Weidmuller

7906100000

BK 12/E
7906100000
  • Erhalten Sie bis zu 90 Tage Zahlungsziele von 500+ Lieferanten
  • Wiederverkaufsrabatte bis zu 40%!
Sign-Up
€57.27
1
Zahlungsmöglichkeiten:
Insgesamt 291 Parts In-Stock von 11 Distributors
Angebot mit Herstellervorlaufzeit
Lieferung:Auf Anfrage
Bester Preis:
€11.63

Additional Information

Part Number
7906100000

Approvals

Approvals
CSA, EAC, IECEXTUR, KEMAKEUR, TUEVNATEX, UR
ROHS
Conform
UL File Number Search
E60693

Dimensions And Weights

Width
22 mm
Width (inches)
0.866 inch
Height
92 mm
Height (inches)
3.622 inch
Depth
20 mm
Depth (inches)
0.787 inch
Net weight
71.6 g

Csa Rating Data

Certificate No. (CSA)
200039-2165696
Current size B (CSA)
10 A
Current size D (CSA)
10 A
Voltage size B (CSA)
300 V
Voltage size D (CSA)
300 V
Wire cross section max. (CSA)
12 AWG
Wire cross section min. (CSA)
22 AWG

Additional Technical Data

Explosion-tested version
Yes
Installation advice
Direct mounting
Type of mounting
Direct mounting

Material Data

Material
KrG
Colour
medium yellow
UL 94 flammability rating
V-0, 5VA

Safety Note

Safety notice
Safety Information

Classifications

ETIM 6.0
EC001284
ETIM 7.0
EC001284
EClass 9.0
27-14-11-06
EClass 9.1
27-14-11-06
EClass 10.0
27-14-11-06
UNSPSC
30-21-18-11

System Specifications

Version
For the mounting rails
End cover plate required
No

Temperatures

Operating temperature range
For operating temperature range see EC Design Test Certificate / IEC Ex-Certificate of Conformity
Storage temperature, max.
40 °C
Storage temperature, min.
10 °C
Storage temperature
10 °C...40 °C
Continuous operating temp., min.
-60 °C
Continuous operating temp., max.
130 °C

Rating Data

Rated cross-section
4 mm²
Rated voltage
400 V
Rated current
32 A
Current at maximum wires
32 A
Standards
IEC 60947-7-1
Volume resistance according to IEC 60947-7-x
1 mΩ
Power loss in accordance with IEC 60947-7-x
1.02 W
Rated impulse withstand voltage
6 kV
Pollution severity
3

Rating Data Iecex/Atex

Certificate No. (ATEX)
TUEV18ATEX8209U
Certificate No. (IECEX)
IECEXTUR18.0019U
Max. voltage (ATEX)
275 V
Current (ATEX)
28 A
Wire cross section max. (ATEX)
4 mm²
Max. voltage (IECEX)
275 V
Current (IECEX)
28 A
Wire cross section max. (IECEX)
4 mm²
Operating temperature range
For operating temperature range see EC Design Test Certificate / IEC Ex-Certificate of Conformity
Marking EN 60079-7
Ex eb II C Gb
Ex 2014/34/EU label
II 2 G D

Conductors For Clamping (Rated Connection)

Blade size
4.0 x 0.8 mm
Clamping range, max.
4 mm²
Clamping range, min.
0.33 mm²
Clamping screw
M 3
Connection cross-section, stranded, max.
4 mm²
Connection cross-section, stranded, min.
1.5 mm²
Connection direction
on side
Gauge to IEC 60947-1
A3
Number of connections
24
Stripping length
8 mm
Tightening torque, max.
0.6 Nm
Tightening torque, min.
0.5 Nm
Torque level with DMS electric screwdriver
2
Type of connection
Screw connection
Wire connection cross section AWG, max.
AWG 12
Wire connection cross section AWG, min.
AWG 22
Wire connection cross section, finely stranded, max.
4 mm²
Wire connection cross-section, finely stranded with wire-end ferrules DIN 46228/1, max.
4 mm²
Wire connection cross-section, finely stranded with wire-end ferrules DIN 46228/1, min.
0.5 mm²
Wire connection cross-section, finely stranded with wire-end ferrules DIN 46228/4, max.
4 mm²
Wire connection cross-section, finely stranded with wire-end ferrules DIN 46228/4, min.
0.5 mm²
Wire connection cross-section, finely stranded, min.
0.5 mm²
Wire connection cross-section, solid core, max.
4 mm²
Wire connection cross-section, solid core, min.
0.5 mm²

Ul Rating Data

Certificate No. (UR)
E60693
Conductor size Factory wiring max. (UR)
12 AWG
Conductor size Factory wiring min. (UR)
26 AWG
Conductor size Field wiring max. (UR)
12 AWG
Conductor size Field wiring min. (UR)
22 AWG
Current size B (UR)
20 A
Current size C (UR)
20 A
Current size D (UR)
10 A
Voltage size B (UR)
250 V
Voltage size C (UR)
150 V
Voltage size D (UR)
300 V
Wire cross section max. (UR)
12 AWG
Wire cross section min. (UR)
22 AWG