Schneider Electric
LC1G800LSEA
1 / 1
Opis
Końcówka Serii
TeSys Giga high power contactor, 3 poles (3 NO) for category AC-3 applications up to 800A 450kW@440V. It provides a 200-500V AC/DC wide band low consumption electronic coil, PLC output control and embedded highly reliability 1NO+1NC auxiliary contact block (17V 1mA). Designed for demanding applications with maximum operating rates up to 600 cycles per hour and environments until 60°C. It procures high reliability and durability with 5 Mcycles mechanical durability. Local and Remote Contact Wear Diagnosis (CWD) as standard function, continuous monitoring with healthy and alarm indicators. It is possibility to replace switching module (main contacts), enhancement contactor life. Contactor can be fixed in all quadrants, maintenance without removing cables/busbars, and OLR could be directly mounted below contactor. To be used with power connection by bolted connection with cable memory kit and control connections by spring terminals, accessible from front for easy and quick replacement. It provides IP2x protection in Front face with shrouds conforming to IEC 60529 and VDE 0106. It can cover -25°C to 60°C operation ambient air temperature and directly mounted on plate, No derating up to 3000m altitude. The dimension is 324mm x 210mm x 248mm (H x W x D), compact size enables panel space savings. Multi standards certified(CE,CB,CCC,cULus,EAC,KC,RCM,Marine) and Green Premium compliant (RoHs/Reach). Unique QR code provides quick access to complete product data.- Part Number
- LC1G800LSEA
- Tariff Code
- 8536490065
- EAN
- 39121529
- UNSPSC
- 39121529
Metody płatności:
- Najlepsza oferta od:
- Zaufany dostawca Automa.Net
- Dostępność:
- 2 szt.W magazynieZaktualizowano: 08-11-2024
- Gwarancja:
- 12 miesięcy
- Szacowany czas dostawy:
- Na zapytanie
- Stan produktu:
- Nowy, Rynek wtórny
Nowy, Rynek wtórny - Nowy, nieużywany, nieuszkodzony przedmiot bez gwarancji producenta. Przedmiot może być dostarczony bez oryginalnego opakowania lub w zastępczym opakowaniu. Jeśli dostarczono, pudełko mogło zostać otwarte.
Bezpieczny proces płatności
Zasady zwrotu i refundacji
Zasady wysyłki
Gwarancja
Complementary
- Product Certifications
- CB Scheme || CCC || cULus || EAC || CE || UKCA || EU-RO-MR by DNV-GL
- Height
- 388.5 mm
- Power Dissipation Per Pole
- 70 W AC-1 - Ith 1050 A || 42 W AC-3 - Ith 800 A
- Average Impedance
- 0.000065 Ohm
- Auxiliary Contact Composition
- 1 NO + 1 NC
- Connection Pitch
- 70 mm
- Standards
- EN/IEC 60947-4-1 || EN/IEC 60947-5-1 || UL 60947-4-1 || CSA C22.2 No 60947-4-1 || JIS C8201-4-1 || JIS C8201-5-1
- Mounting Support
- plate
- Hold-In Power Consumption In W
- 11.0-11.0 W
- Rated Breaking Capacity
- 5870 A at 440 V
- Associated Fuse Rating
- 800 A aM at <= 440 V for motor || 630 A aM at <= 690 V for motor || 1250 A gG at <= 690 V
- Net Weight
- 17.3 kg
- [Uimp] Rated Impulse Withstand Voltage
- 8 kV
- Inrush Power In Va
- 670-670 VA
- Pole Contact Composition
- 3 NO
- Connections - Terminals
- power circuit: bar 2 - busbar cross section: 52 x 20 mm || power circuit: lugs-ring terminals 1 185-185 mm² || power circuit: bolted connection || control circuit: push-in 1 0.2-2.5 mm² - cable stiffness: solid stranded without cable end || control circuit: push-in 1 0.25-2.5 mm² - cable stiffness: flexible with cable end || control circuit: push-in 2 0.5-1.0 mm² with cable end || control circuit: push-in 0.75-2.5 mm² - cable stiffness: solid stranded without cable end || control circuit: push-in 0.75-2.5 mm² - cable stiffness: flexible with cable end
- Coil Technology
- built-in bidirectional peak limiting
- Operating Time
- 40...70 ms closing || 15...50 ms opening
- Maximum Operating Rate
- 600 cyc/h AC-3 || 600 cyc/h AC-3e || 300 cyc/h AC-1 || 150 cyc/h AC-4
- Mechanical Durability
- 5 Mcycles
- Tightening Torque
- 58 N.m
- Compatibility Code
- LC1G
- Hold-In Power Consumption In Va
- 17.0-17.0 VA
- Width
- 211 mm
- Overvoltage Category
- III
- Depth
- 266 mm
- Maximum Horse Power Rating
- 300 hp at 200/208 V 60 Hz || 350 hp at 230/240 V 60 Hz || 700 hp at 460/480 V 60 Hz || 800 hp at 575/600 V 60 Hz
- Motor Power Kw
- 200 kW at 230 V AC 50/60 Hz (AC-3e) || 335 kW at 400 V AC 50/60 Hz (AC-3e) || 355 kW at 415 V AC 50/60 Hz (AC-3e) || 375 kW at 440 V AC 50/60 Hz (AC-3e) || 425 kW at 500 V AC 50/60 Hz (AC-3e) || 560 kW at 690 V AC 50/60 Hz (AC-3e) || 450 kW at 1000 V AC 50/60 Hz (AC-3e) || 250 kW at 230 V AC 50/60 Hz (AC-3) || 450 kW at 400 V AC 50/60 Hz (AC-3) || 450 kW at 415 V AC 50/60 Hz (AC-3) || 450 kW at 440 V AC 50/60 Hz (AC-3) || 500 kW at 500 V AC 50/60 Hz (AC-3) || 560 kW at 690 V AC 50/60 Hz (AC-3) || 450 kW at 1000 V AC 50/60 Hz (AC-3) || 200 kW at 230 V AC 50/60 Hz (AC-4) || 375 kW at 400 V AC 50/60 Hz (AC-4) || 355 kW at 415 V AC 50/60 Hz (AC-4) || 375 kW at 440 V AC 50/60 Hz (AC-4) || 400 kW at 500 V AC 50/60 Hz (AC-4) || 475 kW at 690 V AC 50/60 Hz (AC-4) || 400 kW at 1000 V AC 50/60 Hz (AC-4)
- [Ui] Rated Insulation Voltage
- 1000 V
- Inrush Power In W
- 390 W
- [Icw] Rated Short-Time Withstand Current
- 5.5 kA - 10 s || 4.6 kA - 30 s || 3.6 kA - 1 min || 2.6 kA - 3 min || 1.7 kA - 10 min
Offer Sustainability
- Rohs Exemption Information
- Yes
- Mercury Free
- Yes
- Environmental Disclosure
- ENVPEP2105013
- Sustainable Offer Status
- Green Premium product
- Pvc Free
- Yes
- Reach Regulation
- Reference contains Substances of Very High Concern above the threshold
- California Proposition 65
- WARNING: This product can expose you to chemicals including: Styrene, which is known to the State of California to cause cancer, and Bisphenol A (BPA), which is known to the State of California to cause birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
- China Rohs Regulation
- X
- Circularity Profile
- ENVEOLI2105013
- Eu Rohs Directive
- Compliant with Exemptions
- Halogen Content Performance
- Halogen free plastic parts product
Environment
- Ambient Air Temperature For Operation
- -25-60 °C
- Ambient Air Temperature For Storage
- -60-80 °C
- Protective Treatment
- TH
- Ip Degree Of Protection
- IP2X front face with shrouds IEC 60529 || IP2X front face with shrouds VDE 0106
- Mechanical Robustness
- vibrations 5-300 Hz 2 gn contactor open || vibrations 5-300 Hz 4 gn contactor closed || shocks 10 gn 11 ms contactor open || shocks 15 gn 11 ms contactor closed
- Color
- dark grey
- Permissible Ambient Air Temperature Around The Device
- -40-70 °C at Uc
Specifications
- [Uc] Control Circuit Voltage
- 200...500 V AC 50/60 Hz || 200...500 V DC
- [Ue] Rated Operational Voltage
- <= 1000 V AC 50/60 Hz || <= 460 V DC
- Range Of Product
- TeSys Giga
- Control Circuit Voltage Limits
- operational: 0.8 Uc Min...1.1 Uc Max (at <60 °C) || drop-out: 0.1 Uc Max...0.45 Uc Min (at <60 °C)
- Contactor Application
- power switching || motor control
- Product Or Component Type
- contactor
- Range
- TeSys
- Utilisation Category
- AC-1 || AC-3 || AC-3e || AC-4 || AC-5a || AC-5b || AC-6a || AC-6b || AC-8b || AC-8a || DC-1 || DC-3 || DC-5
- [Ie] Rated Operational Current
- 1050 A (at <40 °C) at <= 1000 V AC-1 || 800 A (at <60 °C) at <= 440 V AC-3
- Poles Description
- 3P
- Device Short Name
- LC1G
Dokumenty
Data Sheet
PobierzModele CAD
traceparts
PobierzInne kategorie
SiłownikiBlokiKable, rury i wężeSprężarkiSterowanieŁączniki i osprzętCylindry i tłokiElektronikaFiltryHVACKomputery przemysłowe i interfejsy HMIOświetlenieTechnika liniowaSilnikiZasilaniePrzeniesienie napęduPompy i zaworyEnergia odnawialnaRobotykaUszczelki, pierścienie i złączaCzujniki i urządzenia pomiaroweNarzędzia i akcesoriaCNCInne