Schneider Electric

6440AXXTZS-DC3

Relay, SE Relays, solid state, SPST NO, 40A, 48…530 VAC, 3...32 VDC Uc, triac AC zero cross, screw terminal
6440AXXTZS-DC3
6440AXXTZS-DC3
6440AXXTZS-DC3
6440AXXTZS-DC3
6440AXXTZS-DC3
  • Termin płatności do 90 dni od 500+ dostawców.
  • Rabaty na odsprzedaż do 40%!
Zarejestruj się
Wyślij zapytanie o cenę
1
Metody płatności:
Poproś o wycenę, a prześlemy Ci informacje o dostępności i cenie.

Additional Information

Part Number
6440AXXTZS-DC3
UNSPSC
39122333
Country of Origin
IN

Specifications

[Uc] Control Circuit Voltage
3...32 V DC
Range Of Product
Legacy
Mounting Support
panel
Maximum Output Current
40 A AC
Output Voltage
48...530 V AC
Product Or Component Type
solid state relay
Phase
1 phase

Complementary

Screw Type
M3.5 || M6
Contacts Type And Composition
NO
Minimum Insulating Resistance
1 GΩ
Height
35.3 mm
Tightening Torque
10 lb.in for input || 20 lb.in for output
Holding Current
250 mA
Dv/Dt
250 V/µs off-state at maximum rated voltage
Local Signalling
for input status 1 LED (green)
Solid State Output Type
triac output || zero voltage switching
Maximum I²T For Fusing
250 A².s
Thermal Resitance
0.9 °C/W
Maximum Voltage Drop
<1.6 V on-state AC
Switch Function
SPST
Surge Current
300 A
Width
47.1 mm
Input Current Limits
16-16 mA DC typical
Response Time
0.5 cycle (turn-on, turn-off)
Depth
58.4 mm
Connections - Terminals
input screw clamp terminal, 1 || output screw clamp terminals, 1
Net Weight
86.5 g
Maximum Leakage Current
10 mA at off-state
Dielectric Strength
4000 V between input and ground || 4000 V between output and ground || 4000 V between input and output
Drop-Out Voltage
1 V
Power Factor
0.5 with maximum load

Offer Sustainability

China Rohs Regulation
X
Rohs Exemption Information
Yes
Mercury Free
Yes
Eu Rohs Directive
Pro-active compliance (Product out of EU RoHS legal scope)
Reach Regulation
Reference contains Substances of Very High Concern above the threshold
California Proposition 65
WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
Weee
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.

Environment

Product Certifications
UL || CSA || CE
Ambient Air Temperature For Operation
-40-80 °C
Ambient Air Temperature For Storage
-40-125 °C
Ip Degree Of Protection
IP20

Dokumenty