0…660 V DC, 0…60 V AC, 0…144 V AC, 0…300 V AC, 0…440 V AC
Input resistance
1 MΩ±5%

Classifications

ETIM 6.0
EC002653
ETIM 7.0
EC002653
EClass 9.0
27-21-01-20
EClass 9.1
27-21-01-20
EClass 10.0
27-21-01-20

Output

Number of outputs
1
Output voltage, note
0...10 V
Output current
0(4)...20 mA
Load impedance voltage
≥ 10 kΩ
Load impedance current
≤ 500 Ω

Product Information

Product information
The analogue voltage converter ACT20P-VM-AO-S measures DC or AC voltages. The analogue input signal is linearly converted into an analogue output signal (current or voltage) and galvanically isolated. Features Configuration and monitoring are performed via FDT/DTM-Software „WI-Manager“. Signal and alarm triggering upon exceeding limit values or reverse polarity DC input voltage Front LED indicates operation status 3-way galvanic isolation between input, output and power supply.

Environmental Product Compliance

REACH SVHC
Lead 7439-92-1

Insulation Coordination

EMC standards
IEC 61000-6 /-2, IEC 61000-6-4, IEC 61326-1
Galvanic isolation
3-way isolator, between input ⁄ output ⁄ supply
Impulse withstand voltage
4 kV (1.2 / 50 μs) input - output/ supply, 6 kV (input - output), 1.2/50 µs
Insulation voltage input or output/supply
2.2 kVAC, 1 min, 50 Hz
Pollution severity
2
Rated voltage
300 VAC (supply-output), 500 VAC (supply-input; input-output)
Surge voltage category
III

Temperatures

Humidity
5...95 %, no condensation
Operating temperature, max.
65 °C
Operating temperature, min.
-25 °C
Storage temperature, max.
85 °C
Storage temperature, min.
-40 °C
Operating temperature
-25 °C...65 °C
Storage temperature
-40 °C...85 °C