Sensor/actuator box 1683659
1683659
  • Ottenete termini di pagamento fino a 90 giorni da 500+ fornitori.
  • Sconti sulla rivendita fino al 40%!
Registrati
Invia una richiesta di prezzo
1
Metodi di pagamento:
Richiedete un preventivo e vi invieremo informazioni su disponibilità e prezzi.
Offerta con tempi di consegna del produttore
Spedizione in:Su richiesta
Miglior prezzo:
289,67 zł

Additional Information

Part Number
1683659
UPC
4017918170981
Country of Origin
PL

Conductor data

Structure of individual litz in acc. with VDE 0295 / smallest wire diameter
Class 2-6 // 0.34 mm²: 0.1 mm; 0.5 - 0.75 mm²: 0.15 mm
Wire insulation material
PVC / PE
Wire diameter including insulation
≤ 2.5 mm
Minimum external conductor diameter
4 mm
Maximum external conductor diameter
7.5 mm
Tightening torque, union nut
2.5 Nm
Wrench size, union nut
22 mm
Note on the frequency of connections
if the conductor is connected more than once, seal and cap may need to be replaced.
Conductor cross section flexible min.
0.34 mm²
Conductor cross section flexible max.
0.75 mm²
Conductor cross section AWG min.
22
Conductor cross section AWG max.
18

Pin assignment

Slot/position = Wire color or connection
1 / 4 (A) = 1 / 4
Slot/position = Wire color or connection
2 / 4 (A) = 2 / 4
Slot/position = Wire color or connection
3 / 4 (A) = 3 / 4
Slot/position = Wire color or connection
4 / 4 (A) = 4 / 4
Slot/position = Wire color or connection
5 / 4 (A) = 5 / 4
Slot/position = Wire color or connection
6 / 4 (A) = 6 / 4
Slot/position = Wire color or connection
7 / 4 (A) = 7 / 4
Slot/position = Wire color or connection
8 / 4 (A) = 8 / 4
Slot/position = Wire color or connection
1-8 / 1 (+ 120 V) = UN
Slot/position = Wire color or connection
1-8 / 3 (0 V) = 0 V
Slot/position = Wire color or connection
1-8 / 5 (PE) = PE

Ambient conditions

Degree of protection
IP65
Degree of protection
IP67
Ambient temperature (operation)
-25 °C - 60 °C

Insulation material

Housing material
PA
Material of the moulding mass
PUR
Contact material
Steel/copper
Contact surface material
Sn
Contact carrier material
PA 6.6
Material of contact, master cable side
CuZn
Material of contact surface, master cable side
NiSn
Material of the contact carrier on the master cable side
PA 6.6 V0

Master cable data/connection data

Connection method
Spring-cage connection
Conductor cross section min. (signal)
0.14 mm²
Conductor cross section max. (signal)
1 mm²
Conductor cross section AWG min. (signal)
26
Conductor cross section AWG max. (signal)
17
Stripping length (signal)
10 mm
Conductor cross section min. (energy)
0.2 mm²
Conductor cross section max. (energy)
1.5 mm²
Conductor cross section AWG min. (energy)
24
Conductor cross section AWG max. (energy)
16
External cable diameter min.
6.5 mm
External cable diameter max.
9.5 mm
Stripping length
70 mm (Master cable)
Tightening torque, union nut
2.5 Nm

Environmental Product Compliance

China RoHS
Environmentally Friendly Use Period = 50
China RoHS
For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration”

Standards and Regulations

Connection in acc. with standard
CUL
Flammability rating according to UL 94
V0