1 / 1
thumbnail

Opis

Końcówka Serii
TeSys LRD thermal overload relay, 10A/690V, thermal setting range 7-10A, tripping class 10A, for protection of 3-phase motors 4kW@400V. Differential device with phase failure and load unbalance detection. It provides a thermal adjustement dial, a manual-automatic reset selector, a test selector for simulation of a tripping, reset and stop buttons, a flag indicator and 2 auxiliary contacts 1NO+1NC for fault signalling. Settings are protected by a transparent cover lockable by sealing. Connection by screw clamp terminals, it connects directly to the bottom terminals of 3-pole contactors LC1D09-D38. Mounting on DIN rail or screw fixing, separated from the contactor, with use of a terminal block LAD7B106 (to be ordered separately). Multi standards certified (IEC, UL, CSA, CCC, EAC, ATEX, Marine), Green Premium compliant (RoHs/Reach).
Country of Origin
FR
Part Number
LRD143
Tariff Code
85364900
EAN
3389110822090
UNSPSC
39122330
Metody płatności:
Najlepsza oferta od:
FRZaufany dostawca Automa.Net
Dostępność:
1 szt.
W magazynie
Zaktualizowano: 25-10-2024
Gwarancja:
12 miesięcy
Szacowany czas dostawy:
Na zapytanie
Stan produktu:
Nowy, Rynek wtórny
Nowy, Rynek wtórny - Nowy, nieużywany, nieuszkodzony przedmiot bez gwarancji producenta. Przedmiot może być dostarczony bez oryginalnego opakowania lub w zastępczym opakowaniu. Jeśli dostarczono, pudełko mogło zostać otwarte.
Łącznie 4 części w magazynie od 4 dostawców
Bezpieczny proces płatności
Zasady zwrotu i refundacji
Zasady wysyłki
Gwarancja

Dostępne Oferty (3)

LRD143 product image
Schneider Electric

LRD143

Stan produktu:
Nowy, Rynek wtórny
Dostępność:
1 szt.
W magazynie
Zaktualizowano: 25-10-2024
Oferta od:
GBZaufany dostawca Automa.Net
Szacowany czas dostawy:
Na zapytanie
Gwarancja:
12 miesięcy
1
LRD143 product image
Schneider Electric

LRD143

Stan produktu:
Nowy, Rynek wtórny
Dostępność:
1 szt.
W magazynie
Zaktualizowano: 04-11-2024
Oferta od:
DEZaufany dostawca Automa.Net
Szacowany czas dostawy:
Na zapytanie
Gwarancja:
12 miesięcy
1
LRD143 product image
Schneider Electric

LRD143

Stan produktu:
Nowy, Rynek wtórny
Dostępność:
1 szt.
W magazynie
Zaktualizowano: 04-11-2024
Oferta od:
DEZaufany dostawca Automa.Net
Szacowany czas dostawy:
Na zapytanie
Gwarancja:
-
1
Oferta z czasem realizacji przez producenta
Wysyłka:Na zapytanie
Najlepsza cena:
€24.31

Environment

Product Certifications
IEC || UL || CSA || CCC || EAC || BV || RINA || DNV-GL || LROS (Lloyds register of shipping) || ATEX INERIS || UKCA
Mechanical Robustness
vibrations6 Gn IEC 60068-2-6 || shocks15 Gn for 11 ms IEC 60068-2-7
Standards
EN/IEC 60947-4-1 || EN/IEC 60947-5-1 || UL 60947-4-1 || UL 60947-5-1 || CSA C22.2 No 60947-4-1 || CSA C22.2 No 60947-5-1 || GB/T 14048.4 || GB/T 14048.5 || EN 50495
Climatic Withstand
IACS E10
Ambient Air Temperature For Operation
-20-60 °C without derating IEC 60947-4-1
Dielectric Strength
1.89 kV 50 Hz IEC 60947-1
Ip Degree Of Protection
IP20 conforming to IEC 60529
Flame Retardance
V1 conforming to UL 94
Ambient Air Temperature For Storage
-60-70 °C

Contractual warranty

Warranty
18 months

Offer Sustainability

Environmental Disclosure
ENVPEP080405EN
Reach Regulation
Free of Substances of Very High Concern above the threshold
California Proposition 65
WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov
Reach Free Of Svhc
Yes
Weee
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
China Rohs Regulation
Product out of China RoHS scope. Substance declaration for your information.
Circularity Profile
ENVEOLI0804005_V1
Eu Rohs Directive
Compliant with Exemptions

Complementary

Network Frequency
0...400 Hz
Height
93 mm
[Ith] Conventional Free Air Thermal Current
5 A signalling circuit
Auxiliary Contact Composition
1 NO + 1 NC
Connections - Terminals
control circuit spring terminals 1 1-2.5 mm² solid without cable end || control circuit spring terminals 1 1-2.5 mm² flexible without cable end || power circuit spring terminals 1 1.5-4 mm² flexible without cable end || power circuit spring terminals 1 1.5-4 mm² flexible with cable end
Phase Failure Sensitivity
tripping current 130 % of Ir on two phase, the last one at 0
[Ue] Rated Operational Voltage
690 V AC 0...400 Hz power circuit IEC 60947-4-1
Associated Fuse Rating
4 A gG for signalling circuit || 4 A BS for signalling circuit
Net Weight
0.14 kg
[Uimp] Rated Impulse Withstand Voltage
6 kV
Permissible Current
3 A 120 V AC-15 signalling circuit || 0.22 A 125 V DC-13 signalling circuit
Tripping Threshold
1.14 +/- 0.06 Ir IEC 60947-4-1
Control Type
Red push-button stop || Blue push-button reset
Mounting Support
plate, with specific accessories || rail, with specific accessories || under contactor
Width
45 mm
Depth
72 mm
Temperature Compensation
-20-60 °C

Specifications

Network Type
AC || DC
Thermal Protection Adjustment Range
7-10 A
Relay Application
motor protection
Product Or Component Type
differential thermal overload relay
Product Name
TeSys LRD || TeSys Deca
Thermal Overload Class
class 10A IEC 60947-4-1
Range
TeSys || TeSys Deca
[Ui] Rated Insulation Voltage
power circuit 600 V CSA || power circuit 600 V UL || power circuit 690 V IEC 60947-4-1
Product Compatibility
LC1D12 || LC1D09 || LC1D18 || LC1D25 || LC1D38 || LC1D32
Device Short Name
LRD

Modele CAD

traceparts
traceparts
Pobierz