Schneider Electric
BDA24050Y2
1 / 5
Opis
Końcówka Serii
PowerPacT B-Frame brings thermal-mechanical circuit protection in a compact size and offers a wide range of accessories, auxiliaries, and connection options. This PowerPacT B-Frame circuit breaker provides thermal magnetic circuit protection with a breaking capacity of 18kA at 480Y/277VAC. All PowerPacT B-Frame circuit breakers are equipped with dual-break rotating contacts that reduce the amount of peak current during a short circuit fault. All PowerPacT circuit breakers have an integral push-to-trip button in the cover to manually trip the circuit breaker. PowerPacT B-Frame circuit breakers come in 1 to 4-pole unit mount construction and in 1 to 3-pole I-Line construction. I-Line circuit breakers come with a shrouded I-Line plug on jaw. This unit has I-Line terminations on the line side and mechanical lugs on the load side. This PowerPacT B, 50A, 2 pole, circuit breaker has a breaking capacity of 18kA at 480Y/277VAC. This circuit breaker has a continuous current rating of 80% with an AC phase connection. PowerPacT B circuit breakers comply to UL, CSA, NOM, and IEC standards and are CE marked.- Part Number
- BDA24050Y2
- Tariff Code
- 8536200020
- UNSPSC
- 39121601
- Termin płatności do 90 dni od 500+ dostawców.
- Rabaty na odsprzedaż do 40%!
Wyślij zapytanie o cenę
1
Metody płatności:
Specifications
- Product Or Component Type
- circuit breaker
- Product Name
- PowerPact B
- Range
- PowerPact
- Device Application
- distribution
- Device Short Name
- BD 050
Complementary
- Mounting Mode
- I-Line
- Network Frequency
- 50/60 Hz
- [Ics] Rated Service Breaking Capacity
- 25 kA 220...240 V AC 50/60 Hz IEC 60947-2 || 14 kA 500...525 V AC 50/60 Hz IEC 60947-2 || 18 kA 380...415 V AC 50/60 Hz IEC 60947-2 || 18 kA 440 V AC 50/60 Hz IEC 60947-2
- Trip Unit Technology
- thermal-magnetic
- Height
- 137 mm
- Connection Pitch
- 27 mm
- [Ue] Rated Operational Voltage
- 525 V AC 50/60 Hz UL 489
- Tightening Torque
- 3.6-4.4 N.m 2.5-6 mm² (AWG 14...AWG 10) || 5-6.2 N.m 10-70 mm² (AWG 8...AWG 2/0)
- Breaking Capacity Code
- D
- 9 Mm Pitches
- 6
- Local Signalling
- presence of auxiliary contacts flag green)
- Number Of Slots
- 1 auxiliary switch OF plug-in) || 1 voltage release MN or MX plug-in)
- Electrical Connection
- I-Line connection, line || lugs, load
- Mounting Height
- 76.2 mm
- Net Weight
- 0.952 kg
- [Uimp] Rated Impulse Withstand Voltage
- 8 kV IEC 60947-2
- Control Type
- toggle
- Circuit Breaker Application
- HACR rated
- Wire Stripping Length
- 20 mm
- Utilisation Category
- category A
- Line Rated Current
- 50-50 A
- Continuous Current Rating
- 80 %
- Breaking Capacity
- 25 kA 208Y/120 V AC 50/60 Hz UL 489 || 25 kA 240 V AC 50/60 Hz UL 489 || 18 kA 480/277 V AC 50/60 Hz UL 489 || 18 kA 480 V AC 50/60 Hz UL 489 || 10 kA 600Y/347 V AC 50/60 Hz UL 489
- [Ui] Rated Insulation Voltage
- 800 V IEC 60947-2
- Mechanical Durability
- 20000 cycles IEC 947-1 Annex K ed 5.2
- Suitability For Isolation
- yes IEC 60947-2
- Electrical Durability
- 10000 cycles IEC 947-1 Annex K ed 5.2 440 V In
- Poles Description
- 2P
- Quantity Per Set
- set of 1
- Awg Gauge
- AWG 14...AWG 2/0 aluminium/copper
- Color
- Gray RAL 7016)
- Width
- 54 mm
- Depth
- 89 mm
- Phase Connection
- AC
Offer Sustainability
- Rohs Exemption Information
- Yes
- Mercury Free
- Yes
- Environmental Disclosure
- ENVPEP1610005EN
- Sustainable Offer Status
- Green Premium product
- Pvc Free
- Yes
- Reach Regulation
- Reference contains Substances of Very High Concern above the threshold
- California Proposition 65
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
- Weee
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- China Rohs Regulation
- Product out of China RoHS scope. Substance declaration for your information.
- Circularity Profile
- N/A
- Eu Rohs Directive
- Compliant with Exemptions
- Halogen Content Performance
- Halogen free product
Environment
- Ik Degree Of Protection
- IK07 IEC 62262
- Ambient Air Temperature For Operation
- -25-70 °C
- Standards
- EN/IEC 60947-5-1 || NMX J-266 || UL 489 || GB 14048.2 || CSA C22.2 No 5 || NEMA AB1 || EN/IEC 60947-2
- Product Certifications
- UL || IEC || CCC || EAC || CSA || NOM
- Ip Degree Of Protection
- front cover IP40 IEC 60529
- Pollution Degree
- 3 IEC 60947-1
- Ambient Air Temperature For Storage
- -50-85 °C
- Quality Labels
- CE
- Operating Altitude
- < 6561.68 ft (2000 m) without derating || 5000 m with derating
Dokumenty
Data Sheet
PobierzInne kategorie
SiłownikiBlokiKable, rury i wężeSprężarkiSterowanieŁączniki i osprzętCylindry i tłokiElektronikaFiltryHVACKomputery przemysłowe i interfejsy HMIOświetlenieTechnika liniowaSilnikiZasilaniePrzeniesienie napęduPompy i zaworyEnergia odnawialnaRobotykaUszczelki, pierścienie i złączaCzujniki i urządzenia pomiaroweNarzędzia i akcesoriaCNCInne