Phoenix Contact
2972880
Multiple relay module - UMK- 4 RM230AC - 2972880
- Termin płatności do 90 dni od 500+ dostawców.
- Rabaty na odsprzedaż do 40%!
Wyślij zapytanie o cenę
1
Metody płatności:
Stan produktu:
Oferta z czasem realizacji przez producenta
Wysyłka:Na zapytanie
Najlepsza cena:
Wyślij zapytanie o cenę
Additional Information
- Part Number
- 2972880
- UPC
- 4017918088828
- Country of Origin
- DE
- ETIM
- Group Code : EG000019
- Group Description : Relays
- Class Description : Relay socket
- Class Code : EC001456
- Version : 7
Input data
- Nominal input voltage UN
- 230 V AC ±10 %
- Input voltage range in reference to UN
- 0.4 - 1.1
- Typical input current at UN
- 0.5 mA (Light indicator)
- Status display/channel
- Glow lamp
Note
- Utilization restriction
- EMC: class A product, see manufacturer's declaration in the download area
Dimensions
- Width
- 67.5 mm
- Height
- 77 mm
- Depth
- 59 mm
Connection data 2
- Connection name
- Output
- Connection method
- Screw connection
- Stripping length
- 8 mm
- Screw thread
- M3
- Number of connections
- 12
- Number of positions
- 3
- Conductor cross section solid
- 0.2 mm² - 4 mm²
- Conductor cross section flexible
- 0.2 mm² - 2.5 mm²
- Conductor cross section AWG
- 24 - 12
Connection data
- Connection name
- Input
- Connection method
- Screw connection
- Stripping length
- 8 mm
- Screw thread
- M3
- Number of connections
- 2
- Number of positions
- 8
- Conductor cross section solid
- 0.2 mm² - 4 mm²
- Conductor cross section flexible
- 0.2 mm² - 2.5 mm²
- Conductor cross section AWG
- 24 - 12
Output data
- Contact type
- 1 PDT
- Maximum switching voltage
- 250 V AC/DC
- Limiting continuous current
- 5 A
- Maximum inrush current
- 8 A
- Error detection (line break / short-circuit)
- no
Ambient conditions
- Ambient temperature (operation)
- -20 °C - 50 °C
- Ambient temperature (storage/transport)
- -20 °C - 70 °C
- Degree of protection
- IP20
Environmental Product Compliance
- REACh SVHC
- Lead 7439-92-1
- China RoHS
- Environmentally Friendly Use Period = 50 years
- China RoHS
- For details about hazardous substances go to tab 'Downloads', Category 'Manufacturer's declaration'
Standards and Regulations
- Standards/regulations
- DIN EN 50178
- Standards/regulations
- IEC 60664
- Rated insulation voltage
- 260 V AC
- Rated surge voltage
- 4 kV (Basic insulation between output contact current paths)
- Rated surge voltage
- 6 kV (Safe isolation and reinforced insulation between input circuit and output contact paths)
- Pollution degree
- 2
- Overvoltage category
- III