Specifications

Input Voltage (V)
200 to 480VAC
Maximum Input Power
5W
Input AC Line Frequency (Hz)
50/60Hz
Output Load Rating (VA)
Pilot Duty: 480VA @ 240VAC; General purpose: 10A @ 240VAC
Timing Accuracy (%)
5% ±1s
Rapid Cycle Timer (s)
0 2 - 500s
Restart Delay Range
Restart Delay After All Faults: 2 - 500s
Repeat Accuracy (%)
Voltage: ±0.5%
Trip Delay Range
Voltage/Unbalance/Frequency Faults/Single-Phase Faults: 1 - 50s
Overvoltage Reset Voltage (%)
97% of HV Setting
Undervoltage Reset Voltage (%)
103% of LV Setting
Voltage Unbalance Reset (%)
UB Setting -1%
Voltage Accuracy (%)
±1%
Over/Under Frequency (%)
Low: 35Hz - HF setting; High: LF setting - 75Hz
Protection Class
IP20 NEMA 1 (finger safe)
Address
A01-A99
Termination Type
Torque: 7in-lbs
Mounting Method
Surface mount (4 - #8 screws) or DIN rail mount
Operating Temperature
-20° to 70°C (-4° to 158°F)
Storage Temperature (F/C)
-40° to 80°C (-40° to 176°F)
Humidity
10 - 95% non-condensing per IEC 68-2-3
Dimensions
3.05 in H x 3.85 in W x 5.05 in D (77.5 x 97.8 x 128.3 mm)
Weight (lbs/g)
1.2 lbs. (19.2 oz. 544.3 g)

Documents

Data Sheet