TeSys Deca changeover contactor , 4P(4 NO) , AC-1 , <= 440V, 125A, 220V AC coil
LC2D80004M5
  • Termin płatności do 90 dni od 500+ dostawców.
  • Rabaty na odsprzedaż do 40%!
Zarejestruj się
€661.10
1
Metody płatności:

Additional Information

Part Number
LC2D80004M5
UNSPSC
39121529
Tariff Code
8536490065
Country of Origin
CZ

Environment

Mechanical Robustness
vibrations contactor open2 Gn, 5...300 Hz || shocks contactor open8 Gn for 11 ms || vibrations contactor closed3 Gn, 5...300 Hz || shocks contactor closed10 Gn for 11 ms
Ambient Air Temperature For Operation
-40-60 °C || 60-70 °C with derating
Height
127 mm
Climatic Withstand
IACS E10
Pollution Degree
3
Net Weight
3.2 kg
Flame Retardance
V1 conforming to UL 94
Ambient Air Temperature For Storage
-60-80 °C
Protective Treatment
TH IEC 60068-2-30
Ip Degree Of Protection
IP20 front face IEC 60529
Operating Altitude
0...9842.52 ft (0...3000 m)
Fire Resistance
850 °C IEC 60695-2-1
Width
207 mm
Depth
158 mm

Contractual warranty

Warranty
18 months

Offer Sustainability

Rohs Exemption Information
Yes
Mercury Free
Yes
Environmental Disclosure
ENVPEP110205EN
Sustainable Offer Status
Green Premium product
Pvc Free
Yes
Toxic Heavy Metal Free
Yes
Reach Regulation
Free of Substances of Very High Concern above the threshold
California Proposition 65
WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov
Reach Free Of Svhc
Yes
Weee
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
China Rohs Regulation
Pro-active China RoHS declaration (out of China RoHS legal scope)
Circularity Profile
N/A
Eu Rohs Directive
Compliant

Complementary

Control Circuit Voltage Limits
0.3...0.6 Uc -40-55 °C drop-out AC 50 Hz || 0.85...1.1 Uc -40-55 °C operational AC 50 Hz
Inrush Power In Va
200-200 VA 50 Hz cos phi 0.75 (at 20 °C)
Coil Technology
without built-in suppressor module
Hold-In Power Consumption In Va
20-20 VA 50 Hz cos phi 0.3 (at 20 °C)
Heat Dissipation
6-10 W 50 Hz

Specifications

Product Certifications
UL || CSA || RINA || CCC || DNV-GL || LROS (Lloyds register of shipping) || BV || UKCA || EAC || CB
Interlocking Type
mechanical
[Uc] Control Circuit Voltage
220 V AC 50 Hz
[Ue] Rated Operational Voltage
power circuit <= 690 V AC 25...400 Hz || power circuit <= 300 V DC
Power Dissipation Per Pole
12.5 W AC-1
Average Impedance
0.8 mOhm - Ith 125 A 50 Hz for power circuit
[Ith] Conventional Free Air Thermal Current
125 A (at 60 °C) for power circuit
Mounting Support
plate || rail
Control Circuit Type
AC 50 Hz
Standards
CSA C22.2 No 60947-4-1 || EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 60947-4-1 || UL 60947-5-1 || CSA C22.2 No 60947-5-1 || GB/T 14048.4
Safety Reliability Level
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Contactor Application
resistive load
Rated Breaking Capacity
1100 A at 440 V for power circuit conforming to IEC 60947
Product Or Component Type
changeover contactor
Irms Rated Making Capacity
1100 A at 440 V for power circuit conforming to IEC 60947
Product Name
TeSys Deca
Associated Fuse Rating
200 A gG at <= 690 V coordination type 1 for power circuit || 160 A gG at <= 690 V coordination type 2 for power circuit
[Uimp] Rated Impulse Withstand Voltage
8 kV IEC 60947
Connections - Terminals
control circuit screw clamp terminals 1 1-4 mm²flexible without cable end || control circuit screw clamp terminals 2 1-4 mm²flexible without cable end || control circuit screw clamp terminals 2 1-2.5 mm²flexible with cable end || control circuit screw clamp terminals 1 1-4 mm²solid || control circuit screw clamp terminals 2 1-4 mm²solid || control circuit screw clamp terminals 1 1-2.5 mm²flexible with cable end || power circuit connector 1 4-50 mm²flexible without cable end || power circuit connector 2 4-25 mm²flexible without cable end || power circuit connector 1 4-50 mm²flexible with cable end || power circuit connector 2 4-16 mm²flexible with cable end || power circuit connector 1 4-50 mm²solid || power circuit connector 2 4-25 mm²solid
Range
TeSys
Pole Contact Composition
4 NO
Device Presentation
preassembled, with prewired power connections
Utilisation Category
AC-1 || AC-3 || AC-3e || AC-4
[Ie] Rated Operational Current
125 A (at <60 °C) at <= 440 V AC AC-1 for power circuit || 80 A (at <60 °C) at <= 440 V AC AC-3 for power circuit || 80 A (at <60 °C) at <= 440 V AC AC-3e for power circuit || 55 A (at <60 °C) at <= 400 V AC AC-4 for power circuit
Maximum Operating Rate
3600 cyc/h 60 °C
Tightening Torque
control circuit 1.2 N.m screw clamp terminals flat Ø 6 mm || control circuit 1.2 N.m screw clamp terminals Philips No 2 || power circuit 12 N.m connector flat Ø 6 to Ø 8 mm || power circuit 12 N.m connector hexagonal 4 mm || control circuit 1.2 N.m screw clamp terminals pozidriv No 2
Electrical Durability
0.8 Mcycles 125 A AC-1 <= 690 V
Mechanical Durability
10 Mcycles
Poles Description
4P
Operating Time
20...35 ms closing || 6...20 ms opening
Overvoltage Category
III
[Ui] Rated Insulation Voltage
power circuit 600 V CSA || power circuit 600 V UL || power circuit 1000 V IEC 60947-4-1
Device Short Name
LC2D
[Icw] Rated Short-Time Withstand Current
135 A 40 °C - 10 min for power circuit || 320 A 40 °C - 1 min for power circuit || 640 A 40 °C - 10 s for power circuit || 990 A 40 °C - 1 s for power circuit
Protective Cover
without

Dokumenty

Data Sheet

Pobierz

Powiązane produkty