- Number of Main Contacts NO
- 2
- Number of Main Contacts NC
- 2
- Number of Auxiliary Contacts NO
- 0
- Number of Auxiliary Contacts NC
- 0
- Standards
- IEC/EN 60947-1, IEC/EN 60947-4-1, UL 60947-1, UL 60947-4-1, CSA C22.2 No. 60947-1:22, CSA C22.2 No. 60947-4-1:22
- Rated Operational Voltage
- Main Circuit 690 V
- Rated Frequency (f)
- Control Circuit 50 / 60 HzMain Circuit 50 / 60 Hz
- Conventional Free-air Thermal Current (Ith)
- acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 105 A
- Rated Operational Current AC-1 (Ie)
- (690 V) 40 °C 70 A(690 V) 60 °C 60 A(690 V) 70 °C 50 A
- Rated Operational Current AC-3 (Ie)
- (415 V) 60 °C 40 A(440 V) 60 °C 40 A(500 V) 60 °C 35 A(690 V) 60 °C 25 A(380 / 400 V) 60 °C 40 A(220 / 230 / 240 V) 60 °C 40 A
- Rated Operational Power AC-3 (Pe)
- (415 V) 22 kW(440 V) 22 kW(500 V) 22 kW(690 V) 22 kW(380 / 400 V) 18.5 kW(220 / 230 / 240 V) 11 kW
- Rated Short-time Withstand Current Low Voltage (Icw)
- at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 600 Aat 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 110 Aat 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 250 Aat 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 1000 Aat 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 350 A
- Maximum Breaking Capacity
- cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 950 Acos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 600 A
- Maximum Electrical Switching Frequency
- (AC-1) 600 cycles per hour
- Rated Insulation Voltage (Ui)
- acc. to IEC 60947-4-1 690 Vacc. to UL/CSA 600 V
- Rated Impulse Withstand Voltage (Uimp)
- 6 kV
- Maximum Mechanical Switching Frequency
- 3600 cycles per hour
- Rated Control Circuit Voltage (Uc)
- 50 Hz 48 ... 130 V60 Hz 48 ... 130 VDC Operation 48 ... 130 V
- Coil Consumption
- Average Holding Value 50 / 60 Hz 4 V·AAverage Holding Value 50 Hz 4 V·AAverage Holding Value 60 Hz 4 V·AAverage Holding Value DC 2 WAverage Holding Value, from Warm State 2 W
- Mounting on DIN Rail
- TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715
- Mounting by Screws (not supplied)
- 2 x M4 or 2 x M6 screws placed diagonally
- Connecting Capacity Main Circuit
- Flexible with Ferrule 1/2x 4 ... 35 mm²Flexible with Insulated Ferrule 1/2x 4 ... 35 mm²Rigid Stranded 1/2x 6 ... 35 mm²
- Connecting Capacity Control Circuit
- Flexible with Ferrule 1/2x 0.75 ... 2.5 mm²Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm²Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm²Rigid Solid 1/2x 1 ... 2.5 mm²Rigid Stranded 1/2x 1 ... 2.5 mm²
- Wire Stripping Length
- Control Circuit 10 mmMain Circuit 16 mm
- Degree of Protection
- acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP10
- Terminal Type
- Screw Terminals