Phoenix Contact
2814647
Current transducers - MCR-S-10/50-UI-DCI - 2814647
- Get up to 90 days payment terms from 500+ suppliers
- Reselling discounts up to 40%!
$175.49
1
Payment methods:
A total of 11 Parts In-Stock from 8 Distributors
Product Conditions:
Offer with manufacturer lead time
Ships in:On Request
Best price:
€322.00
Additional Information
- Part Number
- 2814647
- Country of Origin
- DE
- ETIM
- Group Code : EG000026
- Group Description : Sensors
- Class Description : Current value transformer
- Class Code : EC002475
- Version : 7
Input data
- Input
- Current measuring input
- Configurable/programmable
- Yes, preconfigured
- Input current range
- 0 A - 55 A (AC/DC)
- Operate threshold
- 0.8 % (of measuring range nominal value 50 A)
- Setting range for min. input current
- 0 A - 9.5 A
- Setting range for max. input current
- 0 A - 55 A
- Impulse form
- AC, DC or distorted currents
- Overload capacity
- Depending on through connected conductor
- Surge strength
- Depending on through connected conductor
- Frequency measuring range
- 15 Hz - 400 Hz
- Connection method
- Through connection, diameter 10.5 mm
Note
- Utilization restriction
- EMC: class A product, see manufacturer's declaration in the download area
Dimensions
- Width
- 22.5 mm
- Height
- 99 mm
- Depth
- 114.5 mm
Connection data
- Connection method
- Screw connection
- Stripping length
- 8 mm
- Screw thread
- M3
- Conductor cross section solid
- 0.2 mm² - 2.5 mm²
- Conductor cross section flexible
- 0.2 mm² - 2.5 mm²
- Conductor cross section AWG
- 24 - 14
Output data
- Output name
- Voltage output / current output
- Configurable/programmable
- Yes, preconfigured
- Voltage output signal
- 0 V - 10 V
- Voltage output signal
- 2 V - 10 V
- Voltage output signal
- -10 V - 10 V
- Voltage output signal
- 0 V - 5 V
- Voltage output signal
- 1 V - 5 V
- Voltage output signal
- -5 V - 5 V
- Voltage output signal
- 10 V - 0 V
- Voltage output signal
- 10 V - 2 V
- Voltage output signal
- 10 V - -10 V
- Voltage output signal
- 5 V - 0 V
- Voltage output signal
- 5 V - 1 V
- Voltage output signal
- 5 V - -5 V
- Current output signal
- 0 mA - 20 mA
- Current output signal
- 4 mA - 20 mA
- Current output signal
- 20 mA - 0 mA
- Current output signal
- 20 mA - 4 mA
- Load/output load voltage output
- > 10 kΩ
- Load/output load current output
- < 500 Ω
Ambient conditions
- Ambient temperature (operation)
- -20 °C - 60 °C
- Ambient temperature (storage/transport)
- -40 °C - 85 °C
- Maximum altitude
- < 2000 m
- Degree of protection
- IP20
- Noise immunity
- EN 61000-6-2
Conformance/approvals
- Designation
- CE
- Identification
- CE-compliant
- Designation
- UL, USA/Canada
- Identification
- Class I, Zone 2, AEx nA nC IIC T4, Ex nA nC IIC T4 Gc X
- Identification
- Class I, Div. 2, Groups A, B, C and D or Non-Hazardous Locations Only
Environmental Product Compliance
- REACh SVHC
- Lead 7439-92-1
- China RoHS
- Environmentally Friendly Use Period = 50 years
- China RoHS
- For details about hazardous substances go to tab 'Downloads', Category 'Manufacturer's declaration'
Switching output
- Output name
- No switching output
Standards and Regulations
- Electromagnetic compatibility
- Conformance with EMC directive
- Noise emission
- EN 61000-6-4
- Noise immunity
- EN 61000-6-2
- Connection in acc. with standard
- CUL
- Low Voltage Directive
- Conformance with Low Voltage Directive
- Conformance
- CE-compliant
- UL, USA/Canada
- Class I, Zone 2, AEx nA nC IIC T4, Ex nA nC IIC T4 Gc X
- UL, USA/Canada
- Class I, Div. 2, Groups A, B, C and D or Non-Hazardous Locations Only
Power supply
- Supply voltage range
- 20 V DC - 30 V DC
- Max. current consumption
- < 40 mA (without load)
Other Categories
NanometersManometersFlowmetersSensorsAcceleration SensorsFiber Optic SensorsDetectorsUltrasonic SensorsTemperature & Humidity SensorsVibration SensorsLevel SensorsPressure SensorsProximity SensorsInductive SensorsMotion SensorsMagnetic Sensors GroupOptical SensorsCapacitive SensorsPhotoelectric SensorsPosition SensorsEncodersOther sensors and Accessories