Rectangular sensor L1 type, VigiPacT, 280mmx115mm, 1600A
56053
  • Termin płatności do 90 dni od 500+ dostawców.
  • Rabaty na odsprzedaż do 40%!
Zarejestruj się
€1,569.95
1
Metody płatności:
Łącznie 117 części w magazynie od 14 dostawców
Oferta z czasem realizacji przez producenta
Wysyłka:1 - 2 Dni robocze
Najlepsza cena:
€757.42

Additional Information

Part Number
56053
UNSPSC
39121601
Tariff Code
9030333800
Country of Origin
FR

Environment

Product Certifications
CE
Ambient Air Temperature For Operation
-35-80 °C
Standards
IEC 60947-2
Environmental Characteristic
exposure to damp heat not in service 25...55 °C, RH 95 %) 28 cycles IEC 60068-2-30 || salt mistKb/2 IEC 60068-2-52 || exposure to damp heat in servicecategory C2 48 hours IEC 60068-2-56
Ambient Air Temperature For Storage
-55-100 °C
Ip Degree Of Protection
connectors IP20 || IP30

Contractual warranty

Warranty
18 months

Offer Sustainability

Rohs Exemption Information
Yes
Mercury Free
Yes
Toxic Heavy Metal Free
Yes
Reach Regulation
Free of Substances of Very High Concern above the threshold
California Proposition 65
WARNING: Cancer and Reproductive Harm - www.P65Warnings.ca.gov
Reach Free Of Svhc
Yes
Weee
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
China Rohs Regulation
Pro-active China RoHS declaration (out of China RoHS legal scope)
Eu Rohs Directive
Compliant

Complementary

Mounting Mode
fixed cables) || fixed busbar)
Height
233 mm
Residual Short-Circuit Withstand Current
85 kA / 0.5 s
[Uimp] Rated Impulse Withstand Voltage
12 kV
Connections - Terminals
screw connection 0.2-2.5 mm²
Depth
outside 71 mm || inside 71 mm
Net Weight
13.26 kg
Height
outside 233 mm || inside 115 mm
Width
outside 381 mm || inside 280 mm
Width
381 mm
Overvoltage Category
IV
Depth
71 mm
[Icw] Rated Short-Time Withstand Current
100 kA 0.5 s
Transformer Ratio
1/1000

Specifications

Range Compatibility
VigiPacT RH10M residual current protection relay || VigiPacT RH10P residual current protection relay || VigiPacT RH21M residual current protection relay || VigiPacT RH21P residual current protection relay || VigiPacT RH68M residual current protection relay || VigiPacT RH86M residual current protection relay || VigiPacT RH86P residual current protection relay || VigiPacT RH99M residual current protection relay || VigiPacT RH99P residual current protection relay || VigiPacT RH197M residual current protection relay || VigiPacT RH197P residual current protection relay || VigiPacT RHU residual current protection relay || VigiPacT RHUs residual current protection relay || VigiPacT RMH residual current protection relay
Product Or Component Type
earth leakage current sensor
Range
VigiPacT
[Ie] Rated Operational Current
1600 A
Current Transformer Type
rectangular sensor
Device Application
equipment monitoring and control
Device Short Name
L

Dokumenty

Data Sheet

Pobierz

Powiązane produkty