ABB
1SFL487002R1411
AF190-30-11-14 Contactor
- Termin płatności do 90 dni od 500+ dostawców.
- Rabaty na odsprzedaż do 40%!
€294.42
1
Metody płatności:
Łącznie 33 części w magazynie od 12 dostawców
Stan produktu:
Oferta z czasem realizacji przez producenta
Wysyłka:Na zapytanie
Najlepsza cena:
€258.89
Additional Information
- Part Number
- 1SFL487002R1411
- UNSPSC
- 39121529
- ETIM
- Group Code : EG000017
- Group Description : Low-voltage Industrial Components
- Class Description : Power contactor, AC switching
- Class Code : EC000066
- Version : 7
Dimensions
- Product Net Width
- 105 mm
- Product Net Depth / Length
- 152 mm
- Product Net Height
- 196 mm
- Product Net Weight
- 2.4 kg
Technical
- Number of Main Contacts NO
- 3
- Number of Main Contacts NC
- 0
- Number of Auxiliary Contacts NO
- 1
- Number of Auxiliary Contacts NC
- 1
- Rated Operational Voltage
- Main Circuit 1000 V
- Rated Frequency (f)
- Main Circuit 50 / 60 Hz
- Conventional Free-air Thermal Current (Ith)
- acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 275 A
- Rated Operational Current AC-1 (Ie)
- (1000 V) 40 °C 250 A(1000 V) 55 °C 225 A(1000 V) 60 °C 225 A(1000 V) 70 °C 185 A(690 V) 40 °C 275 A(690 V) 55 °C 250 A(690 V) 60 °C 250 A(690 V) 70 °C 200 A
- Rated Operational Current AC-3 (Ie)
- (415 V) 55 °C 190 A(440 V) 55 °C 190 A(500 V) 55 °C 156 A(690 V) 55 °C 135 A(1000 V) 55 °C 85 A(380 / 400 V) 55 °C 190 A(220 / 230 / 240 V) 55 °C 190
- Rated Operational Current AC-3e (Ie)
- (415 V) 60 °C 190 A(440 V) 60 °C 190 A(500 V) 60 °C 135 A(690 V) 60 °C 135 A(1000 V) 60 °C 85 A(380 / 400 V) 60 °C 190 A(220 / 230 / 240 V) 60 °C 190 A
- Rated Operational Power AC-3 (Pe)
- (415 V) 90 kW(440 V) 110 kW(500 V) 110 kW(690 V) 132 kW(1000 V) 110 kW(380 / 400 V) 90 kW(220 / 230 / 240 V) 55 kW
- Rated Operational Power AC-3e (Pe)
- (415 V) 90 kW(440 V) 110 kW(500 V) 110 kW(690 V) 132 kW(1000 V) 110 kW(380 / 400 V) 90 kW(220 / 230 / 240 V) 55 kW
- Rated Breaking Capacity AC-3
- 8 x Ie AC-3
- Rated Breaking Capacity AC-3e
- 8.5 x Ie AC-3e
- Rated Making Capacity AC-3
- 10 x Ie AC-3
- Rated Making Capacity AC-3e
- 12 x Ie AC-3e
- Short-Circuit Protective Devices
- gG Type Fuses 355 A
- Rated Short-time Withstand Current Low Voltage (Icw)
- at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 1520 Aat 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 275 Aat 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 621 Aat 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 1900 Aat 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 878 A
- Maximum Breaking Capacity
- cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 3300 Acos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 2200 A
- Maximum Electrical Switching Frequency
- (AC-1) 300 cycles per hour(AC-2 / AC-4) 150 cycles per hour(AC-3) 300 cycles per hour
- Rated Operational Current DC-1 (Ie)
- (110 V) 2 Poles in Series, 40 °C 250 A(220 V) 3 Poles in Series, 40 °C 250 A
- Rated Operational Current DC-3 (Ie)
- (110 V) 2 Poles in Series, 40 °C 250 A(220 V) 3 Poles in Series, 40 °C 250 A
- Rated Operational Current DC-5 (Ie)
- (110 V) 2 Poles in Series, 40 °C 250 A(220 V) 3 Poles in Series, 40 °C 250 A
- Rated Insulation Voltage (Ui)
- acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 1000 Vacc. to UL/CSA 600 V
- Rated Impulse Withstand Voltage (Uimp)
- Main Circuit 8 kV
- Mechanical Durability
- 5 million
- Maximum Mechanical Switching Frequency
- 300 cycles per hour
- Coil Operating Limits
- (acc. to IEC 60947-4-1) 0.85 x Uc Min. ... 1.1 x Uc Max. (at θ ≤ 70 °C)
- Rated Control Circuit Voltage (Uc)
- 50 Hz 250 ... 500 V60 Hz 250 ... 500 VDC Operation 250 ... 500 V
- Coil Consumption
- Holding at Max. Rated Control Circuit Voltage 50 Hz 16.1 V·AHolding at Max. Rated Control Circuit Voltage 60 Hz 16.1 V·AHolding at Max. Rated Control Circuit Voltage DC 3.9 WPull-in at Max. Rated Control Circuit Voltage 50 Hz 260 V·APull-in at Max. Rated Control Circuit Voltage 60 Hz 260 V·APull-in at Max. Rated Control Circuit Voltage DC 230 W
- Operate Time
- Between Coil De-energization and NO Contact Opening 37 ... 47 msBetween Coil Energization and NO Contact Closing 25 ... 55 ms
- Connecting Capacity Main Circuit
- Flexible 2 x 50 ... 95 mm²Rigid Al-Cable 1 x 95 ... 185 mm²Rigid Cu-Cable 1 x 6 ... 150 mm²
- Connecting Capacity Auxiliary Circuit
- Flexible with Ferrule 2x 0.75 ... 2.5 mm²Flexible with Insulated Ferrule 2x 0.75 ... 2.5 mm²Flexible 2x0.75 ... 2.5 mm²Solid 2 x 1 ... 4 mm²Stranded 2 x 1 .... 4 mm²
- Degree of Protection
- acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP00
- Terminal Type
- Main Circuit: Bars
Eco Transparency
- Environmental Product Declaration - EPD
- 1SFC100095D0201
Classifications
- Object Classification Code
- Q
- ETIM 4
- EC000066 - Magnet contactor, AC-switching
- ETIM 5
- EC000066 - Magnet contactor, AC-switching
- EClass
- V11.0 : 27371003
- IDEA Granular Category Code (IGCC)
- 4758 >> Iec Contactors
- E-Number (Finland)
- 3706397
- E-Number (Norway)
- 4117640
- E-Number (Sweden)
- 3210135
Environmental
- Ambient Air Temperature
- Close to Contactor Fitted with Thermal O/L Relay (0.85 ... 1.1 Uc) -25 ... 50 °CClose to Contactor without Thermal O/L Relay (0.85 ... 1.1 Uc) -40 ... 70 °CClose to Contactor for Storage -40 ... 70 °C
- Maximum Operating Altitude Permissible
- Without Derating 3000 m
- RoHS Status
- Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Circular Value
- ABB EcoSolutions
- Yes
- Circular Design Principles Recyclability Rate
- Design for Closing Resource Loops - Standard EN45555 - 79.2 %
- End of Life Instructions
- 1SFC100112M0001
- Group Waste to Landfill Target
- Non-hazardous waste is sent to a landfill, where there is no alternative option available within 100km of a facility
- Improved Resource Efficiency for Customers
- Product Efficiency - Product requires less energy to operate compared to similar product on market or older products from the same line
- Sustainable Material Content
- Recycled Metal - 35 %
Technical UL/CSA
- Maximum Operating Voltage UL/CSA
- Main Circuit 1000 V
- General Use Rating UL/CSA
- (600 V AC) 250 A
- Horsepower Rating UL/CSA
- (200 V AC) Three Phase 50 hp(208 V AC) Three Phase 50 hp(220 ... 240 V AC) Three Phase 60 hp(440 ... 480 V AC) Three Phase 125 hp(550 ... 600 V AC) Three Phase 150 hp
Ordering
- Minimum Order Quantity
- 1 piece
- Customs Tariff Number
- 85364900