Opis

Końcówka Serii
EXN three phase low voltage dry type distribution transformers from Square D comply with DOE energy conservation standards and Natural Resources Canada (NRCan) minimum energy efficiency levels. This transformer is a 30kVA, 480V primary (three wire), 208Y/120V secondary (four wire) with aluminum windings with a 220 insulation system design for 150 degree C temperature rise. This transformer’s DOE 2016 and NRCan efficiency is a minimum of 98.23% at 35% loading and 75°C temperature. Terminals are designed to accommodate wire ranges sized for 125% of the secondary nameplate current and 250% of the primary nameplate current. The terminals allow for NEMA two hole lugs and wiring bending radius to align with the wire ranges and to allow for side and bottom access. Units are natural air cooled with exhaust vents located on the front only, allowing the transformers to be mounted with rear clearance to obstructions of 1/2 inch. Units are shipped as Type 2 for indoor installation, field convertible to Type 3R via weathershield for outdoor installation. The transformers are floor mounted but field accessories are available for wall or trapeze (ceiling) mounting. EX transformers have a low sound level, with a minimum of 3dB below NEMA Standard ST-20 requirements. Units are specifically designed to function with other Square D equipment; inrush is coordinated to meet identified breaker trip curves, and IZ levels allow for let through current to match AIR levels of panelboards. See product data sheets for these values.
Country of Origin
MX
Part Number
EXN30T3H
Tariff Code
8504330040
EAN
39121001
UPC
785901272540
UNSPSC
39121001
  • Termin płatności do 90 dni od 500+ dostawców.
  • Rabaty na odsprzedaż do 40%!
Zarejestruj się
Wyślij zapytanie o cenę
1
Metody płatności:
Poproś o wycenę, a prześlemy Ci informacje o dostępności i cenie.

Offer Sustainability

Rohs Exemption Information
Yes
Mercury Free
Yes
Environmental Disclosure
ENVPEP1604028EN
Sustainable Offer Status
Green Premium product
Pvc Free
Yes
Toxic Heavy Metal Free
Yes
Reach Regulation
Free of Substances of Very High Concern above the threshold
California Proposition 65
WARNING: This product can expose you to chemicals including: Phenyl Glycidyl Ether, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
Reach Free Of Svhc
Yes
China Rohs Regulation
Pro-active China RoHS declaration (out of China RoHS legal scope)
Circularity Profile
N/A
Eu Rohs Directive
Compliant
Halogen Content Performance
Halogen free plastic parts product

Complementary

Tap Loss
80 no load (core loss) || 1044 load loss (coil loss)
Network Frequency
60 Hz
Primary Voltage
480 V delta
Percentage Impedance Voltage
3.80 %
Height
719 mm
Number Of Mounting Holes
4 Ø: 13 mm
[Uimp] Rated Impulse Withstand Voltage
10 kV
Primary Operational Current
36.08-36.08 A 83.27 A 30 kVA
Temperature Rise
150 °C || 220 °C insulated
Degree Of Protection
UL type 2 || UL type 3R, with 7400WS18M19M20M
Number Of Tap-Offs
2 2.5 % FCAN || 4 2.5 % FCBN
X/R Ratio
0.49
Rated Operational Power In Va
30 kVA
Electrical Connection
2 Hole Nema Pad primary 11.1 mm || 2 Hole Nema Pad secondary 11.1 mm || 4 Hole Nema Pad sec - XO 11.1 mm
Phase
3 phase
Material
aluminium
Net Weight
137.44 kg
Secondary Voltage
208Y/120 V
Percentage Reactance
1.58 %
Noise Level
3 dB NEMA ST-20 || 42 dB
Type Of Cooling
natural convection
Efficiency
98.28 % at 35 % load factor , 75.0 °C
Mounting Support
floor || floor, with 7400FMB || ceiling, with 7400CMB18M19M20M || wall, with 7400WMB18M19M20M
Continuous Thermal Current Rating Factor
372 16.6 % || 496 25 % || 1164 50 % || 2277 75 % || 3835 100 %
Width
648 mm
Depth
627 mm
Inrush Current
668 A
Box Number
18M
[Ipk] Rated Peak Withstand Current
2.19 kA

Specifications

Range Of Product
Square D
Product Or Component Type
transformer
Transformer Type
energy efficient
Device Application
low voltage electrical distribution
Device Short Name
DOE 2016

Environment

Average Ambient Air Temperature For Operation
30 °C
Ambient Air Temperature For Operation
40-40 °C
Standards
UL 1561 || CSA C22.2 No 47 || NEMA ST-20