Schneider Electric
GB2CB12
TeSys GB2 thermal magnetic circuit protector, 1 P, 6 A, Id = 83 A
- Termin płatności do 90 dni od 500+ dostawców.
- Rabaty na odsprzedaż do 40%!
€11.67
1
Metody płatności:
Łącznie 672 części w magazynie od 27 dostawców
Stan produktu:
Oferta z czasem realizacji przez producenta
Wysyłka:Na zapytanie
Najlepsza cena:
€6.62
Additional Information
- Part Number
- GB2CB12
- UNSPSC
- 39121633
- Tariff Code
- 8536200020
- Country of Origin
- FR
Environment
- Product Certifications
- UL || CSA
- Ambient Air Temperature For Operation
- -20-60 °C
- Standards
- EN/IEC 60947-1 || EN/IEC 60947-2 || CSA C22.2 No 235 || UL 1077
- Ambient Air Temperature For Storage
- -40-80 °C
- Protective Treatment
- TC
- Ip Degree Of Protection
- IP20 IEC 60529
- Operating Altitude
- 9842.52 ft (3000 m)
- Fire Resistance
- 960 °C IEC 60695-2-1
Contractual warranty
- Warranty
- 18 months
Offer Sustainability
- Rohs Exemption Information
- Yes
- Mercury Free
- Yes
- Environmental Disclosure
- ENVPEP2306023
- Sustainable Offer Status
- Green Premium product
- Toxic Heavy Metal Free
- Yes
- Reach Regulation
- Free of Substances of Very High Concern above the threshold
- California Proposition 65
- WARNING: Cancer - www.P65Warnings.ca.gov
- Reach Free Of Svhc
- Yes
- Weee
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- China Rohs Regulation
- Pro-active China RoHS declaration (out of China RoHS legal scope)
- Circularity Profile
- N/A
- Eu Rohs Directive
- Compliant
Complementary
- Mechanical Robustness
- shocks 22 Gn for 20 ms IEC 60068-2-27 || vibrations 5 Gn, 5...110 Hz IEC 60068-2-6
- Line Rated Current
- 6 A
- [Ue] Rated Operational Voltage
- 250 V AC 50/60 Hz IEC 60947-2 || 277 V AC 60 Hz CSA C22.2 No 235 || 277 V AC 60 Hz UL 1077 || 48 V DC
- Height
- 74 mm
- Mounting Support
- rail || plate
- 9 Mm Pitches
- 2
- Connections - Terminals
- connector 1 0.75-6 mm²solid without cable end || connector 2 0.75-4 mm²solid without cable end || connector 1 0.75-4 mm²flexible with cable end || connector 2 0.75-2.5 mm²flexible with cable end
- [Uimp] Rated Impulse Withstand Voltage
- 4 kV IEC 60947-2
- Control Type
- toggle
- Power Dissipation Per Pole
- 2 W
- Electrical Durability
- 8000 cycles
- Mounting Mode
- by clips
- Tightening Torque
- 1.2 N.m connector
- Mechanical Durability
- 8000 cycles
- Quantity Per Set
- set of 6
- Mounting Position
- vertical || horizontal
- Width
- 15 mm
- Depth
- 67 mm
Specifications
- Network Type
- AC/DC
- Magnetic Tripping Current
- 83-83 A
- Product Or Component Type
- circuit breaker
- Product Name
- TeSys GB2
- Utilisation Category
- category A IEC 60947-2 || DC-12 IEC 60947-5-1 || DC-13 IEC 60947-5-1
- Range
- TeSys
- [Ics] Rated Service Short-Circuit Breaking Capacity
- 75 % 110 V AC 50/60 Hz IEC 60947-2 || 75 % 230/240 V AC 50/60 Hz IEC 60947-2
- Breaking Capacity
- 3 kA Icu 110 V AC 50/60 Hz IEC 60947-2 || 1.5 kA Icu 230/240 V AC 50/60 Hz IEC 60947-2 || 1.5 kA Icu 24 V DC IEC 60947-2 || 1 kA Icu 48 V DC IEC 60947-2
- Poles Description
- 1P
- Network Frequency
- 50/60 Hz IEC 60947-2
- Device Application
- control
- Device Short Name
- GB2
- Trip Unit Technology
- thermal-magnetic
Dokumenty
Data Sheet
PobierzModele CAD
traceparts
Pobierz