- Fault Type
- open circuit 4...20 mA
- Maximum Voltage Drop
- <30 V 25 mA
- Setting Time
- 3.2 ms to +/-0.1% of the final value || 1.6 ms to 5% of the final value
- Loop Voltage
- 6-30 V DC
- Linearity
- +/- 12 µA 4...20 mA 0...4095 counts || +/- 4 µA 0...20 mA 0...20000 counts || +/- 4 µA 0...25 mA 0...25000 counts || +/- 4 µA 4...20 mA 0...16000 counts
- Marking
- CE
- Accuracy Drift According To Temperature
- 0.004 % of full scale/°C typical || 0.007 % of full scale/°C maximum
- Net Weight
- 0.3 kg
- Analogue Output Range
- 0...20 mA 0...20000 counts || 0...25 mA 0...25000 counts || 4...20 mA 0...16000 counts || 4...20 mA 0...4095 counts
- External Power Requirement
- 6...30 V
- Maximum Power Dissipation In W
- 5 W
- Analogue Output Number
- 8
- Absolute Accuracy Error
- +/- 0.2 % of full scale 25 °C
- Bus Current Requirement
- 550 mA
- Addressing Requirement
- 8 output words
- Local Signalling
- for bus communication is present (Active) 1 LED (green) || for external fault 1 LED (red) || for channel is turned on 8 LEDs (green) || for channel fault 8 LEDs (red)
- Module Format
- standard
- Update Time
- 5 ms
- Isolation Between Channels And Bus
- 1780 V for 1 minute AC