Thermomagnetic device circuit breaker 0914594
0914594
  • Termin płatności do 90 dni od 500+ dostawców.
  • Rabaty na odsprzedaż do 40%!
Zarejestruj się
Wyślij zapytanie o cenę
1
Metody płatności:
Poproś o wycenę, a prześlemy Ci informacje o dostępności i cenie.
Oferta z czasem realizacji przez producenta
Wysyłka:1 - 2 Dni robocze
Najlepsza cena:
Wyślij zapytanie o cenę

Additional Information

Part Number
0914594
UPC
4017918009274
Country of Origin
DE

Electrical data

Fuse type
Automatic device
Rated surge voltage
2.5 kV
Rated voltage
250 V AC
Rated voltage
65 V DC
Rated current I<sub>N</sub>
0.6 A
Insulation resistance R<sub>iso</sub>
> 100 MΩ (500 V DC)
Rated short-circuit switching capacity I<sub>cn</sub>
400 A
Rated short-circuit switching capacity I<sub>cn</sub>
2500 A (32 V DC)
Short-circuit switching capacity I<sub>k</sub>
5000 A (UL 1077: 277 V AC)
Short-circuit switching capacity I<sub>k</sub>
2000 A (UL 1077: 65 V DC)
Dielectric strength
3000 V AC (Actuation area)
Dielectric strength
3000 V AC (Main to auxiliary circuit)
Switching cycles, max.
10000 (At 1 x In, inductive)
Degree of pollution
2
Overvoltage category_GRP
II
Insulating material group
II

Dimensions

Height
82.5 mm
Width
12.5 mm
Depth
96 mm

Connection data

Conductor cross section solid min.
0.2 mm²
Conductor cross section solid max.
6 mm²
Conductor cross section flexible min.
0.2 mm²
Conductor cross section flexible max.
4 mm²
Conductor cross section AWG min.
24
Conductor cross section AWG max.
10
Conductor cross section flexible, with ferrule without plastic sleeve min.
0.25 mm²
Conductor cross section flexible, with ferrule without plastic sleeve max.
4 mm²
Conductor cross section flexible, with ferrule with plastic sleeve min.
0.25 mm²
Conductor cross section flexible, with ferrule with plastic sleeve max.
2.5 mm²
2 conductors with same cross section, solid min.
0.2 mm²
2 conductors with same cross section, solid max.
0.75 mm²
2 conductors with same cross section, stranded min.
0.2 mm²
2 conductors with same cross section, stranded max.
0.75 mm²
2 conductors with same cross section, stranded, ferrules without plastic sleeve, min.
0.25 mm²
2 conductors with same cross section, stranded, ferrules without plastic sleeve, max.
1 mm²
2 conductors with same cross section, stranded, TWIN ferrules with plastic sleeve, min.
0.5 mm²
2 conductors with same cross section, stranded, TWIN ferrules with plastic sleeve, max.
2.5 mm²
Connection method
Screw connection
Stripping length
12 mm
Internal cylindrical gage
A3
Screw thread
M3
Tightening torque, min
0.6 Nm
Tightening torque max
0.8 Nm

Ambient conditions

Degree of protection
IP30 (Actuation area)
Degree of protection
IP20 (Connection area)
Ambient temperature (operation)
-30 °C - 60 °C

Environmental Product Compliance

REACh SVHC
Lead 7439-92-1

Standards and Regulations

Standards/specifications
EN 60934
Standards/specifications
UL 1077