Schneider Electric
LV846446
1 / 1
- Country of Origin
- FR
- Part Number
- LV846446
- Tariff Code
- 85362090
- EAN
- 3606481155375
- UNSPSC
- 39121601
- Termin płatności do 90 dni od 500+ dostawców.
- Rabaty na odsprzedaż do 40%!
Wyślij zapytanie o cenę
1
Metody płatności:
Specifications
- Network Frequency
- 50/60 Hz
- Network Type
- AC
- Breaking Capacity Code
- H3
- Product Or Component Type
- circuit breaker
- Product Name
- MasterPact MTZ1
- Range
- Masterpact
- Utilisation Category
- category B
- Suitability For Isolation
- yes IEC 60947-2
- Poles Description
- 4P
- Neutral Position
- left
- Device Application
- protection
- Device Short Name
- MTZ1 12 H3
Complementary
- [Ics] Rated Service Breaking Capacity
- 50 kA 440 V AC 50/60 Hz IEC 60947-2 || 50 kA 220...415 V AC 50/60 Hz IEC 60947-2
- Line Rated Current
- 1250 A 40 °C
- [Ue] Rated Operational Voltage
- 690 V AC 50/60 Hz IEC 60947-2
- Mounting Support
- rails || base plate
- Circuit Breaker Ct Rating
- 630 A || 1000 A || 1250 A || 400 A || 800 A
- Maximum Breaking Time
- 25-25 ms
- Depth
- 209 mm
- Control Type
- push-button
- Maximum Closing Response Time
- 50 ms
- Mounting Mode
- fixed
- Breaking Capacity
- 66 kA Icu 220...415 V AC 50/60 Hz IEC 60947-2 || 66 kA Icu 440 V AC 50/60 Hz IEC 60947-2
- [Icm] Rated Short-Circuit Making Capacity
- 145 kA 220/415 V AC 50/60 Hz || 145 kA 440 V AC 50/60 Hz
- [Ui] Rated Insulation Voltage
- 1000 V AC 50/60 Hz IEC 60947-2
- Mechanical Durability
- 10000 cycles with periodic preventive maintenance IEC 60947-2
- Height
- 301 mm
- Width
- 346 mm
- [Uimp] Rated Impulse Withstand Voltage
- 12 kVIEC 60947-2
- [Icw] Rated Short-Time Withstand Current
- 30 kA 3 s IEC 60947-2 || 50 kA 1 s IEC 60947-2 || 50 kA 0.5 s IEC 60947-2
Offer Sustainability
- Rohs Exemption Information
- Yes
- Mercury Free
- Yes
- Environmental Disclosure
- ENVPEP1706010EN
- Sustainable Offer Status
- Green Premium product
- Reach Regulation
- Reference contains Substances of Very High Concern above the threshold
- California Proposition 65
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
- Weee
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- China Rohs Regulation
- Product out of China RoHS scope. Substance declaration for your information.
- Circularity Profile
- ENVEOLI1706010EN
- Eu Rohs Directive
- Compliant
Environment
- Ambient Air Temperature For Operation
- -25-70 °C
- Pollution Degree
- 3 IEC 60947-1
- Ambient Air Temperature For Storage
- -40-85 °C
Modele CAD
traceparts
Pobierz