Electrical data

Fuse type
Automatic device
Rated surge voltage
2.8 kV
Rated voltage
240 V AC (50/60 Hz)
Rated voltage
28 V DC
Operating voltage
50 V AC - 264 V AC (48 - 62 Hz)
Operating voltage
5 V DC - 30.8 V DC
Rated current IN
6 A
Rated insulation voltage Ui
440 V AC
Insulation resistance Riso
> 100 MΩ (main contact)
Required backup fuse
20 A
Rated short-circuit switching capacity Icn
200 A (240 V AC)
Rated short-circuit switching capacity Icn
400 A (28 V DC)
Dielectric strength
2000 V
Switching cycles, max.
6000 (at 1 x In)
Switching cycles, max.
50 (at 1.5 x In)
Switching cycles, max.
40 (at 6 x In)
Degree of pollution
2
Overvoltage category
II

Dimensions

Height
85.5 mm
Width
12.3 mm
Depth
89.5 mm

Connection data

Conductor cross section solid min.
0.2 mm²
Conductor cross section solid max.
10 mm²
Conductor cross section flexible min.
0.2 mm²
Conductor cross section flexible max.
10 mm²
Conductor cross section AWG min.
24
Conductor cross section AWG max.
8
Conductor cross section flexible, with ferrule without plastic sleeve min.
0.25 mm²
Conductor cross section flexible, with ferrule without plastic sleeve max.
6 mm²
Conductor cross section flexible, with ferrule with plastic sleeve min.
0.25 mm²
Conductor cross section flexible, with ferrule with plastic sleeve max.
6 mm²
2 conductors with same cross section, solid min.
0.2 mm²
2 conductors with same cross section, solid max.
2.5 mm²
2 conductors with same cross section, stranded min.
0.2 mm²
2 conductors with same cross section, stranded max.
2.5 mm²
Two conductors with the same cross section stranded, with ferrule and without plastic sleeve, minimum
0.25 mm²
Two conductors with the same cross section stranded, with ferrule and without plastic sleeve, maximum
1.5 mm²
Two conductors with the same cross section, flexible, with TWIN ferrules, with plastic sleeve, minimum
0.5 mm²
Two conductors with the same cross section, flexible, with TWIN ferrules, with plastic sleeve, maximum
4 mm²
Connection method
Screw connection
Stripping length
12 mm
Screw thread
M4
Tightening torque, min
1.5 Nm
Tightening torque max
1.8 Nm

Ambient conditions

Ambient temperature (operation)
-30 °C - 60 °C
Altitude
2000 m (acc. to EN 60934)
Degree of protection
IP40 (Actuation area)
Degree of protection
IP20 (Connection area)

Environmental Product Compliance

China RoHS
Environmentally Friendly Use Period = 50 years
China RoHS
For details about hazardous substances go to tab 'Downloads', Category 'Manufacturer's declaration'

Standards and Regulations

Standards/specifications
EN 60934
Standards/specifications
UL 1077
Standards/specifications
CSA 22.2 No. 235
Standards/specifications
EAC