Schneider Electric
JDA261752
1 / 1
Opis
Końcówka Serii
PowerPacT J-Frame circuit breakers are designed to protect electrical systems from damage caused by overloads and short circuits. PowerPacT J-Frame circuit breakers are available with either thermal magnetic or MicroLogic electronic trip protection units. This PowerPacT J-Frame circuit breaker provides thermal magnetic circuit protection with a breaking capacity of 14kA at 600VAC. All PowerPacT J-Frame circuit breakers are equipped with dual-break rotating contacts that reduce the amount of peak current during a short circuit fault. All PowerPacT circuit breakers have an integral push-to-trip button in the cover to manually trip the circuit breaker. PowerPacT J circuit breakers are available in 2 and 3-pole unit mount and I-Line constructions. PowerPacT J I-Line circuit breakers are available in I-Line construction for easy installation and removal in I-Line applications. This unit has I-Line terminations on the line side and mechanical lugs on the load side. This PowerPacT J, 175A, 2 pole, circuit breaker has a breaking capacity of 14kA at 600VAC. This circuit breaker has a continuous current rating of 80% with an AC phase connection. PowerPacT J circuit breakers comply to UL, CSA, NOM, and IEC standards and are CE marked.- Part Number
- JDA261752
- Tariff Code
- 8536200020
- UPC
- 785901558408
- UNSPSC
- 39121601
- Termin płatności do 90 dni od 500+ dostawców.
- Rabaty na odsprzedaż do 40%!
Wyślij zapytanie o cenę
1
Metody płatności:
Environment
- Ambient Air Temperature For Operation
- -2-70 °C
- Standards
- UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
- Product Certifications
- UL || CSA || NOM
- Ip Degree Of Protection
- front cover IP40
- Pollution Degree
- 3
- Ambient Air Temperature For Storage
- -50-85 °C
- Quality Labels
- CE
- Operating Altitude
- < 6561.68 ft (2000 m) without derating || 5000 m with derating
Contractual warranty
- Warranty
- 18 months
Offer Sustainability
- Rohs Exemption Information
- Yes
- Mercury Free
- Yes
- Environmental Disclosure
- ENVPEP2206031EN
- Sustainable Offer Status
- Green Premium product
- Pvc Free
- Yes
- Reach Regulation
- Reference contains Substances of Very High Concern above the threshold
- California Proposition 65
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
- China Rohs Regulation
- Product out of China RoHS scope. Substance declaration for your information.
- Circularity Profile
- ENVEOLI2206031EN
- Eu Rohs Directive
- Compliant with Exemptions
Complementary
- Mounting Mode
- I-Line bracket)
- Network Frequency
- 50/60 Hz
- Terminal Identifier
- AL175JD
- [Ics] Rated Service Breaking Capacity
- 25 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 18 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 14 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
- Trip Unit Technology
- thermal-magnetic
- Height
- 191 mm
- [Ue] Rated Operational Voltage
- 600 V AC 50/60 Hz IEC 60947-3
- Tightening Torque
- 25-25 N.m 25-95 mm² (AWG 4...AWG 4/0)
- Mounting Support
- bracket
- Breaking Capacity Code
- D
- Magnetic Tripping Current
- 1750-1750 A
- Local Signalling
- switched off (OFF) 1 trip indicator green)
- Number Of Slots
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
- Electrical Connection
- I-Line connection, line || lugs, load
- Mounting Height
- 4.5 in
- Net Weight
- 2.4 kg
- [Uimp] Rated Impulse Withstand Voltage
- 8 kV IEC 60947-2
- Magnetic Hold Current
- 875 A
- Control Type
- toggle
- Circuit Breaker Application
- HACR rated
- Wire Stripping Length
- 25 mm
- Line Rated Current
- 175-175 A
- Utilisation Category
- category A
- Long Time Pick-Up Adjustment Range
- 0.25...1 x In
- Continuous Current Rating
- 80 %
- Breaking Capacity
- 25 kA 240 V AC 50/60 Hz UL 489 || 18 kA 480 V AC 50/60 Hz || 14 kA 600 V AC 50/60 Hz || 20 kA 250 V DC
- [Ui] Rated Insulation Voltage
- 750 V IEC 60947-2
- Suitability For Isolation
- yes IEC 60947-2
- Communication Interface
- Modbus
- Poles Description
- 2P
- Protection Type
- overload protection || short-circuit protection
- Awg Gauge
- AWG 4...AWG 4/0 aluminium/copper terminal
- Width
- 104 mm
- Depth
- 86 mm
- Phase Connection
- AC
Specifications
- Product Or Component Type
- circuit breaker
Dokumenty
Data Sheet
PobierzInne kategorie
SiłownikiBlokiKable, rury i wężeSprężarkiSterowanieŁączniki i osprzętCylindry i tłokiElektronikaFiltryHVACKomputery przemysłowe i interfejsy HMIOświetlenieTechnika liniowaSilnikiZasilaniePrzeniesienie napęduPompy i zaworyEnergia odnawialnaRobotykaUszczelki, pierścienie i złączaCzujniki i urządzenia pomiaroweNarzędzia i akcesoriaCNCInne