Specifications

Pressure Sensor Type
electromechanical pressure switch
Pressure Sensor Size
75 psi
Controlled Fluid
hydraulic oil -40-250 °F) || non-corrosive liquids || air || non-corrosive gas
Range Of Product
9012G
Scale Type
adjustable differential
Maximum Pressure
100 psi
Pressure Switch Type Of Operation
monitors the difference between 2 thresholds
Contacts Type And Composition
2(NC-NO), DPDT-DB, Form ZZ, snap action, silver nickel contacts
Local Display
without
Pressure Sensor Name
9012G
Fluid Connection Type
0.25 inch 18 NPTF UL 508

Contractual warranty

Warranty
18 months

Complementary

Repeat Accuracy
4 %
Height
8.02 in
Pressure Actuator
diaphragm nitrile (Buna-N)
Maximum Operating Rate
120 cyc/mn
Terminal Block Type
8 screw terminals
Short-Circuit Protection
10 A cartridge overload and short-circuit protection gL
Setting
internal
Mechanical Durability
5000000 cycles
Line Rated Current
3 A 240 V AC A600 NEMA rating designation || 6 A 120 V AC A600 NEMA rating designation || 0.27 A 250 V DC R300 NEMA rating designation || 0.22 A 125 V DC R300 NEMA rating designation
Range On Decreasing Pressure
0-75 psi
Cable Entry
0.5 inch NPT conduit entrance
Operating Position
any position
Electrical Circuit Type
control circuit
Electrical Connection
screw-clamp terminals, AWG 22...AWG 12
Enclosure Material
die cast aluminium alloy 380
Approx Adjustable Differential At Mid Range
0.8-2 psi increasing || 0.25-10 psi decreasing +/- 2.5 % full scale
Width
5.05 in
Depth
4.56 in
Materials In Contact With Fluid
zinc plated steel || nitrile (Buna-N)
Net Weight
3 lb(US)
Local Signalling
without

Offer Sustainability

Circularity Profile
ENVEOLI111210EN
Environmental Disclosure
ENVPEP111211EN
Eu Rohs Directive
Not applicable, out of EU RoHS legal scope
Reach Regulation
Reference contains Substances of Very High Concern above the threshold
California Proposition 65
WARNING: This product can expose you to chemicals including: Diisononyl phthalate (DINP), which is known to the State of California to cause cancer, and Di-isodecyl phthalate (DIDP), which is known to the State of California to cause birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov

Environment

Product Certifications
CE || CSA LR25490 class 3211 03
Ambient Air Temperature For Operation
-10-185 °F
Standards
UL 508 || CSA C22.2 No 14
Nema Degree Of Protection
NEMA 4/4X/13 UL 50
Shock Resistance
50 gn IEC 58-2-27
Vibration Resistance
2 gn 40-150 Hz)IEC 68-2-6

Dokumenty

Data Sheet

Pobierz