Schneider Electric
LC1F400E7
1 / 1
Opis
Końcówka Serii
TeSys F contactor, 3 poles (3NO), 400A/1000V AC-3, for motor applications up to 200kW@400V. It provides a low sealed consumption 48V 40-400Hz AC coil, bolt terminals for bars or cables with lugs. For high operating rates until 2400 cycles/hour and environments until 55°C, it procures high reliability and durability. It makes installation and maintenance easy thanks to its drawer-mounted coil and a large choice of add-on blocks and accessories (to be ordered separately). Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine), Green Premium compliant (RoHS/REACh).- Country of Origin
- CZ
- Part Number
- LC1F400E7
- Tariff Code
- 85364190
- EAN
- 3389110226935
- UNSPSC
- 39121529
Metody płatności:
- Najlepsza oferta od:
- Zaufany dostawca Automa.Net
- Dostępność:
- 10 szt.W magazynieZaktualizowano: 12-11-2024
- Gwarancja:
- 12 miesięcy
- Szacowany czas dostawy:
- Na zapytanie
- Stan produktu:
- Fabrycznie Nowe, Zapieczętowane
Fabrycznie Nowe, Zapieczętowane - Nowy, nieużywany, nieotwarty, nieuszkodzony przedmiot w oryginalnym opakowaniu zapieczętowanym przez producenta.
Bezpieczny proces płatności
Zasady zwrotów i reklamacji
Zasady wysyłki
Gwarancja
Specifications
- [Uc] Control Circuit Voltage
- 48 V AC 40...400 Hz
- Range Of Product
- TeSys F
- [Ue] Rated Operational Voltage
- <= 1000 V AC 50/60 Hz || <= 460 V DC
- Contactor Application
- resistive load || motor control
- Product Or Component Type
- contactor
- Range
- TeSys
- Utilisation Category
- AC-4 || AC-3 || AC-1
- [Ie] Rated Operational Current
- 500 A 40 °C) <= 440 V AC AC-1 || 400 A 55 °C) <= 440 V AC AC-3
- Poles Description
- 3P
- Device Short Name
- LC1F
Contractual warranty
- Warranty
- 18 months
Complementary
- Product Certifications
- RINA || BV || RMRoS || LROS (Lloyds register of shipping) || UL || ABS || CSA || CB || DNV || UKCA
- Power Dissipation Per Pole
- 65 W AC-1 || 42 W AC-3
- Average Impedance
- 0.26 mOhm - Ith 500 A 50 Hz
- [Ith] Conventional Free Air Thermal Current
- 500 A 40 °C
- Control Circuit Voltage Limits
- operational 0.85...1.1 Uc 40...400 Hz 55 °C) || drop-out 0.3...0.5 Uc 40...400 Hz 55 °C)
- Standards
- IEC 60947-1 || IEC 60947-4-1 || EN 60947-4-1 || EN 60947-1 || JIS C8201-4-1
- Mounting Support
- plate
- Control Circuit Type
- AC 40...400 Hz
- Contactor Coil Voltage
- 48 V AC standard
- Rated Breaking Capacity
- 3200 A IEC 60947-4-1
- Power Range
- 110-220 kW 480-500 V 3 phase || 110-220 kW 380-440 V 3 phase || 110-220 kW 200-240 V 3 phase || 250-500 kW 480-500 V 3 phase
- Associated Fuse Rating
- 400 A aM <= 440 V || 500 A gG <= 440 V
- [Uimp] Rated Impulse Withstand Voltage
- 8 kV
- Inrush Power In Va
- 1075-1075 VA, 40...400 Hz 0.9 20 °C)
- Connections - Terminals
- control circuit screw clamp terminals 1 1-4 mm²flexible without cable end || control circuit screw clamp terminals 2 1-4 mm²flexible without cable end || control circuit screw clamp terminals 1 1-4 mm²flexible with cable end || control circuit screw clamp terminals 2 1-2.5 mm²flexible with cable end || control circuit screw clamp terminals 1 1-4 mm²solid without cable end || control circuit screw clamp terminals 2 1-4 mm²solid without cable end || power circuit bar 2 30 x 5 mm || power circuit lugs-ring terminals 2 150-150 mm² || power circuit bolted connection
- Pole Contact Composition
- 3 NO
- Motor Starter Type
- direct on-line contactor
- Operating Time
- 40...65 ms closing || 100...170 ms opening
- Maximum Operating Rate
- 2400 cyc/h 55 °C
- Mechanical Durability
- 10 Mcycles
- Tightening Torque
- control circuit 1.2 N.m || power circuit 35 N.m
- Compatibility Code
- LC1F
- Hold-In Power Consumption In Va
- 15-15 VA, 40...400 Hz 0.9 20 °C)
- Overvoltage Category
- III
- Motor Power Kw
- 75 kW 400 V AC 50/60 Hz AC-4) || 200 kW 380...400 V AC 50/60 Hz AC-3) || 220 kW 415 V AC 50/60 Hz AC-3) || 250 kW 440 V AC 50/60 Hz AC-3) || 257 kW 500 V AC 50/60 Hz AC-3) || 280 kW 660...690 V AC 50/60 Hz AC-3) || 185 kW 1000 V AC 50/60 Hz AC-3) || 110 kW 220...230 V AC 50/60 Hz AC-3)
- [Ui] Rated Insulation Voltage
- 1000 V IEC 60947-4-1 || 1500 V VDE 0110 group C
- [Icw] Rated Short-Time Withstand Current
- 3600 A 40 °C - 10 s || 2400 A 40 °C - 30 s || 1700 A 40 °C - 1 min || 1200 A 40 °C - 3 min || 1000 A 40 °C - 10 min
- Heat Dissipation
- 14-14 W
Offer Sustainability
- Rohs Exemption Information
- Yes
- Mercury Free
- Yes
- Environmental Disclosure
- ENVPEP1505009EN
- Sustainable Offer Status
- Green Premium product
- Reach Regulation
- Reference contains Substances of Very High Concern above the threshold
- California Proposition 65
- WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
- Weee
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- China Rohs Regulation
- Product out of China RoHS scope. Substance declaration for your information.
- Circularity Profile
- ENVEOLI1505009EN
- Eu Rohs Directive
- Compliant
Environment
- Ambient Air Temperature For Operation
- -5-55 °C
- Height
- 206 mm
- Net Weight
- 9.1 kg
- Ambient Air Temperature For Storage
- -60-80 °C
- Protective Treatment
- TH
- Ip Degree Of Protection
- IP20 front face with shrouds IEC 60529 || IP20 front face with shrouds VDE 0106
- Operating Altitude
- 9842.52 ft (3000 m) without derating
- Width
- 213 mm
- Depth
- 219 mm
- Permissible Ambient Air Temperature Around The Device
- -40-70 °C
Modele CAD
traceparts
PobierzInne kategorie
SiłownikiBlokiKable, rury i wężeSprężarkiSterowanieŁączniki i osprzętCylindry i tłokiElektronikaFiltryHVACKomputery przemysłowe i interfejsy HMIOświetlenieTechnika liniowaSilnikiZasilaniePrzeniesienie napęduPompy i zaworyEnergia odnawialnaRobotykaUszczelki, pierścienie i złączaCzujniki i urządzenia pomiaroweNarzędzia i akcesoriaCNCInne