Additional Information

Part Number
2906492
UPC
4055626082059

UL specifications

SPD Type
4CA
Maximum continuous operating voltage MCOV
34 V AC
Maximum continuous operating voltage MCOV
34 V DC
Nominal voltage
24 V DC
Mode of protection
L-N
Mode of protection
L-G
Mode of protection
N-G
Mode of protection
(L+) - (L-)
Mode of protection
(L+) - G
Mode of protection
(L-) - G
Power distribution system
Single phase
Nominal frequency
50/60 Hz
Measured limiting voltage MLV (L-N)
330 V
Measured limiting voltage MLV (L-G)
600 V
Measured limiting voltage MLV (N-G)
600 V
Measured limiting voltage MLV (L+) - (L-)
330 V
Measured limiting voltage MLV (L+) - G
600 V
Measured limiting voltage MLV (L-) - G
600 V
Nominal discharge current I<sub>n</sub>
1 kA

Additional descriptions

Note
PLT-T3-24-P must not be used in DC applications with grounded positive pole.

Dimensions

Height
44.8 mm
Width
17.5 mm
Depth
51.7 mm
Horizontal pitch
1 Div.

Connection data

Connection method
pluggable

Ambient conditions

Degree of protection
IP20
Ambient temperature (operation)
-40 °C - 80 °C
Ambient temperature (storage/transport)
-40 °C - 80 °C
Altitude
≤ 2000 m (amsl (above mean sea level))
Permissible humidity (operation)
5 % - 95 %

Environmental Product Compliance

REACh SVHC
Lead 7439-92-1

Protective circuit

Nominal voltage U<sub>N</sub>
24 V AC (TN-S)
Nominal frequency f<sub>N</sub>
50 Hz (60 Hz)
Maximum continuous voltage U<sub>C</sub>
34 V AC
Maximum continuous voltage U<sub>C</sub>
44 V DC
Rated load current I<sub>L</sub>
16 A AC (at 63 °C)
Rated load current I<sub>L</sub>
10 A DC
Residual current I<sub>PE</sub>
≤ 5 µA
Nominal discharge current I<sub>n</sub> (8/20) µs
1 kA
Standby power consumption P<sub>C</sub>
≤ 60 mVA
Reference test voltage U<sub>REF</sub>
27 V AC
Combination wave U<sub>OC</sub>
2 kV
Voltage protection level U<sub>p</sub> (L-N)
≤ 0.18 kV
Voltage protection level U<sub>p</sub> (L-PE)
≤ 0.55 kV
Voltage protection level U<sub>p</sub> (N-PE)
≤ 0.55 kV
TOV behavior at U<sub>T</sub> (L-N)
36 V AC (5 s / withstand mode)
TOV behavior at U<sub>T</sub> (L-PE)
42 V AC (5 s / withstand mode)
Response time t<sub>A</sub> (L-N)
≤ 25 ns
Response time t<sub>A</sub> (L-PE)
≤ 100 ns
Response time t<sub>A</sub> (N-PE)
≤ 100 ns
Short-circuit current rating I<sub>SCCR</sub>
1.5 kA AC
Short-circuit current rating I<sub>SCCR</sub>
1 kA DC
Max. backup fuse with branch wiring
16 A AC (B)
Max. backup fuse with branch wiring
10 A DC (gG / B)
Maximum backup fuse for through wiring
16 A AC (B)
Maximum backup fuse for through wiring
10 A DC (gG / B)

Standards and Regulations

Standards/specifications
EN 61643-11 2012