Distributed I/O device - FLS IB M12 DO 8 M12-2A - 2736039
2736039
  • Termin płatności do 90 dni od 500+ dostawców.
  • Rabaty na odsprzedaż do 40%!
Zarejestruj się
$1,055.99
1
Metody płatności:
Łącznie 4 części w magazynie od 4 dostawców
Oferta z czasem realizacji przez producenta
Wysyłka:1 - 2 Dni robocze
Najlepsza cena:
Wyślij zapytanie o cenę

Additional Information

Part Number
2736039
UPC
4017918899653
Country of Origin
DE
ETIM
Group Code : EG000024
Group Description : PLC's
Class Description : Fieldbus, decentr. periphery - digital I/O module
Class Code : EC001599
Version : 7

Note

Utilization restriction
EMC: class A product, see manufacturer's declaration in the download area

Dimensions

Width
60 mm
Height
178 mm
Depth
49.3 mm
Drill hole spacing
168 mm

Fieldline potentials

Voltage supply UL
24 V DC
Power supply at UL
4 A
Current consumption from UL
typ. 80 mA
Current consumption from UL
max. 100 mA
Voltage supply US
24 V DC
Power supply at US
max. 4 A
Current consumption from US
typ. 3.5 mA
Current consumption from US
max. 700 mA
Voltage supply UA11
24 V DC
Power supply at UA11
max. 4 A
Current consumption at UA11
typ. 12 mA (plus actuator current)
Current consumption at UA11
max. 4 A
Voltage supply UA12
24 V DC
Power supply at UA12
max. 4 A
Current consumption at UA12
typ. 12 mA (plus actuator current)
Current consumption at UA12
max. 4 A
Voltage supply UA21
24 V DC
Power supply at UA21
max. 4 A
Current consumption at UA21
typ. 12 mA (plus actuator current)
Current consumption at UA21
max. 4 A
Voltage supply UA22
24 V DC
Power supply at UA22
max. 4 A
Current consumption at UA22
typ. 12 mA (plus actuator current)
Current consumption at UA22
max. 4 A

Ambient conditions

Ambient temperature (operation)
-25 °C - 60 °C
Ambient temperature (storage/transport)
-25 °C - 85 °C
Permissible humidity (storage/transport)
95 %
Air pressure (operation)
80 kPa - 106 kPa (up to 2000 m above sea level)
Air pressure (storage/transport)
70 kPa - 106 kPa (up to 3000 m above sea level)
Degree of protection
IP65/IP67

Environmental Product Compliance

REACh SVHC
Lead 7439-92-1
China RoHS
Environmentally Friendly Use Period = 50 years
China RoHS
For details about hazardous substances go to tab 'Downloads', Category 'Manufacturer's declaration'

Electrical isolation

Test section
24 V supply (bus logics) / FE 500 V AC 50 Hz 1 s
Test section
24 V supply (bus logics) / 24 V supply (US) 500 V AC 50 Hz 1 s
Test section
24 V supply (bus logics) / Digital outputs (actuator supply) 500 V AC 50 Hz 1 s
Test section
24 V supply (bus logics) / Incoming remote bus 500 V AC 50 Hz 1 s
Test section
24 V supply (bus logics) / Outgoing remote bus 500 V AC 50 Hz 1 s
Test section
24 V supply (US) / FE 500 V AC 50 Hz 1 s
Test section
Digital outputs (actuator supply) / FE 500 V AC 50 Hz 1 s
Test section
Digital outputs (actuator supply) / 24 V supply (US) 500 V AC 50 Hz 1 s
Test section
Digital outputs (actuator supply) / Incoming remote bus 500 V AC 50 Hz 1 s
Test section
Incoming remote bus / FE 500 V AC 50 Hz 1 s
Test section
Incoming remote bus / Outgoing remote bus 500 V AC 50 Hz 1 s
Test section
Outgoing remote bus / FE 500 V AC 50 Hz 1 s
Test section
Outgoing remote bus / 24 V supply (US) 500 V AC 50 Hz 1 s
Test section
Outgoing remote bus / Digital outputs (actuator supply) 500 V AC 50 Hz 1 s

Digital outputs

Output name
Digital outputs
Connection method
M12 connector
Connection technology
2, 3-wire
Number of outputs
8
Protective circuit
Short-circuit protection
Output voltage
24 V DC
Maximum output current per channel
2 A

Interfaces

Designation
INTERBUS
Designation
Remote bus
Connection method
2 M12 connectors, B-coded
Designation connection point
Copper cable
Transmission speed
500 kbps
Number of positions
5

Standards and Regulations

Mechanical tests
Shock in acc. with EN 60068-2-27/IEC 60068-2-27 Load 30g, half sine wave, positive and negative per direction
Mechanical tests
Vibration resistance in acc. with EN 60068-2-6/IEC 60068-2-6 5g in each space direction
Connection in acc. with standard
CUL
Protection class
III (IEC 61140, EN 61140, VDE 0140-1)

Power supply for module electronics

Connection method
M12 connector, (A-coded)
Designation
UL
Supply voltage
24 V DC
Supply voltage range
18 V DC - 30 V DC (including ripple)